MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Seismic Req'd on Fire Pump Suction & Discharge?

1/27/2026

2 Comments

 
Haven't come across this one before - are the horizontal pipes, both suction and/or discharge from a fire pump, required to be seismically braced?

We have seismic bracing required for the building and a review comment to assess bracing for the fire pump suction and discharge. NFPA 20 and 13 both don't seem to speak to it, but perhaps I am missing something.

What is code required for seismic on these two runs?

Thanks in advance.

​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
2 Comments

How to Address Fire Pump with Poor Supply?

1/20/2026

17 Comments

 
We have a disagreement on a fire pump installation. Flow test shows 42 psi static, 10 psi residual at 475 gpm from an 8" municipal main.

The fire sprinkler contractor plotted the water supply curve and says it cannot support the specified 1,000 gpm @ 100 psi pump; they're refusing to certify the fire pump without a suction tank or another resolution.

The mechanical engineer argues the 8" main at 42 psi static should theoretically deliver way more than 1,000 gpm and questions whether the flow test results accurately represent what the pump will actually see at its suction connection.

The steep pressure drop (42 psi to 10 psi in only 475 gpm) seems abnormal for an 8" main.
The area has aging infrastructure and known low-pressure issues.

Looking for the community's input on: (1) 
Is the fire sprinkler contractor correct to base their analysis on residual pressure under flow conditions, or should we be looking at static pressure as the mechanical engineer suggests?

(2) What's the correct NFPA 20 methodology for evaluating water supply adequacy for a fire pump?

(3) When you see such a steep pressure drop in a flow test, what are the typical causes and how would you approach resolving this?

What solutions have worked for others dealing with marginal municipal water supplies?


Thanks in advance.
​
Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
17 Comments

Fire Pump Test Loop Connect Upstream of OS&Y?

1/14/2026

5 Comments

 
NFPA 20 (2019) Figure A.4.22.1.3(b) provides a typical diagram indicating pipe for fire pump test connections. In this detail the flow meter loop is shown to return to the suction side of the pump and connect between the fire pump and the suction side OS&Y control valve.

I have seen installations over the years
 where this connection is placed on the inlet or city side of the OS&Y. This seems to simplify the loop arrangement. Functionally, it would seem to be similar as you would need the OS&Y open to allow some cooling water to reach the circulation relief valve.

Is there anything in NFPA 20 that would prohibit this arrangement?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Sensing & Air Lines Need Be "Listed for FP?"

1/13/2026

4 Comments

 
In order to use pipe and fittings, they need to be "listed for fire protection service."

Do fire pump sensing lines need to meet this listing?

What about compressed air lines coming from the air compressor to the air maintenance device, do they need to meet this listing?

What about air on the downstream side of the maintenance device?

We're curious on different methods to install these components where some fittings & pipe combinations are listed and some aren't (such as copper pro-press for sensing lines).

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Tolerance in Pump Curve Nameplate vs. Test?

12/17/2025

8 Comments

 
We find that the pressure and flow vary between the nameplate and the shop test curve of the UL-listed fire pump.

What is the allowable tolerance for the difference?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Keep NPSHₐ > NPSHᵣ At All Times Pump Running?

11/24/2025

6 Comments

 
According to NFPA 20, for any pump installation, the NPSH supplied must be at least equal to the NPSH required for the operating conditions specified.

So does the NPSHₐ need to be continuously
maintained at or above the NPSHᵣ during pump operation?

During the operation of the fire pump, the liquid level of the fire water tank will keep dropping, which may lead to a situation where the NPSHₐ is lower than the NPSHᵣ (unless the fire water tank is built at a very high elevation).

​Is this situation permitted?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Standpipe for Scissor Stair Need 500 or 750 gpm?

11/19/2025

4 Comments

 
For scissor stairs having 2 separate standpipe risers (one of them is a combined sprinkler and standpipe system) running 12 floors, how do we size the pump flow rate required?

Can we argue that we can use
a 500GPM pump since the Risers are in close proximity to each other and are within one stairwell, or should we use a 750GPM pump following the NFPA 14 sizing of 500GPM plus 250 GPM per additional riser?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Need Auto. Standpipes when Fire Pump Provided?

10/22/2025

7 Comments

 
I'm working with a not-so-good flow test on a project that will require a pump because of the flow test.

Where this is getting in the muck is the test flow rate being 712 gpm. The hydrant is about 565 feet from the entry and about 4 feet below finished floor elevation.

This is a 5-story, light hazard with 2 standpipes, so the standpipe demand is 750 gpm.

Flow test had 44 psi static and 34 psi residual with a 0.9 coefficient through the 2.5" outlet. As you know this is a 750 gpm system demand.

The person over me is adamant that we not separate the sprinkler and standpipe systems out - sprinklers and then standpipe - by code when it comes to fire pumps. Even though this is a
low-rise building and all we are technically concerned with is an automatic sprinkler system, and if the responding FD has an engine/pumper, the manual standpipe is in their realm.

The argument is that they don't want a "partially automatic system" on any project; if a fire pump is to be provided for the project, they insist that the standpipe system connected to it must also be automatic.

Back to the 750 gpm thing. At 34 psi, we have 712 gpm, obviously. The thing here is putting a 111 psi, 750 gpm pump on. They're  concerned with the NPSH of the pump and not the duty point or the 150% rated test goals.

(1) When a fire pump is provided to meet the needs of the sprinkler system, are the standpipes required to be automatic?

(2) Is there a requirement here for automatic standpipes that I'm missing? The local jurisdiction has no amendments that affect standpipe requirements different than the model IBC.

(3) Is an automatic standpipe here even achievable given the limits of the water supply, or are we causing more issues in testing down the road?

If it was local, the FMs have already told me that's close enough and we will make up any flow from our trucks. What am I missing here?

I understand clearly that at 20 psi the flow is 1,124 gpm. That's not what I'm trying to accomplish. I am attempting to make the combined system fully automatic per policy at 750 gpm and I'm told it's all good to go.

Help a man at wit's end out here.


TLDR: How would you approach manual vs. automatic standpipes when a fire pump is provided for a 5-story sprinkler system, but a 750 gpm pump could overtax the water supply?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

NFPA Requirements for Campus-Style Fire Pump?

10/15/2025

8 Comments

 
Does NFPA provide guidance on campus-style fire pump design?

Can I provide two water services (one from each building) and serve out to two buildings?

NFPA 20 4.9 implies that campus-style designs are acceptable, but I am not seeing any code lines referencing any further requirements for such a design.

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Acceptance Test Req'd for Replaced Controller?

10/10/2025

8 Comments

 
When a new fire pump controller is installed or replaced, is an acceptance test required?

I suppose I know the answer, but I am looking for a code basis. Thank you.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Is a Sprinkler System with Pump Already Bonded?

10/9/2025

7 Comments

 
Assuming a jurisdiction requires sprinkler pipe to be bonded to the building grounding system, would a sprinkler system fed from a fire pump be considered bonded since it is attached to the pump which is already grounded?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

How to Address Fire Pump Surge/Water Hammer?

10/1/2025

6 Comments

 
TL;DR:
How can surge/water hammer forces be managed in very tall high-rise fire protection system using a single high-pressure pump (~365 psi) without exceeding equipment ratings or NFPA limits?

Question:
Trying to pre-plan in my mind for some upcoming pretty tall highrises where design teams would like to utilize 1 pump in lieu of a high/low multi-pump set up.

I'm coming up with a couple of challenges. For the sake of the problem lets assume the static pressure at the fire pump discharge flange is 365 psi. I'm concerned that fire pump starting methods might create shockwaves/water hammer in high-pressure standpipes whether it be at the start of the pump like across-the-line or end of the curve spike like a wye-delta closed might see.

How concerning is creating surge forces that exceed coupling/PRV valve/Pressure Relief Valve listed ratings?

First reaction for many like me has always been to utilize soft-start but electrically with generators soft-start has a much higher load that has to be accounted for in the generator sizing because of the electrical engineers have to size them as across-the-line because of the bypass & 600% FLA.

Maybe they just have to suffer on their design for FPs to be what it needs to be, but am trying to be accommodating where it makes sense.

Is the general method to rely on a main relief valve in these high-pressure systems?

NFPA 14 limits us to 400 psi but I'm not finding pressure relief valves that are listed high enough for the static pressure of the system i.e. cal-val at 300 psi, Victaulic at 350 psi.

Is anyone utilizing anything like an Amtrol Surge-Trol Tank type products?

Maybe VFD controllers to flatten/lower the static pressure?

Some additional concerns in my mind are PRV hose valves have a 400 psi rated value and some couplings for example Victaulic might be rated at 365 psi. I know there are higher rated couplings on the market, like 500 psi, but if my static pressure on the system is 365 psi, I could see a surge force exceeding the rated values (zero math to support that claim).

I'm struggling to quantify the possible surge force values in the design phase and how to handle that. Reading SFPE Handbook of Fire Protection Engineering 5th edition Water Hammer section pg 1407, it's focused mostly on the closing of valves, and still wrapping my head around if those equations can be applicable/same for pump starting forces.

Thanks in advance.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Maximum Length of Suction from Tank to Pump?

9/10/2025

8 Comments

 
We have a facility with an NFPA 13 Extra Hazard 1 sprinkler system.

The client's proposed location of the water storage tank is approximately 33-ft (10m) higher than the level of the protected building and around 100-ft (30m) away.

The client's proposed pump house is closer to the building, separate from the tank.

My question is - is there a maximum length for the suction feed from the tank to the pumphouse under NFPA rules (13, 20, 22)?

I would rather locate the pump house next to the tank and run the delivery main to the building. Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

When Did NFPA 20 Start Req'ing Exterior Access?

9/8/2025

5 Comments

 
When did NFPA 20 start requiring exterior access to Fire Pumps?

I have an older fire pump, sprinklers had to be tested at 50 years, and when this thing was installed, they had no exit door in the pump room. Current NFPA 20 in our jurisdiction (2016) calls for an exterior access door or access from an enclosed stairway or different exterior exit. The AHJ is aware of that. (Sections 4.13.2.1.1)

Because it's an older system, I'm trying to see if the exterior exit requirement still applies to the system at the time of original approval. The oldest NFPA 20 I can get for free on NFPA Link is 1996. I cannot find this requirement or the "equipment access" section in this code beyond some parts about when a fire pump is installed wholly outside the building.

​Anyone with more experience than me know when this started?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

How to Address UL/FM Strain Relief Connection?

8/15/2025

6 Comments

 
We have a project with a very large Water Storage Tank that requires a 20" suction line from the tank to the suction manifold side of (3) pumps.

Per NFPA 20, at the connection point from the water storage tank to the supply line to the fire pumps as required by NFPA 20 (2019 ed.) 4.16.6.5, where the pump and its suction supply are on separate foundations with rigid interconnecting pipe, the pipe shall be provided with strain relief in Figure A.6.3.1(a).

We can find no manufacturer that has a 20" UL/FM strain relief connection.

We do, although, have a supplier that makes a 20" Flexible Double Expansion Joint, but not UL/FM Listed.

Does anyone know of any other options, or can we just use this flexible expansion joint and get a waiver from the Fire Marshal and EOR?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Use Armored Cable for Controller to Pump?

7/31/2025

5 Comments

 
Is it permitted to install fire pump cables, from the controller panel to the motor, through a cable tray using armored cables, at a height of about 4 inches (10 cm) above the finished floor level?

Are there any code or standard requirements that affect this?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Smaller Underground Than Fire Pump Discharge?

7/18/2025

7 Comments

 
Is there a velocity limitation or velocity direction provided for the design of private fire service mains?

Is it possible (or acceptable) to have an underground main smaller than the size of the discharge pipe required by NFPA 20?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

How "Loose" Can a Diesel Fire Pump Exhaust Be?

7/14/2025

6 Comments

 
What is considered "too loose" for a diesel fire pump exhaust?

I'm referring to the vertical section just above the flex of the engine. 

NFPA just says that you have to secure and shall refer to the manufacturer's instructions, so in this case, it's a Clarke. Thanks in advance. Video is below.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Are Diesel Fire Pumps Subject to Emissions?

6/23/2025

4 Comments

 
In California (and other states), are diesel fire pumps subject to emissions requirements, or are they exempt?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Separate Fire Pump & PRV Tests for Acceptance?

6/19/2025

3 Comments

 
On a fire pump system that has a large PRV on it, should there be a test of just the fire pump, as in the fire pump annual test,​ and also separately a test with the pump through the PRV?

This would ensure that the reduced-pressure standpipe/ sprinklers work ( system acceptance ).

Are these required to be separate tests, or can they be combined?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Is a Strainer Mandatory on Fire Pump Suction?

6/4/2025

7 Comments

 
Is it mandatory to install a strainer at the suction pipe of a fire pump?

​Or are there specific criteria in NFPA for horizontal centrifugal pumps to determine under what circumstances a strainer may not be required at the suction pipe?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

At What Level Should Diesel Tanks Be Refilled?

5/15/2025

4 Comments

 
Diesel fuel tank - how low should I allow the diesel fuel level to drop before I fill the tank with diesel fuel for a fire pump?

Should
I add diesel fuel when the fuel gauge drops to 3/4 full, 2/3 full,​ or 1/2 full?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

NFPA 13R System with 3/4" Domestic + Tank?

5/6/2025

9 Comments

 
I'm designing a 13R system. The building currently has a 3/4" domestic water service. The building is in a location that would make installing a new (larger) service a logistical nightmare.

Is it allowed to connect the 3/4" existing supply to a water storage tank (sized per system/domestic demand) in the basement, then build a residential riser from that?

If this is allowed, do I only take my calculations back to the storage tank?

Do you foresee other problems with this? 

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Pipe Stand, Bracing for 12" Fire Pump Discharge?

4/21/2025

4 Comments

 
Pipe Stands and Bracing I have a 12" fire pump that feeds the "U Turn" in the attached picture. Insurance company is adamant more bracing is needed.

My question is what size pipe stands are required for 12", and do I need more lateral bracing for the surge if the fire pump runs?

All I can find in NFPA 13 only addresses up to 10". Any thoughts or ideas on codes I may be missing would be appreciated.

​Thank you!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
4 Comments

OK to Locate Diesel Fire Pump Fuel Tank Outside?

3/6/2025

9 Comments

 
Does anybody have experience with locating diesel fire pump fuel tanks in exterior locations where the local ambient temperature can drop to below freezing point?

We have an unavoidable situation where we have to locate the fuel tank outside the pump room and we're hoping not to have to build a heated enclosure. NFPA 20 seems to require a heated enclosure, but FM not so much.

I am aware that condensation and fuel deterioration
are issues to be dealt with, but I was thinking maybe good quality thermal lag of the tank and feed/return fuel piping may be sufficient with just a roof structure above the fuel tank.

What are your thoughts on this?

any thanks in advance for your thoughts and advice

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
<<Previous
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Dec '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT