MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Egress Speed for NFPA 2001 Egress Time Study?

4/9/2025

6 Comments

 
NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems now require an egress time study to show that the design limits exposure to halocarbon agents is no longer than 5 minutes, like FK-5-1-12 (NOVEC 1230), HFC-227ea (FM 200).

This comes from 2018 Edition Section 1.5.14, 2020 Edition Section 4.3.4, and 2022 Edition Section 4.3.4.

Exposure time for inert gas agents will depend on the oxygen levels within the space or room. Concentration below 43 percent shall be permitted where exposure is no longer than 5 minutes. Concentration between 43 and 52 percent shall be permitted where exposure is no longer than 3 minutes.

The annex of NFPA 2001 tells us to review the NFPA Handbook and the SFPE Handbook for more information.

Is anyone doing these calculations, and if so, what exit flow, movement speed, and reaction time would you consider appropriate for spaces using these systems?

​Thanks in advance.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Fire Protection for Dry Rooms for Batteries?

3/11/2025

4 Comments

 
How would you recommend protecting a dry room for battery operations, such as battery testing or packaging?

I've been designing these with dry systems but was curious if there are any codes to omit sprinklers, or if anyone uses clean agent systems?

If you use something alternatively, why do you go that direction?

Moderator's Note: Dry Rooms for batteries have less moisture to avoid corrosion and any chemical reaction for the batteries, which would degrade or reduce performance. Very low moisture is the key for a dry room for batteries.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Replacement Recommendation for NOVEC 1230?

2/26/2025

12 Comments

 
Where are we with the newest clean agents?

I'm running into an interesting scenario where the discussion of the phasing out by 3M of the NOVEC 1230 agent is coming up. I mentioned the competitors to NOVEC 1230 that we're aware of - FK-5-1-12 but they are interested in the next-gen stuff because they don't want to have to redo anything in the near future.

Does anyone have any experience with the Fluoro-K or any other newer, lesser used in the past but now have to look into agents?

I'm aware of Victaulic's Vortex and CO
₂ options, but I'm asking about chemical agents. I look forward to hearing your thoughts and experience.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments

Difference of "Spray Room" vs "Spray Area?"

2/7/2025

5 Comments

 
Our facility is exploring constructing two large (7,200 ft²) facilities for media blasting and coating large steel structures.

The facilities have a ceiling height of approximately 40' and are enclosed via a large roll-up door on one end. The coating systems are categorized as flammable liquids.

There has been some internal debate on how to categorize these per the IFC - as "spray rooms
," which would require fire suppression, or "spraying spaces," which the IFC does not have a prescriptive requirement for fire suppression.

The commentary in the IFC notes that spraying spaces are typically "unenclosed", leading us to lean towards considering these spray rooms, even though they make up the entirety of the building versus a portion of it.

We've reached out to some of the local AHJs, who all seem to agree with the spray room determination. However, the builder of the structures has indicated that most of their installations have not required suppression, even when reviewed by the local AHJ.

​Is categorizing these structures as "spray rooms" the wrong application of the term?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

How to Address Control Areas in Old Buildings?

1/27/2025

8 Comments

 
We are a large metropolitan area with multiple universities that have been operating for decades with high levels of hazardous materials. They want to have separated control areas, but their building construction does not meet current requirements.

On one side we can only enforce the code that these were built to, which was BOCA or even no building code at the time, but on the other hand, there is a reason why control areas came about in the first place.

As they cannot easily upgrade the structure to meet 2-hr requirements, I am planning on just using equivalent level of safety through sprinkler protection and other factors, but was wondering if anyone had experience doing enforcement like this?

Is NFPA 45 enforceable here?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Does NFPA 30, 31, 37 Apply to Diesel Generators?

12/6/2024

6 Comments

 
What NFPA Standard(s) apply for two diesel generator tanks?

Two diesel generators (not emergency or standby), outside (but
have enclosures) with each diesel tank stored underneath, the tank is rectangular in shape and has ~5,000 gallons of diesel fuel.

Looking at the following code path; IMC Chapter 13 for fuel oil piping and storage and IFC Chapter 6--> 605.4 Fuel Oil Storage Systems --> storage above ground in quantities exceeding 660 gallons --> NFPA 31; OR IMC Chapter 9 engine and gas turbine-powered equipment and appliances.

Is this approach correct?

In reviewing both NFPA 37 and NFPA 31, both seem to be applicable
; however, when it comes to "outside aboveground tanks" of this capacity, they both reference NFPA 30 (Section 6.3.3 for NFPA 37 and 7.9.3 for NFPA 31).

So here's the main question - is NFPA 30 applicable here?

I base this on a few things:

1. NFPA 30 Scope section 1.1.2 item 9 - it says it is NOT applicable to "liquids in fuel tanks of... stationary engines" ; and
2. All the boundary and tank to tank separation requirements throughout chapter 22 are based on the diameter of the tank.

This leads me to believe this standard was not written for the type of tanks I have, but instead typical giant circular storage tanks.?

Any insight is greatly appreciated.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Radiation Affect Oxygen Concentration Level?

12/5/2024

2 Comments

 
I have 10+ years of experience in the design, specification, installation, commissioning and operation of oxygen reduction systems. ORS are designed to prevent fires from occurring.

The experimental work undertaken by Xin and Khan, FM Global etc is all concerned with fire suppression, using substantial fires (up to 33 kW) combusting in ambient conditions, and then trying to suppress the resultant fire.

There is a substantial variation in limiting oxygen concentration (LOC) with variation in the received level of radiation at the precombusted surface, which means that the LOC is not a fixed value.

Is there a recognition of the impact of the received level of radiation upon the LOC in the fire engineering community?

​Is there any data or study to back it up?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
2 Comments

Does NFPA 30 Chapter 16 Apply if Under MAQ?

11/7/2024

8 Comments

 
I don’t often dabble in NFPA 30, so I have some specific questions regarding the protection of flammable and combustible liquids that I am having issues finding straight answers to.

I have a sprinklered general-purpose warehouse that stores flammable liquids in container sizes less than or equal to those indicated in NFPA 30 (2021) Table 12.8.1. The total quantities (MAQs) of these containers are also less than those shown in Table 9.6.1.

NFPA 30 (2021) Section 12.8.1 indicates that “The liquid-container combinations listed in Table 12.8.1 shall be permitted to be stored in a general-purpose warehouse without quantity limits if protected in accordance with Chapter 16."

An older version of NFPA 30 (2015) Section 12.8.1(1) indicates that if “the applicable provisions of NFPA 13 for 20ft high storage of Class IV commodities based on the storage configuration of the liquids” is used for protecting these containers, no additional protection criteria is required barring the storage arrangements are in line with the rest of the Section 12.8.

My questions are as follows (per NFPA 13 -2021):

1. If combustible liquids are stored in amounts under the MAQs stated in Section 9.6.1 (and IFC) are the additional requirements of Section 16 (NFPA 30) required, no matter what?

2. If combustible liquids are stored in container sizes less than or equal to those set forth in Table 12.8.1 (NFPA 30), are the requirements of Section 16 still required?

3. Will the storage of these commodities within liquid storage cabinets negate the requirements set forth by Section 16?

The bones of the matter is that I am having a hard time finding a section directly indicating that the requirements of Section 16 are not required. Most if not all sections I can find only indicate that Section 16 is to be used when something is stated.

​Thank you all ahead of time. As always this forum has always been a wealth of information.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

NFPA 30B Classification for Aerosol Spray Cans?

9/27/2024

3 Comments

 
How would you classify metallic spray cans containing aerosol Category 3, where 20.1% of the contents by mass are flammable (specifically, propane-2-ol, isopropyl alcohol, or isopropanol). The product Flash point exceeds 61 (23 – 60) °C (estimated value).

How should I define and handle this product under NFPA 30B?

Is it defined as Aerosol Level 3?

Thank you!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Area Per Unit of A vs. Floor Area Per Extinguisher?

9/23/2024

7 Comments

 
I have never quite understood the difference between the maximum floor area per unit of A and the maximum floor area per extinguisher in NFPA 10 Table 6.2.1.1.

If you are only permitted 6,000 sqft for a 2A (3,000 x 2) how does the 11,250 sqft limitation come into play?

Regardless
, with a 75-ft travel distance maximum, you rarely get anywhere near these limits, but I wonder if anyone knows more. Thanks in advance!

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Fire Suppression for Wood-Fired Pizza Oven?

8/19/2024

11 Comments

 
What are the requirements for fire suppression for a wood-fired pizza oven in a commercial application?

Does a wood-fired pizza oven require anything special, like a Type I hood would? 

If it does require some level of suppression - what's commonly provided? A high-temperature sprinkler on the adjacent fire sprinkler system, a feed from domestic water, or something else?

Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

How to Best Protect Room w/ Oxygen Cylinders?

8/12/2024

16 Comments

 
Is there a preferred method of protecting a room with the sole purpose of storing oxygen cylinders?

FM-200, NOVEC, IG, water mist?

Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
16 Comments

Any Experience with Oxygen-Reduction Systems?

1/23/2024

15 Comments

 
I had a client ask about Oxygen-Reduced Systems (ORS), aka Hypoxic air technology (displacing ambient oxygen in an enclosed environment such as in warehouses). I did a quick read with what's available on Wiki, FM and NFPA. But even my go-to suppression people have hardly encountered these. Testing has been very specific.

Just to increase my knowledge, does anyone here have an practical experience in these?

Are these systems really being installed?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
15 Comments

Is AR-SFFF Allowed to Discharge to Storm Drains?

1/5/2024

10 Comments

 
Are foam system test headers allowed to flow outside and discharge the foam to the ground/storm water?

I see more and more places are banning AFFF from storm water.

What about flowing AR-SFFF to storm?

Any recommendations for capture if its not allowed to be send down the storm drain?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments

An Upper Limit of Room Volume for Clean Agent?

12/14/2023

7 Comments

 
Is there a room volume cut off that you use for clean agent space to make sure that your system will pass the room integrity fan test?

As an extreme example, a 50,000 sf space would probably be better for something like a double interlock preaction system since it would be difficult to make sure that the space is of tight enough construction to hold the clean agent (there will inherently be some leaks in construction despite doing all the recommended practices of gasketing, door threshold blocking, etc).

Thanks in advance!

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

How to Determine the Reserve Amount of Foam?

8/25/2023

6 Comments

 
What is the correct procedure for determining the quantity of the reserve amount of foam, such as FP 3%, for a plant?

I've looked specifically through NFPA 11 and NFPA 16, and can't determine it.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

What is MAQ for a High Hazard H-3 Occupancy?

4/7/2023

11 Comments

 
We have a customer who is building a storage building that includes flammable liquids.

The liquids are Class I-B flammable (as classified under NFPA 30).

I understand that there are limits for the quantity that is allowed within one control area. The Maximum Allowable Quantity (MAQ) is 120 gallons, from NFPA 30 tables. The reading can be increased 100% when a sprinkler system is used. 

So the limit increases to 240 gallons with sprinkler protection.

The number can increase even more when stored in approved liquid storage cabinets or safety cans, which I assume the customer would prefer.

So the final MAQ becomes 240 gallons x 2 = 480 gallons.

The biggest storage room is 2,000 square feet and the customer wants to exceed the MAQ to be above 480 gallons in that storage room.

I have understood that exceeding the MAQ is permitted if the building is classified as an H-3 Occupancy (High Hazard). This occupancy applies more restrictive requirements. 

Is there any numerical value for a new MAQ limit in that case?

My current path is as follows:
Class I-B liquid storage in Storage occupancy > maximum MAQ exceeded > building re-classified as H-3 Occupancy > but where is the new MAQ?

Thanks in advance for your input. I usually design under SFS and CEA standards, and they don't have the same MAQ concept within those standards.

​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Need to Meet High Hazard During Construction?

3/8/2023

3 Comments

 
I am overseeing an NFPA 101, Chapter 43 reconstruction project in an existing storage occupancy that is changing to an industrial/high hazard occupancy.

I am trying to coordinate the means of egress during construction.

Other parts of the building are currently occupied and the new area is less than 50% of the building.

Section 43.7.2.3 requires that the area comply with the applicable new construction chapters of the occupancy. The hazard category per table 43.7.3 leads me to believe this would be a hazard category 1.

The question is: when is the construction area considered to be high hazard?

The contents of the hazardous occupancy will not be present through the entirety of the construction and will only be put in place after the space is ready to be occupied and compliant with all means of egress requirements. During construction, the "high hazard contents room" is just a small room with nothing located inside.

Even with no high hazard contents present until the space is ready to be occupied, does it need to meet the egress requirements of new industrial/high hazard or can it meet the egress requirements of existing for storage?

Thanks.

​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Dampers Required for Room with Clean Agent?

2/20/2023

8 Comments

 
We have a project where we're adding a sound (anechoic) chamber and and protecting it with clean agent.

A question came up as to whether or not dampers are required for the HVAC system that provide supply and return air to the pre-manufactured chamber.

Is an anechoic chamber required to have dampers for limiting the migration of the clean agent?

My thinking is that the clean agent will be activated by an air sampling system, so there should be no meaningful amount of smoke in the chamber.

That said, do the dampers have to be listed for fire/smoke? 

Any help with getting specifics from code or a clearer understanding is always appreciated from the community so thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Alternative Chemical Agent to NOVEC 1230?

2/9/2023

20 Comments

 
3M recently announced they will no longer manufacture NOVEC 1230 by end of 2025 due to the presence of PFAS (https://news.3m.com/2022-12-20-3M-to-Exit-PFAS-Manufacturing-by-the-End-of-2025).

Other similar agents, such as FM-200, have similar environmental concerns due to having HCFCs.

Does anyone know a chemical fire suppression agent that doesn't have CFC or PFAS issues?

I know there is a new NFPA standard (770) on hybrid systems and that the Victualic Vortex is one such system, but not sure what other alternatives are out on the market. Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
20 Comments

How to Calc "In-Use" System That Spans MAQs?

2/2/2023

12 Comments

 
We have a situation where we'll have a piece of equipment in one control area that has a closed-use pipe arrangement with oxidizing gases that goes through different control areas. I've gotten conflicting feedback on this.

How do you figure the amount of "in-use" for each control area? 

Here's a sketch of the concept:
Picture
The equipment that is using the oxygen is on the fourth floor Control Area 2. The tanks that feed it are (2) 200 CF oxygen tanks that are in the second floor Control Area 1.

Which of the following two scenarios is the proper way to tally up the "in-use" quantity for the fourth floor Control Area 2 when comparing against the Maximum Allowable Quantities (MAQs)?

  • Concept #1: The "in-use" amount is only the gas within the equipment itself, and only the gas within the piping to the extent of the control area wall.
  • Concept #2: The "in-use" amount is all of the gas within the equipment itself, and all of the gas within all of the piping, and all of the gas within the (2) oxygen tanks which are actively hooked up to it.
 
My initial gut reaction was that the second option is correct, but now I’m not sure. My reasoning being that if there is an event in 4th floor control area 2 that causes a leak or something like that, it’s not going to just leak out what is physically within the control area… it’s going to leak out everything in all of the piping, all of the equipment, and all of the hooked up tanks. This is all presuming there are no safety devices to stop this from happening.

Assuming my initial gut reaction was correct, is there a way to limit the amount so that it stops at the control area wall?

As in: is there a safety device such as an automatic shutoff valve we can put at the wall such that in the event of a leak or other event, the automatic valve will shut off and then we only have to count the amount of gas between the equipment and the shutoff valve?

I’ve looked in the IBC and its commentary for more info, but couldn’t find anything helpful. I’ve also reached out to a number of different people and there seems to be a variety of different opinions on it.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments

Use Grate Nozzles without Low-Expansion Foam?

12/9/2022

6 Comments

 
I am a fire sprinkler fitter a military installation. Have a question regarding low expansion foam systems with the use of Viking Grate nozzles.

Of course with the concerns of AFFF, there are many issues and decisions flying around about the existing systems we have out here in our aircraft hangars.

Is it acceptable to use the Viking grate nozzles without the low expansion foam?

How does this provide any fire protection?

Obviously, this is not how the system was designed, in my opinion.

Please help me understand how this can be acceptable. I appreciate any and all input. 

​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Alternative to Wet-Pipe Sprinkler in Data Center?

11/25/2022

15 Comments

 
What are some popular solutions for elimination of wet-pipe sprinkler systems in data centers that have installed wet-pipe, VESDA and clean agent systems?

A client wants me to find a solution that will be acceptable to the local Authority Having Jurisdiction to eliminate the wet-pipe sprinkler system in the data center portion of the facility.

We already have the VESDA and clean agent. Are there other recommendations/insight here that might be helpful?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
15 Comments

Does Remote Ansul System Need Monitoring?

11/14/2022

7 Comments

 
We have a stand alone open-air pool pavilion with no attached building.

There is a gas grill under the roof with a very elaborate hood/exhaust/Ansul system. There is no fire alarm system in this pool pavilion.

The Fire Inspector wants the Ansul system monitored by the clubhouse fire alarm system that is 100-ft away.

Is he correct by code?

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Ventilation for Lithium-Ion Battery Off-Gassing?

10/12/2022

11 Comments

 
[Moderator's note: since the first lithium battery question a few weeks ago, we've been flooded with more questions on the topic. We'll do our best to not overburden everyone here but still keep with the topics people are asking. As always, we're thankful for you all!]

Could anybody point out some publications that deal specifically with the ventilation of lithium-ion batteries during off-gassing and how the ventilation should be controlled?

I am familiar with FM Global Loss Prevention Datasheet, and NFPA 855, and I went through some publications such as FIA, however from those I only get that there should be sufficient ventilation.

I am more interested in the off-gas detection part of the design.

The ventilation should be turned on and ESS turned off at the first sign of explosive gasses, but what gasses should those be?

H2, CO, C2H4, CH4, or all mentioned in a combination?

Not sure how to proceed in this.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments
<<Previous
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top April '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 45
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT