MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

"Low Pressure FDC" Allowed Upstream of Pump?

5/6/2024

9 Comments

 
I have seen this method of arranging fire suppression components (see attached schematic) several times where I live. The attached is a partial re-creation of the fire water entry schematic for a high-rise building with a fire pump. The system has low and high pressure zones.

The underground parking dry systems are served by the municipal water directly, and the standpipes and aboveground sprinklers are fed by the pump.

Picture

Questions: 1. Can you have a FDC serving the low pressure zones as shown on the suction side of the pump per NFPA-14 6.4.3.1?

2. If not, how should the schematic be arranged instead?

3. What could happen if the Low Pressure FDC were pressurized as shown?

​This project was built under the 2013 editions of NFPA-13, 14, and 20. I am asking because I am beginning design of a sprinkler system for a 22 story high-rise. Thanks for your help.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Is Building Fire Pump Size Affected by Firetrucks?

3/29/2024

11 Comments

 
For multi family buildings, I am being told that for a 4-story building, normally the fire pumps are only 15HP because the standpipes are pressurized by the fire trucks.

My understanding of NFPA 20 is that it would still be required to have a correctly sized fire pump without considering the size of the pump on the local fire trucks.

Is this an industry norm that is allowed by certain AHJ’s or is there code related to multi family that I am missing?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Mix Standpipe Types in Same Building Complex?

3/22/2024

5 Comments

 
In a 15-story highrise building, can the standpipe system be zoned with an Automatic Dry in the 1st -5th floors of the unheated Parking Garage, and an Automatic Wet in the 6th- 15th floors of the heated office portion?

Are we allowed to mix types?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Standpipe Required if Stairs are 470-ft Apart?

1/8/2024

13 Comments

 
Is there any requirement for a standpipe to be installed due to travel distance between stairwells in a 3-story R-2 building?

I am reviewing plans of a U-shaped apartment building with two stairwells on the ends. The distance between them is about 470 feet. We are under the 2018 IFC.

If not required by code, would you as the AHJ consider requiring them for improved fire operations?

Thanks for any feedback.

​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Use 65 or 100 psi for Manual Class III Standpipe?

9/26/2023

6 Comments

 
What is the required pressure for a manual Class III standpipe, 65 or 100 psi?

We're working on a 44'-4" high, 5-story, Type V-B construction building that has a 1-story garage and amenities. The upper floor is R-2. 

The local code says I can have Class III standpipe. As I go through NFPA 13 and NFPA 14, it circles back around to 2-1/2" outlets, except with 2-1/2" x 1-1/2" reducers and caps.

It's going to be fully-sprinklered with a combination standpipe in one stairwell, and just one standpipe riser in the other.

Does this sound correct given the project?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Valve for Hose Connection on Sprinkler System?

9/20/2023

7 Comments

 
We're working on a one-story school. The AHJ (Fire Marshal) is requiring inside 2 1/2-inch hose valves at the exit locations.

These hose valves are fed directly off the wet sprinkler system main - not fed from a dedicated standpipe main.

1. I'm having trouble finding code regarding feeding hose valves off of the wet system main.

2. I'm trying to determine if the pipe, off the main, to these hose valves, needs a control valve installed.

Appreciate the tips and insight. 

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Tips to Handle a Late Standpipe Requirement?

9/18/2023

3 Comments

 
Hello everyone. Looking to get some feedback on a building under construction.

I have a 3-story condo building with 4 stairwells, protected by an NFPA 13 sprinkler system. The condo building is exterior access via corridor which connects the stairwells and is about 20 units total.

There is a single fire sprinkler riser that enters one of the stairwells at the corner of the building and goes vertical to serve all levels. Overall, fairly typical.

Currently, the building is nearing the end of construction and they’re installing drywall.

However, a new Fire Inspector is asking for “more standpipes”, despite the fact that the building does not have standpipes, nor are standpipes required (3 stories, none below grade, and below height threshold to the top floor, etc.) The reason he is requiring them is because he is saying per NFPA 14, you cannot exceed ~200 feet in between standpipes. However, because the building does not require standpipes in the first place, this code section does not seem to make sense.

Of course, I know the AHJ is allowed to require things above and beyond the code but my big issue is that the building is about 80% complete now, and he asked for this on a typical inspection. The design criteria, FP shop drawings, civil plan, etc. were all approved by other inspectors/ AHJ / Reviewers, and has been for a couple of years.

I noticed he seems to be intermixing the word “Standpipe” and “Fire Riser” frequently which makes conversations more difficult. Just looking for some other opinions on this issue and I appreciate any input at all.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Ground Floor Standpipe Hose Connection Req'd?

8/30/2023

13 Comments

 
Regarding: IFC 905.4 Location of Class I standpipe hose connections.

Class I standpipe hose connections shall be provided in all of the following locations: 1.in every required interior exit stairway, a hose connection shall be provided for each story above and below grade plane,. Hose connections shall be located at the main floor landing unless otherwise approved by the fire code official.

