MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Add 5th Apartment Without Sprinkler System?

3/6/2026

3 Comments

 
There is a seemingly willful gap in information in scoping code (IBC) for small group R structures: those on the threshold of IRC/IBC: I am working on an existing 4 unit building where we do not have verified assembly information so the construction is assumed to be V-B.

The owner would like to renovate the existing basement, which is ~50% above grade, into an apartment with a new exterior exit. Three of the units share a common interior exit stairway & the upper ones are served by a fire escape. The 4th unit is built like a townhouse on the rear of the building and does not share any exit components.

If an existing 4-unit residential building (currently not sprinkler protected) adds a 5th unit in the basement — and that unit does not share exit components — is there a code path that allows the project to proceed without installing sprinklers throughout the entire building?

Or, a way to construct the new unit in an existing fire area in a way that does not increase risk (ie: 2-hour separation)?

While the group is a trigger for requiring a system, looking at Chapter 5 as a scoping reference, the total fire area is below the threshold for a sprinkler system in group R-2 with V-B construction.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Design Area for Very Small Extra Hazard Rooms?

3/5/2026

10 Comments

 
Working on the fire protection for a new industrial building. I only have two small areas to protect with sprinklers:
1. 400 ft² hydraulic room
2. 520 ft² transformer room

Both are considered Extra Hazard due to the presence of flammable liquids.

My understanding of NFPA 13 forces me to use 2500 ft² and 0.50 gpm/ft² as the minimum water supply. This will give me 1250 gpm of water to apply to very small rooms, which doesn't make much sense to me.

Am I understanding this right?

Is there a way around it, or a different way of calculating the water supply need?

Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments

FM Requirement for Height of Skylight Sprinkler?

3/4/2026

4 Comments

 
How should the new provisions in FMDS 2-0 (2025 Edition) regarding skylights in storage areas (sections 2.5.4.1.7 and 2.5.4.1.8) be correctly interpreted?

I have two cases based on the flowchart from the snippet below. In both scenarios, sprinklers will be required (even in the case highlighted in the green rectangle, which is optional).

My question is: Should they be installed at the base of the skylights, at the same level as the surrounding ceiling-level sprinklers (similar to Option 2 for skylight protection in the 2023 edition of FMDS 2-0)?

​Or should they be installed inside the skylight, close to the highest point of the skylight (similar to Option 1 for skylight protection in the 2023 edition of FMDS 2-0)?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
4 Comments

Sprinklers Req'd Over Kitchen, Laundry in 13/13R?

3/3/2026

7 Comments

 
We have a 4-story motel that the architect of record stipulated the sprinkler system was to be designed in accordance with NFPA 13R. The building is wood construction with open wood joists. We have a kitchen and several laundry rooms that have suspended ceilings, which would be designed in accordance with NFPA 13 Ordinary Hazard Group I Occupancy.

What about the combustible area above the ceiling in the combustible area above the suspended ceiling in the laundry room?

​Are sprinklers required in this space?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Thank You to Top Feb 2026 Contributors!

3/2/2026

 
Our industry gets stronger every time you share what you know. Thank you to our top February 2026 Contributors! 
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture

When to Extend Design Area to Next Sprinkler?

3/2/2026

3 Comments

 
If the required dimensions of a remote area in either orientation exceeds half the distance to the next sprinkler, does 13 require picking up additional sprinklers?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Dry Sidewall Sprinkler for a 24'-6" Wide Porch?

2/27/2026

5 Comments

 
We have a 24.5' wide porch that needs to be sprinklered. Can we use a dry sidewall sprinkler?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Hose Allowance Req'd for Foam/Water Deluge?

2/26/2026

4 Comments

 
Is a hose stream allowance required for foam/water deluge system, in either NFPA 13 or NFPA 16?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Check Valve or Alarm Check for Small Riser?

2/25/2026

3 Comments

 
Hi, I have a fire pump house separated from the protected building. The main alarm check valve is located in the protected building.

So, for the connection supplying eight (8) sprinklers protecting the fire pump room itself, which will be upstream of the building alarm check valve, as I understand it, I have two options:

Option-1: OS&Y valve + separate alarm check valve assembly + Water flow switch

Option-2: OS&Y valve + check valve+ water flow switch

Is an alarm check valve required, or just a check valve, to serve the 8 sprinklers in the fire pump room if there's a waterflow switch provided either way?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Why Two NFPA 13D Pumps Installed in Parallel?

2/24/2026

8 Comments

 
I have an NFPA 13D system covering an ADA house that has two pumps in the basement. I am struggling to understand why the two pumps were installed in parallel.

Would this just be to increase Total Dynamic Head (TDH)?

Why would you need to increase TDH on a residential system?

Basically
, the customer wants the pumps replaced with new ones because they're old, and I guess what my question really boils down to is what info do I need to figure out to replace these pumps with the correct size pump(s) to satisfy system demand?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Is NFPA 20 10-Diameter Req'mt One Straight Run?

2/23/2026

4 Comments

 
NFPA 20 – Does the 10 pipe diameter suction requirement have to be one continuous straight run?

I’m looking for clarification on the NFPA 20 requirement for 10 pipe diameters of straight pipe on the suction side of a horizontal split‑case fire pump.

NFSA’s Layout Book states: “The length of pipe that needs to be 10 pipe diameters long can be either vertical or horizontal, or some combination of the two, as long as there are no more elbows or tees with a horizontal change in direction in the length of pipe.”

This makes sense—but when I look at NFPA 20’s own figures (specifically the “Right and Wrong Pump Suctions” illustration), one of the “Right” examples shows a 90° elbow dropping directly into a tee located right at the pump suction flange. In that configuration, there is no 10‑diameter straight run at all. My questions: Where in NFPA 20 is it actually stated that the 10 pipe diameters must be a single, continuous straight run of pipe?

NFSA says the 10 diameters can be vertical, horizontal, or a combination, but NFPA 20’s figure seems to show exceptions.

Is NFPA 20’s 10‑diameter rule only triggered by elbows/tees that introduce a horizontal component to the change in direction? (For example, a vertical elbow turning up does not trigger the 10D requirement.)

Is this 10‑diameter rule only applicable to horizontal split‑case pumps?

Or does it apply to all pump types?

​I’m trying to reconcile the NFSA explanation with NFPA 20’s figures and determine whether certain configurations truly require the 10D straight run. Thanks in advance for any clarification.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Best Setup to Refill Area Water Storage Tank?

2/20/2026

7 Comments

 
My fire department is requesting that a new large development in our district install a more robust water storage tank (20,000 gallons more than required by code, along with a wet hydrant adjacent to the tank).

We will use the extra water for fires in the area.

My question is - how can the fire department refill the tank after the nearby fire is under control?

Can we require a FDC adjacent to the tank (5"storz connection) so we can refill the water storage tank quickly from FD tankers?

​There is no public water supply in area-wells only. Thanks!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Obstruction Matter Between Opposing Sidewalls?

2/19/2026

5 Comments

 
I have a 2-story space with a mezzanine. The ceiling above the mezzanine is unconditioned. I need to sprinkler the space and plan to do so using two rows of sidewall sprinklers along the ceiling, pointing towards the middle of the opening.

There is an obstruction running down the middle of the ceiling. (See diagram below for a section view of the space.)

Using Figure and Table 10.3.6.1.3 from NFPA 13 2019, the sidewall sprinklers would need to be spaced 8' to 8'-6" away from the obstruction, which isn't possible.

However, I'm not sure if Figure 10.3.6.1.3 applies to my situation, given that I am spraying from both sides of the obstruction. Section 10.3.6.1.5 might apply to my situation, but the wording makes it seem like it is referring to obstructions along the same wall the sprinkler is on.

Does Section 10.3.6.1.5 apply here?

Thanks in advance!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
5 Comments

Requirements for a Spray Booth in Semi-Trailer?

2/18/2026

3 Comments

 
I have a client who has created a spray finishing area in the back of a semi-trailer. The spray booth area is noncombustible construction, but the surrounding area is typical semi-construction (combustible plywood).

Are there any fire-related code requirements regarding spray finishing in a semi-trailer?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
3 Comments

Draft Curtains, Sprinklers for Vertical Opening?

2/17/2026

3 Comments

 
I am working on a project with non-enclosed vertical floor openings, approximately 6-ft by 10-ft. Looking at FMDS (Factory Mutual Data Sheet) 2-0 and NFPA 13, I found similar language that I need help understanding.

FMDS 2-0 2.5.1.7.4.1: A non-enclosed vertical floor opening does not need a combination of draft curtains and closely spaced sprinklers if
  • (A) The floor opening joins spaces/floor levels that are protected by ceiling sprinklers in accordance with FM Property Loss Prevention Data Sheets, 
  • (B) The horizontal distance between opposite ends of the opening is a min. of 20 ft (6.1 m) in all directions, and
  • (C) The area size of the opening is a minimum of 1,000 ft² (93 m²).

(B) seems to contradict (C) as I read it. (B) seems to be describing an area of 400 ft², which leads me to believe I am misunderstanding something.

NFPA 13 words it differently, but it still didn’t click.

NFPA 13 2022: 9.3.5.4 Large Openings. Closely spaced sprinklers and draft curtains are not required around large openings such as those found in shopping malls, atrium buildings, and similar structures where all adjoining levels and spaces are protected by automatic sprinklers in accordance with this standard and where the openings have all horizontal dimensions between opposite edges of 20 ft (6.1 m) or greater and an area of 1000 ft² (93 m²) or greater.


How should the 20-ft horizontal dimension requirement be interpreted, and how does it work together with the 1,000-ft² minimum area requirement without creating a contradiction?​

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Route Diesel Pump Relief Discharge to Suction?

2/16/2026

3 Comments

 
For a diesel engine–driven fire pump installation, is it permitted by NFPA 20 to route the PRV discharge piping back to the fire pump suction piping, at a point downstream of the suction control valve, particularly in cases where the fire pump test/meter header discharge is already routed back to the pump suction?
Picture
Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Is 65 psi Standpipe OK for Highrise Conversion?

2/13/2026

8 Comments

 
Regarding existing high-rises going through an occupancy change (B to R-2), am I correct that all an engineer has to meet is the 65 psi at the top most floor per IEBC 2021 803.3 Exception 1: "A pump shall not be required provided that the standpipes are capable of accepting delivery by fire department apparatus of not less than 250 gallons per minute (gpm) at 65 pounds per square inch (psi) (946 L/m at 448 KPa) to the topmost floor in buildings equipped throughout with an automatic sprinkler system or not less than 500 gpm at 65 psi (1892 L/m at 448 KPa) to the topmost floor in all other buildings. Where the standpipe terminates below the topmost floor, the standpipe shall be designed to meet (gpm/psi) (L/m/KPa) requirements of this exception for possible future extension of the standpipe."

The code section makes no mention of high-rise difference and the commentary states: "Exception 1 allows the installation of a standpipe system without a fire pump if sufficient water with sufficient pressure could be delivered by means of fire department apparatus pumps to the topmost floor of the building. Under this exception, the location of the work area is irrelevant, and the topmost floor must be considered whether the work area is located at the topmost floor or not."

I
can't find anything that an existing building needs to meet the 100 psi requirement of the IBC, and this would trigger the need for a fire pump if I can meet 65 psi already.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Run Fire Pump with 5-Year Underground Testing?

2/12/2026

4 Comments

 
For the 5-year Underground and exposed piping flow test NFPA 25 7.3.1 - are you to run the fire pump while recording your static, residual, and GPM's?

Without a fire pump, can I utilize the main drain as long as I can flow enough to have the 10% drop between the static and residual, along with using a pitot or a flow meter at the discharge point of the main drain?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Thank you to the Top January 2026 Contributors!

2/11/2026

 
We’re so grateful to our January top contributors for kicking off the year by making this community such a helpful place! Thank you! Here are January's top contributors on the Forum:
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture

Sidewall & Pendent Sprinklers in Same Room?

2/11/2026

7 Comments

 
I'm designing a fire protection wet pipe system for a large gathering space (light hazard occupancy) that's architecturally sensitive. The architect is requesting sidewall sprinklers where possible to minimize visual impact, but the space is too large for sidewalls alone (even extended coverage sidewalls can't adequately reach the center areas).

Can I combine sidewall sprinklers around the perimeter with ceiling pendent sprinklers in the interior to achieve complete coverage throughout the room?

Or does code require me to use one sprinkler type throughout the entire space and prohibit mixing of sidewall and ceiling sprinklers in the same room?

The room is about 35 feet wide and 35 feet long with 13 foot ceilings. Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Strobe Required in Bathroom of R-1 Occupancy?

2/10/2026

2 Comments

 
I'm seeking clarification on where in code it dictates the need for a strobe device in the bathroom of a R-1 occupancy type (for the number of sleeping units required to have visual devices from IFC Table 907.5.2.3.2).

IFC 2024 Section 907.5.2.3.2 states "Habitable spaces in dwelling units and sleeping units" ... shall be provided with visible alarm notification.

The definition of "habitable space" from Chapter 3 is "A space in a building for living, sleeping, eating, or cooking. Bathrooms, toilet rooms, closets, halls, storage or utility spaces, and similar areas are NOT considered habitable spaces".

The 2010 ADA Standards for Accessible Design
, Section 702.1, states that alarms in guest rooms required to provide communication features shall comply with Sections 4-3 and 4-4 of NFPA 72 (1999 edition) or Sections 7.4 and 7.5 of NFPA 72 (2002 edition).

Neither of these sections mandates a strobe in the bathroom.

I would like some context on when this became an industry standard (if it has) and where the code reference driving it comes from. Thanks in advance!!!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
2 Comments

Install Intermediate Temp Sprinklers Throughout?

2/9/2026

14 Comments

 
Our company installs all Intermediate temp. sprinklers throughout buildings as a rule - primarily to avoid the issue of having an ordinary temperature sprinkler end up in a ceiling tile 12 inches from the edge of a diffuser. We're basing this on NFPA-13 (2019) Section 9.4.2.1.

Unless the requirements of 9.4.2.2, 9.4.2.3, 9.4.2.4, or 9.4.2.5 are met, ordinary- and intermediate-temperature sprinklers shall be used throughout buildings.

A.9.4.2.1  It is acceptable to install ordinary-temperature sprinklers throughout a building, intermediate-temperature sprinklers throughout a building, or a mix of ordinary- and intermediate-temperature sprinklers throughout a building.

We've received some pushback on this recently from different AHJ's stating that ordinary temperature sprinklers are to be installed unless higher temperature sprinklers are required - are we interpreting the above code section incorrectly?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
14 Comments

FM Hose Allowance for Auto Retrieval Storage?

2/6/2026

1 Comment

 
I'm designing an in-rack sprinkler system for an automatic storage retrieval system, up to 30 ft tall. I've designed the system per FM Data Sheet 8-34.

The storage commodities are open-top, non-expanded combustible bins. I referenced Section 2.2.7 since this is a mini-load automatic retrieval system. I'm currently using Figure 39 for the in-rack sprinkler layout.

I didn't see anywhere what hose stream allowance to use for in-rack sprinklers only. I currently am using 500 gpm in my design. I attached the FM data sheet 8-34. I based the design from page 85, table 40. Figure 39, unexpanded plastic, 15ft distance between rack sprinklers.

Is 500 gpm hose allowance applicable here?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
1 Comment

Any Fittings or Offsets Allowed Under Building?

2/5/2026

6 Comments

 
Is a fire supply allowed to have any joints, offsets, or fittings underneath the building foundation other than the 90-degree elbow looking up to the flange?

​What's the code or standard basis for allowing or not?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Passive Smoke Wall Vents Allowed with ESFR?

2/4/2026

4 Comments

 
Clarification on Use of Passive Natural Smoke Relief Openings in Walls Below ESFR Sprinkler Elevation

I am requesting clarification regarding the compatibility of 'passive natural smoke relief openings located in exterior walls' of buildings protected by ESFR systems.

NFPA 13 prohibits the use of automatic roof-mounted heat or smoke vents unless they use high-temperature, standard-response sprinklers, due to possible premature venting interfering with sprinkler operation.

Does NFPA 13 or NFPA 92 prohibit or restrict the use of passive, fixed, natural smoke relief openings located in exterior walls (not roofs), which are positioned below the elevation of the ESFR sprinklers and have no operating mechanism (neither automatic nor manual)?

These openings are permanently open (fixed, non-operable), not connected to any fire detection or alarm system, intended solely to allow natural smoke movement during fire events, and located entirely below the sprinkler deflector level.

Looking to see if these openings are acceptable and whether they otherwise would introduce any related concerns on sprinkler performance or smoke control strategy. Much appreciated.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments
<<Previous
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Feb '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT