|
Does anyone know if there's a way to determine the water hammer created when a Fire Pump turns on (Hard Start)?
I have an existing facility that's about 60 years old with a lot of buried fire mains serving about 10-15 systems. They are on city water at about 55 psi static, and they want us to install a Diesel Fire Pump. Everything in the facility is Ordinary Hazard Group 2, with no plans to add on or change occupancy down the road. I've chosen a 1,500 gm diesel fire pump at 49 psi, but the owner is worried about blowing out the underground when the pump kicks on. The churn is 55 psi + the city at static 55 psi + 21% for pump overspeed gives us a maximum of around 133 psi that the pump could ever produce. Although it's not required, we plan to install a main discharge relief valve. Adding 10 psi more for the jockey pump, we could be up around 143 psi, and the owner is not comfortable with this. What are some options? Reduce the pump down to 1,000 GPM, 750 GPM? Reduce the pump's rated pressure to 35 PSI? We would need to adjust the PRV's to relieve at predetermined pressures. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments
What if both main fire pumps discharge into a common header, and the flowmeter/test line is connected to that header?
We had a review comment that the testing arrangement of the pumping system shall be in accordance with NFPA 20 to allow for individual main pump testing without impairing the entire system. Are we in conflict because of the common header? Arrangement attached. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe I have a 9-story residential building with 3 levels of parking. The building requires a fire pump. The AHJ limits us to a design pressure of 60 psi regardless of the available water pressure.
In my case, the available pressure is 85 psi static, and I have a 115 psi fire pump with a 134 psi shutoff pressure. Therefore, I need to reduce the pressure to ensure that the system does not exceed 175 psi. I am planning a double pressure reduction, with the first reducing valve set at 162 psi and the second reducing valve set at 165 psi, with the second valve essentially acting as friction loss only. Assuming a 5 psi pressure increase per floor, would it be acceptable to supply two basement levels below the pressure-reducing valves and reach 172 psi at those levels? I have already noticed that PRVs can have up to 10 psi above their set point under static conditions, which would make the pressure exceed the maximum limit of 175 psi. To eliminate this overshoot, I plan to install a 1-inch pressure relief valve set at 165 psi to ensure that the system pressure never exceeds 175 psi. This solution seems ideal, except in the event that the pressure-reducing valve is unable to stabilize the downstream pressure below 165 psi. In that case, both the pressure-reducing valve and the relief valve would remain slightly open, allowing a continuous flow of water. This could cause the jockey pump to start repeatedly in an attempt to maintain system pressure, potentially resulting in premature wear of the pump. Do you have any advice to help me in my design? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe Is an FDC required on a water storage tank meant to service a fire pump to a commercial warehouse when there is already an FDC connection on the discharge side of the pump piping?
Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe What are the rules when installing a flow meter on a diesel fire pump?
I am seeing recommendations from the manufacturer, such as 5 times the Venturi diameter on the inlet and 2 times the Venturi diameter on the outlet (minimums). What are the 'hard' rules when it comes to installing a flow meter? I do not intend to loop it back to the suction side. This is fed from a 10k water tank with a 6-inch tank discharge flange. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe Section 5.4 NFPA 20 2019 says that: Fire Pump Test Arrangement. Where the water supply to a fire pump is a tank, a listed flowmeter or a test header discharging back into the tank with a calibrated nozzle(s) arranged for the attachment of a pressure gauge to determine pitot pressure shall be required.
I've never seen this type of test header arrangement before. We are installing 2 horizontal split-case pumps, each with a flow rate of 1,250 USgpm. Could you explain how this can be achieved in actuality? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe We are working on a school project that needed a 1,000 gpm fire pump due to three standpipes.
We initially did a hydrant flow test and had a flow of 425 gpm with a static of 55 psi and residual of 50 psi when we started the design. By the time it went out to bid and the contractor performed their own test, they flowed 354 gpm with a static of 55 and a residual of 50. In the first test, we got 1215 gpm at 20 psi, and 1012 gpm in the second test. They went to turn on the pump and were only getting 368 gpm when the building inlet pressure was at 20 psi. We re-did the flow test to see what changed so drastically and again got a static of 51 with residual of 46 at 375 gpm, which would give us 1004 gpm at 20 psi. We have confirmed the two valves between the street and the building are fully open, and we only have about 50 feet of 8” pipe, so the pressure drop to the building is negligible, especially at 368 gpm. We are at a loss for what could be causing such a difference in pressure to the building and such a low flow. Has anyone ever run into an issue like this or have any suggestions of what else we could check out? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe A project we're looking at has a hydrant network that connects to fire sprinkler systems and hydrants.