Does this mean a standpipe connection is not needed at the ground floor?

I've brought this up to numerous design/build sprinkler subs and they all say a connection is required at the ground floor.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Provide a 750 or 1,000 GPM Pump for Standpipes?

8/22/2023

10 Comments

 
I have a standpipe demand of 750gpm. I am providing a fire pump for the system demand.

Should I be selecting a 750 gpm pump or a 1000 gpm pump, based on adding a safety factor (or other reasoning)?

My sprinkler demand is less than 750 gpm so I would only need to provide the 750 gpm for the standpipes. Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments

Standpipe Required in Stairs 30-ft Apart?

8/17/2023

9 Comments

 
We have a 3-family building with parking garage and three floors over parking for a total of four floors.

According to the IBC, a standpipe is required; my question is - is the standpipe required in all stairs?

We have two stars which are less than 30-feet between the stairs. 

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Thread: Is a Post-Indicator Valve Required?

8/16/2023

0 Comments

 
A thread to discuss more on Post-Indicator Valve requirements from our blog hits series.

Original 2019 article link: www.meyerfire.com/blog/post-indicator-valve-required-for-my-project
Picture
0 Comments

Allowed to Isolate a Hose Valve on Standpipe?

8/8/2023

7 Comments

 
Are you allowed to have a valve off the standpipe feeding a hose valve that is not in the stairwell?

Working in a high rise building with two stairwells. It is dual fed with combination riser standpipes.

On the tenant space there is a hose valve and they want a butterfly on the feed for the hose valve, always thought that was not allowed but couldn’t find it.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Add Hose Connection to the Sprinkler System?

8/7/2023

5 Comments

 
Occasionally, additional hose valve connections are required due to the failure of meeting a 150-ft / 200-ft travel distance to a hose connection.

Can you put a hose valve connection on a sprinkler system without a standpipe?

How do you reflect this in a hydraulic calculation?

A most-remote standpipe would require 500 gpm in a standpipe calculation. Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Can Fire Pump Feed Standpipe But Not Sprinkler?

8/3/2023

26 Comments

 
​I am currently evaluating a 7-story building that is being partially renovated and has an existing standpipe system (2 standpipes), but no sprinklers. My scope was to add sprinklers to the renovated areas, creating a partially sprinklered building.

The lack of pressure is leading the AHJ to require a fire pump due the 100 psi required for the standpipe system.

While the standpipe requires the fire pump, hydrant flow tests indicate that there may be sufficient pressure to supply a sprinkler system.

My question is two-fold. Is there really such a thing as a non-combined sprinkler/standpipe system where they are both required?

They both get their water supply from the same source.

Also, can I evaluate supplying the sprinkler system through a separate riser that tees off before the fire pump, while the fire pump supplies only the standpipe, significantly reducing the size of the pump?

The pump would be sized for 750 gpm total, 500 gpm @ 100 psi to the remote hose connections, and 250 gpm to the second standpipe.

What would that sprinkler calculation look like?

Would the sprinkler calculation remove the hose stream allowance and replace it with the 750 gpm to consider the flow to the pump/standpipes?

The flow potential is there based on the hydrant flow test just not the pressure for the standpipes (and it's close for sprinklers). I'm just wondering if I can give the client and rest of the design team options.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
26 Comments

Handrails Required on Roof Due to Standpipe?

6/22/2023

11 Comments

 
Is it a requirement to have a 42-inch handrail on the edge of the building, due to the standpipe hose connections and this needing to be accessible for the fire department use?

​If it's required, it seems that handrails could apply under IBC 2018 Section 1015.6.
Picture
Thanks in advance.

​​
Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

How to Best Regulate Pressure on Combo Riser?

6/12/2023

7 Comments

 
I'd appreciate some advice.

What's the best way to regulate pressures on a combined sprinkler (OH2) and Class 3 standpipe system?

Obviously the pressures required vary between sprinklers, 2-1/2" standpipe outlets and 1-1/2" hose rack connections.

Pressure regulating valves are expensive to put in on all connections, but I was thinking about using pressure regulating valves for the 2-1/2" standpipe outlets.

I think it's great that we can all share our combined experience on this great website - thanks in advance!

​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Second Valve Required on a Fire Service Main?

6/7/2023

13 Comments

 
I'm working with a city inspector who is adamant that we add a second non-rising stem valve (NRS) in the fire sprinkler service main just before the building. The first valve being in the street at the live-tap location with the roadway box.

Is a valve required on the service main before the building?

The requested location would place the valve under the sidewalk, accessible by T-handle wrench only, prohibiting reliable supervision of any kind.

I can't seem to find any language in NFPA 24 that I can use to argue against the second unsupervised valve. I don't see any value in the position the inspector has taken and requested a copy of the city ordinance requiring the additional valve.

Installing the second valve wouldn't be a huge deal but certainly seems like an unnecessary opportunity for an unsupervised valve to get closed or fail. I would like to hear what others in this community think and if anyone has something to offer.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Approved Pipe Material for Pier/Dock Standpipe?

6/6/2023

11 Comments

 
Has anyone designed a dry manual standpipe for a pier or dock standpipe system in the past?

My question is in regards to materials used for the pipe.

With the tides rising and falling my client is struggling to find an approved material that will allow for enough flexibility.

I walked an adjacent marina to our project and it looked like they used 4" heavy-duty rubber tubing to run out the standpipe lines and transitioned to steel only for the vertical 2 1/2" up to the hose valves on the dock.

Any information to point us in the right direction would be helpful. Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

What Does "Listed for Fire Protection Use" Mean?

5/11/2023

11 Comments

 
What does "listed for fire protection use" actually mean?

The Department of Defense specifications Section 21 13 13 calls for backflow preventers to be "listed for fire protection use".

From what I have found, there is no such specific listing.

Has anyone else heard of this?

Thank you for your input.

​
11 Comments

How to Fix Fluctuating Pressure on Pump Suction?

4/14/2023

5 Comments

 
Hi everyone - thanks for answering my previous questions and for checking out today's as well.

I have three projects all connected to the same central fire pump assembly. It's a huge network of pipe running for miles. 

The client is having a problem with the fluctuating pressure (up and down) on the network for some reason that affects the fire pump's suction pressure. It's in series, and connected to each project.

The client refuses to add a break tank and cut the fluctuation. 

In your experience, is there any alternative solution available? 

Would a pressure relief valve help? What would happen when the pressure is less than design?

Thanks in advance!

​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Separate FDC Required for Each NFPA 14 Zone?

4/13/2023

7 Comments

 
In regards to installing pressure reducing stations for separating areas of the building into different pressure zones, NFPA 14 calls out that the FDC needs to be installed downstream of the pressure reducing valves.

Is a separate FDC required for each pressure zone?

If you provide just one FDC, and the fire department supplies the system for an upper floor of a high-rise, you will exceed the maximum working pressure of the lower systems. I'm not sure how that's possible to avoid.

​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Is Feed to Remote FDC Allowed Under Building?

2/3/2023

13 Comments

 
Can the pipe from a remote FDC at the front of our building route under the building slab to connect to our fire pump room at the back of the building?

The Fire Pump Room is on the basement level.

This is for a six-story hotel with a partial basement along the back portion of the building that is open to a lower grade level in back. Here's a sketch below.
Picture
The fire marshal requires a remote FDC at the sidewalk in front of the building. Our fire pump room happens to be on the opposite side, in the back.

The most straightforward routing is below the building, but it is minimum 60' of run which certainly exceeds the 10' maximum distance allowed for the fire supply from NFPA 13.

Going above the first floor ceiling is challenging given all the interiors/ceilings, public spaces, and glass at the street front.

Given that the FDC pipe is normally-dry and not pressurized, do we have the same restrictions of 10' max below grade?

Even if not, can't say I'm thrilled about having that many joints below our building above. Thanks for your help/thoughts!

​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Standpipes Required for Open Exterior Stair?

2/1/2023

7 Comments

 
Do open (exterior) stairs need standpipes?

If the stairs are more than 50% open, sprinkler protection is not required but what about standpipes?

This building has three stairways. Two are interior and one is open and on the exterior. Standpipes are provided in the two interior stairways.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

PRVs for Static or Flowing Standpipe Over 175 psi?

1/25/2023

8 Comments

 
I have a plan reviewer that is not accepting our proposed design for a manual standpipe calculation.

The calculation shows a required pressure on the fire department pumper truck to be a minimum of 217 PSI.

It has been confirmed that the pumper truck can reach and/or exceed 250 PSI.

The AHJ is requesting that we increase the standpipe from 4-inch to 6-inch, which is not alleviating the higher pressures as we are still above 175 PSI.

This would be a first for me to have to install pressure reducing hose valves on a manual wet standpipe.

My understanding per NFPA-14 (2016) 7.2.3.2 is that this is only an issue when the static pressures on the systems exceed 175 PSI (city static is 113 PSI).

So in essence, we are advising the fire department pumper truck operator to dial his pump up to 217, but this wouldn't be static, as they would be flowing out of the hose valve(s), correct?

​
​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Set Standpipe PRV by Flowing One or All Valves?

1/9/2023

7 Comments

 
We are working on a new (750 gpm) standpipe system.

When testing and setting the field adjustable 2-1/2" PRV hose valves, do you set each one flowing 250 gpm while also flowing 500 gpm elsewhere, to account for the hydraulically calculated design (i.e. lower inlet pressure per NFPA 14-11.5.5.1)?

Or do you just set each one only flowing 250 GPM by itself?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments
<<Previous
Forward>>
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Oct '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT