MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Calculation Method for Wet, Manual Standpipe?

10/30/2020

8 Comments

 
We are designing a residential building that will have a manual wet standpipe in a fully-sprinklered building. The building itself is less than 75-feet high.

I need to calculate the wet manual standpipe but would like to check my approach. 

Do I need to calculate the remote standpipe at the two most remote hose valves at 100 psi, 250 gpm each, plus one more hose valve closer to the source at 250 gpm all the way back from a supply at the fire truck?

​Thanks in advance for any feedback.

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments

How to Calculate Vapor Density Against Lower Flammability Limit?

10/29/2020

5 Comments

 
I have a question regarding the need to provide electrical classification for a building using Class 1A flammable liquids.

For this building, 4 gallons could be out in use (located anywhere in the building). The MAQ is 10 gallons. I have discussed this with NFPA 30 committee, the manufacturer, and the AHJ (who is a knowledgeable FPE). They have all determined that even if the MAQ is not exceeded, electrical classification is required if a flammable/explosive mixture could be present.

The NFPA 30 staff directed me to a provision in NFPA 497, Section 5.5, that if the materials will not reach 25% of the lower flammable limit (LFL), this could be utilized to justify not providing classified electrical fixtures.

Does anyone know how to do this calculation, or know of firms that can be hired to do this?

I am an FPE and do not know how to perform it, and I have spoken with other FPE’s who also are not aware. The gentleman I spoke with at NFPA 30 agreed it would be by an industrial hygienist or a chemical engineer and not an FPE.

But does anyone know any that can be hired for a one-off calculation, or have a place where I could learn how to perform it myself (NFPA reference, SFPE article, course, etc.?).

Thank you!

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Standpipes for Existing Building Connected to New, Taller Building?

10/28/2020

7 Comments

 
We have an existing building were the highest occupied floor is less than 30'-0 above fire vehicle access. This building is being renovated.

Part of the renovation involves the construction of a new building to be connect to the existing building. The new building is higher than 30'-0 above fire vehicle access. The exit stairwells in the new building need a standpipe system.
Picture
Does the existing building need a standpipe system since it is connected even though the existing building stairways and floors are not higher than 30'-0 above fire vehicle access?​

​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Do Standpipe Penetrations in Stair Require Seal?

10/27/2020

8 Comments

 
We have a project where the general contractor is stating that the vertical penetration in the stairwell landing, where the standpipes are located, need to be sealed.

They are not asking for it to be a fire-rated seal, but they say some sort of seal will be required. I know on past projects this typically was never a requirement. I have searched NFPA and the IBC with no luck on finding something that would insinuate that no seal is required for the vertical standpipes openings within the rated stair.

Is a seal required for these stair landing penetrations?

Any input is much appreciated.

​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments

Avoid Header in Weekly Test of Diesel Fire Pump?

10/26/2020

4 Comments

 
Are there any drawbacks of testing a diesel-engine fire pump on a main header where other diesel pumps are connected to, instead of a test header?

This is happening in my plant because the test header is is large enough that it would require frequent throttling of test header discharge gate valves for each pump, which has started to wear out and not hold pressure.

Also, what is the minimum flow requirement for weekly diesel pump testing considering the test header doesn't hold? Do we need to run 0%, 100%, and 150% flow test each week?

Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

The 2020 PE Prep Series Final Leaderboard

10/26/2020

0 Comments

 
For all those who took the October 2020 and January 2021 Fire Protection PE Exam - we hope your experience on the exam was overall positive and you hear good news on your exam score soon.

As the 2020 Prep Series wrapped up last week, we are happy to announce the winners for the 20-week 2020 Prep Series season. The top ten winners will receive plaques like the one below. 
2020 PREP SERIES, 1ST OVERALL:
Picture

​2020 PREP SERIES FINALISTS:
Picture

The final standings are computed as the total of all on-time 20-week scores. See the entire final standings here. Thanks and congratulations to all PE examinees on your hard work this year!
0 Comments

Split-Case Fire Pump with Suction Under -1.5 psi?

10/23/2020

7 Comments

 
Can a split-case fire pump be used with a suction that is below negative 1.5 psi of pressure (below 1.0m)?

Would this be acceptable under NFPA 20?

Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Hydrostatic Criteria for Remote FDC in NFPA 25?

10/22/2020

2 Comments

 
We have an account that failed the five year FDC hydrostatic test. The Fire Department Connection is a remote, freestanding FDC. The Fire Marshal is claiming that there is no leakage, however, will not give a pass or fail. 

NFPA 25 (2017) and others reference hydrostatic tests.

6.3.2.1  hydrostatic test 200 psi for 2 hrs or at 50 psi in excess of the maximum pressure where maximum pressure is in excess of 150 psi every five years. (manual standpipe systems and semi-automatic dry standpipe systems, including piping in the FDC)

Annex  6.3.2.1* that mentions a minimum leakage existing under test pressure.

Section 13.8.5 FDC five year hydrostatic testing shall be tested at 150 psi for 2 hrs. There is no mention of minimal leakage allowed.


What is this allowable leakage?

NFPA 24 (2010) Private Fire Mains & Their Appurtenances Section 10.10.2.2.1 requires 200 psi or 50 psi in excess of the system working pressure whichever is greater and maintain that pressure at +/-5 psi for 2 hrs.

Is that my allowable leakage, so that if we lose less than 5 psi or gain no more than 5 psi for 2-hours, that we pass? Wasn't sure if the existing 5-year hydrostatic for underground has leakage that is measured differently from an inside hydrostatic test.
 
Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments

PE Problem #75

10/22/2020

3 Comments

 
A theater has aisles serving its main seating area. One of the aisles has a stair 51 inches wide, with a wall and handrail on one side and fixed seating on the other. If the handrail has a center-line of 4 inches from the wall, what is the effective width of the stair?
a. 37.5 in.
b. 43.5 in.
c. 45 in.
d. 47 in.

Solution | Posted 10/23/20

Read More
3 Comments

Are Regular Fittings Allowed Before Backflow?

10/21/2020

6 Comments

 
I understand that based on most Plumbing Code requirements that black steel pipe is not permitted on the upstream side of a backflow preventer. If pipe is provided between a flange and the backflow, it should be galvanized.

Do fittings, such as an elbow off the flange, need to also be galvanized?

I'm familiar with the Victaulic orange painted cast-iron grooved fittings (Firelock series) as well as ductile iron flanged fittings that seem to be commonly off of a stub-in flange, but I'm wondering if these need anything special like a painted or galvanized finish?

Thanks in advance - really appreciate the community and expertise here.

Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

PE Problem #74

10/21/2020

5 Comments

 
Which of the following occupancies have no difference in maximum permitted travel distance for sprinklered versus unsprinklered buildings?
a. Existing Day Care
b. Residential Lodging
c. Existing Mercantile
d. New Business

Solution | Posted 10/22/20

Read More
5 Comments

What is Pass/Fail Threshold for Fire Pump Test?

10/20/2020

3 Comments

 
As part of acceptance testing for a fire pump we test the installed pump net pressures at various flows (churn, 100%, 150%) and compare that against the factory certified curve for that specific fire pump. 

For these tests, what is the pass/fail threshold?

What would fail this test, and how far off could the installed pump be to fail this test?

As I understand it, the installed fire pump cannot differ from the factory certified curve more than the error in the measurement equipment (the allowed error in gauges, typically 1% of the gauge reading). I'm not sure if that's the proper way to go about it, but was curious if there's a better pass/fail mark I should be looking for with these tests.

Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments

PE Problem #73

10/20/2020

5 Comments

 
​A fire pump's speed is altered from 1760 to 1800 rpm. What is the new head if the original was 120 ft?
a. 115 ft.
b. 123 ft.
c. 126 ft.
d. 128 ft.

Solution | Posted 10/21/20

Read More
5 Comments

What is a Wall Fire Hydrant Used for?

10/19/2020

7 Comments

 
Can you explain what a wall hydrant is used for, and where they would typically be needed?

There are some in older office buildings here in Massachusetts where things freeze.

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

PE Problem #72

10/19/2020

3 Comments

 
​Which of the following is typically not considered obstructed construction for fire sprinkler design?
a. concrete tees with solid members 5 inch wide and 2 ft tall
b. heavy timber construction with 4 inch solid wood beams
c. beam and girder construction with 6 inch steel beams 6 ft apart
d. panel construction with panels under 300 sqft

Solution | Posted 10/20/20

Read More
3 Comments

Prep Series: Week 20 Leaderboard

10/19/2020

 
Last week was week twenty, the final, of our 2020 PE Prep Series - it's 20-weeks worth of mini Fire Protection PE Exams.

If you haven't caught it already, see some thoughts about wrapping up the 2020 PE Prep Season here:  Blog Post


Each week we'll post the leaderboard here with the results of that week's exams. To see full leadership board and more details, visit the PE Prep Series page here.
Picture
The Leaderboard lists the top total scores for the most recent three weekly exams for PE Prep Series participants. 
See the entire scoreboard here.

​
For those following along, next Monday we'll reveal the overall 2020 Season Winners.

Picture

Add FDC to Sprinkler Main or Standpipe Location?

10/16/2020

4 Comments

 
Adding a new Fire Department Connection to an existing building with a 4-inch combination standpipe and 2-1/2 inch mains feeding each level. The standpipe is significantly farther from the new FDC location; however, the 2-1/2 inch feed main is located closer to the new location.

Is it acceptable to connect the 4" FDC pipe to the 2-1/2" main, or do we need to route the pipe back to the standpipe location?

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

PE Problem #71

10/16/2020

2 Comments

 
​Consider the following fire hydrant flow tests conducted at the same elevation:
   Test A: 75 psi Static, 60 psi Residual at 1,200 gpm
   Test B: 65 psi Static, 60 psi Residual at 1,800 gpm
   Test C: 70 psi Static, 45 psi Residual at 1,200 gpm
 Which of the following is true?
a. Test A would provide better pressure than Test B for a 1,500 sqft Light Hazard sprinkler system.
b. Test A would provide better pressure than Test B for a 3,000 sqft ESFR sprinkler system.
c. Test B would always provide better pressure than Test C for any type fire sprinkler system.
d. Both a and c.

Solution | Posted 10/19/2020

Read More
2 Comments

Minimum Required Size for Fuel Oil Day Tank?

10/15/2020

3 Comments

 
NFPA 110 (Standard for Emergency and Standby Power) Section 7.9.2 requires a fuel oil day tank be provided when the main tank is not close enough to the generator to provide sufficient suction head from the prime mover integral fuel oil pump. A day tank is also required if the engine manufacturer's fuel pump static head limits are exceeded when the main tank is at full fuel oil level.

Section 5.5.3 indicates minimum sizing requirements for the main tank, while other documents have maximum sizing allowances for the day tank.

​I cannot find minimum sizing requirements for the day tank in NFPA 110 or other codes and standards. Can someone point me in the correct direction?

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments

PE Problem #70

10/15/2020

6 Comments

 
Determine the required thrust block volume (in cubic feet) for a 45-degree elbow serving a wet 6-inch schedule 10 pipe in sandy silt with a 50% safety factor added. The water within the pipe has a maximum pressure of 140 psi and the block material has a density of 150 pounds per cubic foot.
a. 28 cubic feet
b. 31 cubic feet
c. 44 cubic feet
 d. 63 cubic feet

Solution | Posted 10/16/20

Read More
6 Comments

How to Approach Heat Loss for Sprinkler Pipe?

10/14/2020

5 Comments

 
NFPA 13 states the following:

8.16.4.1.5 Water-filled piping shall be permitted to be installed in areas where the temperature is less than 40 deg F when heat loss calculations performed by a professional engineer verify that the system will not freeze.

For some reason I had always thought that Tyco or some other heat trace provider had a program available to perform these calculations. I feel there is a better way than breaking out my old heat transfer book. Our general consensus is that the risk is relatively high with these types of calculations.

I’m sure you been tasked with this before; what is the best approach to going about these calculations?

Some owners require these calculations to be performed to avoid dry-pipe systems in Florida, even though the location of the iso-thermal line would require dry-pipe systems - I feel this essentially puts all the liability on the engineer.

I'd be curious to see how others would normally approach this. In this case we would look to run calculations to justify that a wet-pipe system would be sufficient without any insulation or heat trace. Thanks in advance.

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

PE Problem #69

10/14/2020

4 Comments

 
An opening within a smoke partition for air transfer requires what type of protective device?
a. fire/smoke damper, minimum 45 minute rating
b. fire/smoke damper, minimum 1.5 hour rating
c. smoke damper, minimum 250 F rated
d. smoke damper, minimum 350 F rated

Solution | Posted 10/15/20

Read More
4 Comments

Min. Font Size & Type for "Out-Of-Service" Sign?

10/13/2020

3 Comments

 
I need to label some deflagration vents as "out-of-service" since they are not being maintained properly and are currently not needed from a code standpoint (as the use of the room has changed). We do not want to remove them as the room may be changed back one day depending on research needs.

Does anyone know if there is a code reference that points to the size of the letters or font type for an out-of-service-tag?

In this case a tag is not practical since it needs to go on a flat panel. I know there are such requirements for exit and "no exit" signs, but I'm not aware of any code guidance for out-of-service signs. Thanks in advance for any feedback.

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments

PE Problem #68

10/13/2020

4 Comments

 
Which of the following would not require a re alarm system?
a. A new second-floor tenant insurance sales office of 60 people
b. An existing four-story fraternity house of 70 people
c. A single-story 80,000 sqft high-hazard warehouse of 90 people
 d. A new single-story 35,000 sqft Class A department store

Solution | Posted 10/14/20

Read More
4 Comments

Storage Capacity for Existing OH Pipe Schedule?

10/12/2020

8 Comments

 
NFPA 13, 2016 Chapter 11 and Chapter 23 provide information on systems that were designed as a Pipe Schedule System (as defined in Section 3.4.9). Section 11.2.2 and 23.7 provide information regarding "Ordinary Hazard" pipe schedule systems, but the storage capabilities in NFPA 13 are based on specifically Ordinary Hazard Group 1 and Ordinary Hazard Group 2 (specifically referencing chapter 13 in this situation for Miscellaneous storage).

I am working in an existing building with an "Ordinary Hazard" pipe schedule system, what are the storage capabilities of the existing system (assuming it does not adequately calculate)?

I did try hydraulically calculating the system just to see if it would work, but there wasn't enough pressure for the existing pipe configuration. A few people I have talked to agreed to stick to OH1 storage capabilities without any upgrades, but I am looking for formal guidance if anyone knows of any.

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments
<<Previous
    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​October '20 Contributors!
    1. SK
    2. Franck
    3. Dan W.
    4. Jonathan ​5. Casey M.
    6. Sean
    7. Colin L.
    8. Mike
    9. Jonathan J
    ​10. Daniel G.


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About