What would be the process we'd need to consider for the water supply (fire pump and tank capacities)? How does the greatest sprinkler system demand (possibly with hose allowance) relate to the hydrant demand? Are they additive? Not all buildings could have sprinkler systems in the future, so we're questioning the relationship between sprinklered building system demands and the fire hydrant demand. Thanks for your input. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe I wanted to get your thoughts on temporary fire pumps. We are in warm weather season here in MA, and a building wants to use a temporary fire pump to alleviate a fire detail that is on the building.
If this wasn't a high-rise, I honestly feel more inclined, but being that it is, I am more hesitant. I wanted to see if others have used them, and if so, what evidence did you bring to AHJs/Fire Depts? The client shopped around on their own accord and found an industrial end-suction centrifugal pump used for sewage bypass and general construction dewatering, which doesn't seem to be generally used for Fire Protection applications. Thanks in Advance! Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe While NFPA 20 requires a minimum NEMA Type 2 enclosure for fire pump controllers, an alternative view has been expressed that a "NEMA Type 3R" enclosure should be provided where the fire pump room is sprinkler-protected.
The rationale is that activation of the sprinkler system during a fire event may subject the enclosure to water spray similar to rain exposure, for which NEMA Type 3R enclosures are designed to provide protection. What is your thought on this? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe I have two sets of fire pumps (electric - diesel), one with a discharge of 1000 gpm and a pressure of 160 psi (11 bar), and the other with a discharge of 750 gpm and a pressure of 115 psi (8 bar).
How are these supposed to be arranged if they're to be connected in parallel? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe Hi, have you encountered cases where the fire pump is more than 100 ft (30 m) away from the water storage tank (underground)?
I know this isn't ideal. What type of pump or setup do you suggest or recommend in this situation? Thank you. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe I have a DoW project with specifications that require the diesel fire pump flow meter to discharge both into the pump suction and through the test header.
I don't have experience with this setup; in all my previous projects, the diesel fire pump discharged back to the water tank as well as to the test header. I understand that NFPA 20 allows this arrangement (see attached figure from the 2025 edition), but I'm curious how it works in practice for two main reasons: 1. If we close the tank valve during testing, the pump's suction pipe will receive considerable pressure. Will this repeated pressure adjustment after each test impact the longevity of the soft packing, particularly regarding increased water leakage? 2. How does a diesel fire pump cool its motor if the heat exchanger water isn't returned to the tank with fresh cool water coming in? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe I am working on a new building in a rural area that will require sprinkler protection. There is no access to a public water supply, only a 30-100 gpm well on site.
Options for fire suppression water include pumping from a large farm pond 150 feet away or installing a 15,000-gallon water storage tank with a pump. Any thoughts on which option is more feasible and cost-effective, or any alternatives we're not considering? This is in a freezing climate. Thank you in advance! Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe We have a situation where we need to replace a 40-year-old fire pump where the original RPZ is located downstream of the pump. Our current code requires all BFP's upstream of the pump. We are worried that the RPZ will start dumping every time the pump is started.
Does anyone have experience with this that could lend a recommendation? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe I have a plan reviewer requiring calculations (CFH) for a diesel fuel tank because the vent extends further than the UL label is calculated for.
What are the guidelines and how is this calculation performed? The comment: "Provide the required emergency vent capacity, in Cubic Feet Per Hour (CFH), for the primary and secondary fuel tank emergency vents. The venting capacity should be indicated on the UL label on fuel tank. The shop drawings don't list the emergency vent capacity. Note: The capacity listed on the UL label is calculated with the vent within 12 inches of the tank body. If the vent is extended above the tank more than 12-inches, additional calculations are required to account for the additional piping and height above the fuel tank. These calculations are required to be computed by a registered engineer." Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe NFPA 20 – Does the 10 pipe diameter suction requirement have to be one continuous straight run?
I’m looking for clarification on the NFPA 20 requirement for 10 pipe diameters of straight pipe on the suction side of a horizontal split‑case fire pump. NFSA’s Layout Book states: “The length of pipe that needs to be 10 pipe diameters long can be either vertical or horizontal, or some combination of the two, as long as there are no more elbows or tees with a horizontal change in direction in the length of pipe.” This makes sense—but when I look at NFPA 20’s own figures (specifically the “Right and Wrong Pump Suctions” illustration), one of the “Right” examples shows a 90° elbow dropping directly into a tee located right at the pump suction flange. In that configuration, there is no 10‑diameter straight run at all. My questions: Where in NFPA 20 is it actually stated that the 10 pipe diameters must be a single, continuous straight run of pipe? NFSA says the 10 diameters can be vertical, horizontal, or a combination, but NFPA 20’s figure seems to show exceptions. Is NFPA 20’s 10‑diameter rule only triggered by elbows/tees that introduce a horizontal component to the change in direction? (For example, a vertical elbow turning up does not trigger the 10D requirement.) Is this 10‑diameter rule only applicable to horizontal split‑case pumps? Or does it apply to all pump types? I’m trying to reconcile the NFSA explanation with NFPA 20’s figures and determine whether certain configurations truly require the 10D straight run. Thanks in advance for any clarification. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe For a diesel engine–driven fire pump installation, is it permitted by NFPA 20 to route the PRV discharge piping back to the fire pump suction piping, at a point downstream of the suction control valve, particularly in cases where the fire pump test/meter header discharge is already routed back to the pump suction?
Haven't come across this one before - are the horizontal pipes, both suction and/or discharge from a fire pump, required to be seismically braced?
We have seismic bracing required for the building and a review comment to assess bracing for the fire pump suction and discharge. NFPA 20 and 13 both don't seem to speak to it, but perhaps I am missing something. What is code required for seismic on these two runs? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe We have a disagreement on a fire pump installation. Flow test shows 42 psi static, 10 psi residual at 475 gpm from an 8" municipal main.
The fire sprinkler contractor plotted the water supply curve and says it cannot support the specified 1,000 gpm @ 100 psi pump; they're refusing to certify the fire pump without a suction tank or another resolution. The mechanical engineer argues the 8" main at 42 psi static should theoretically deliver way more than 1,000 gpm and questions whether the flow test results accurately represent what the pump will actually see at its suction connection. The steep pressure drop (42 psi to 10 psi in only 475 gpm) seems abnormal for an 8" main. The area has aging infrastructure and known low-pressure issues. Looking for the community's input on: (1) Is the fire sprinkler contractor correct to base their analysis on residual pressure under flow conditions, or should we be looking at static pressure as the mechanical engineer suggests? (2) What's the correct NFPA 20 methodology for evaluating water supply adequacy for a fire pump? (3) When you see such a steep pressure drop in a flow test, what are the typical causes and how would you approach resolving this? What solutions have worked for others dealing with marginal municipal water supplies? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe NFPA 20 (2019) Figure A.4.22.1.3(b) provides a typical diagram indicating pipe for fire pump test connections. In this detail the flow meter loop is shown to return to the suction side of the pump and connect between the fire pump and the suction side OS&Y control valve.
I have seen installations over the years where this connection is placed on the inlet or city side of the OS&Y. This seems to simplify the loop arrangement. Functionally, it would seem to be similar as you would need the OS&Y open to allow some cooling water to reach the circulation relief valve. Is there anything in NFPA 20 that would prohibit this arrangement? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe In order to use pipe and fittings, they need to be "listed for fire protection service."
Do fire pump sensing lines need to meet this listing? What about compressed air lines coming from the air compressor to the air maintenance device, do they need to meet this listing? What about air on the downstream side of the maintenance device? We're curious on different methods to install these components where some fittings & pipe combinations are listed and some aren't (such as copper pro-press for sensing lines). Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe We find that the pressure and flow vary between the nameplate and the shop test curve of the UL-listed fire pump.
What is the allowable tolerance for the difference? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe According to NFPA 20, for any pump installation, the NPSH supplied must be at least equal to the NPSH required for the operating conditions specified.
So does the NPSHₐ need to be continuously maintained at or above the NPSHᵣ during pump operation? During the operation of the fire pump, the liquid level of the fire water tank will keep dropping, which may lead to a situation where the NPSHₐ is lower than the NPSHᵣ (unless the fire water tank is built at a very high elevation). Is this situation permitted? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe For scissor stairs having 2 separate standpipe risers (one of them is a combined sprinkler and standpipe system) running 12 floors, how do we size the pump flow rate required?
Can we argue that we can use a 500GPM pump since the Risers are in close proximity to each other and are within one stairwell, or should we use a 750GPM pump following the NFPA 14 sizing of 500GPM plus 250 GPM per additional riser? Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop Oct '26 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
November 2026
PE PREP SERIES |
RSS Feed
