MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Heat Loss on Sprinkler Main in Unheated Space?

2/24/2021

8 Comments

 
In our area, wet standpipe/sprinkler pipe running through unheated parking garages always gets heat tracing and insulation. 

On this current project, the general contractor wants us to run a 4-inch main as high as possible to a 7.5-inch thick post-tensioned concrete deck that has a heated space above it and a 24 deg F 1% design temperature below in the garage. They're looping 14-inches of batt fiberglass with a plastic barrier below it creating an envelope around the pipe.

The general contractor is questioning whether the heat tracing is needed. We've got plenty of experience 'tenting' sprinkler pipe in attics but never under concrete. I've suggested they hire a mechanical engineer to do the calculations.

Does anyone have experience with this situation?

​​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments

Help With Old Glycerin Corrosion on Steel Pipe?

2/23/2021

5 Comments

 
Is anyone having problems with steel pipe corrosion after using the older glycerin?

Three year old condominium complex was an NFPA 13R job. About 75% of the pipe is CPVC with exposed basements installed in steel. We hydo-tested four of the buildings in the winter with the glycerin before the buildings had heat so the builder can insulate and sheetrock. We drained out what we could but did not pull any heads in the basement. We didn't think leaving some trapped glycerin in the steel basement piping would be anything to be concerned about.

The basements have developed pin hole leaks and the odor when draining is putrid! I saw the new UL-listed (Freezemaster) antifreeze states, "includes a corrosion inhibitor package".

Any help/advice is greatly appreciated in stopping this attack on the pipe.

​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Clearance Required from Nearest Fire Sprinkler?

2/22/2021

4 Comments

 
I get asked by building owners somewhat frequently - what is the required clearance from a sprinkler?

I understand most typical ordinary storage/miscellaneous storage/office/standard spray sprinklers the clearance is 18-inches.

I also understand ESFR requires 36-inch minimum. I'm trying to understand the big picture and not misspeak. 

What about other sprinklers, like CMDA, CMSA? Is there a rule of thumb across the board?

​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Sprinkler Criteria for Compact Mobile Shelves?

2/18/2021

7 Comments

 
Having trouble getting a good feel for fire sprinkler design criteria for compact, mobile storage shelves. These contain Class I-IV commodities. As I understand it, NFPA 13 only covers light hazard for compact shelving.

The metal shelves have a height of 8-feet, the ceiling height is 26-feet. The room is 3,000 sqft, and the shelves have a footprint within that space of 21 x 30 feet. Any help is appreciated. 

​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

How to Calculate Balcony Sprinklers in NFPA 13R?

2/17/2021

0 Comments

 
We have a four-story project that uses NFPA 13R - 2016 Edition. There are balconies with wood structure that are getting sprinkler protection. The building is in a cold climate.

I'm trying to figure out how to correctly incorporate these balcony sprinklers in the hydraulic calculations while still being efficient in the sprinkler design (there's no fire pump on this and poor city supply).

As I understand it in NFPA 13R, my options are:

(1) NFPA 13R for Dwelling Unit Calculation: use dry-sidewall residential sprinklers (Reliable and Tyco have some) for the balcony. This would then be a 0.05 gpm/sqft calculation over a compartment, up to four sprinklers. 

(2) NFPA 13R for Outside of Dwelling Unit: use dry-sidewall quick response sprinkler for balcony. This would be a 0.10 gpm/sqft calculation for four adjacent sprinklers. The inside sprinklers could still be 0.05 gpm/sqft (per 13R), but the balcony sprinklers need to be 0.10 gpm/sqft (per 13R 7.2.2, 7.2.3).

(3) If the balcony is under 500 sqft and meets a string of conditions, then dry-sidewall quick response sprinklers for the balcony can be for the compartment, up to four sprinklers (per 13R 7.2.3.1). We don't meet this here, because there are large glass slider doors over 50 sqft.

Are there other options here, or is my approach for the first two options appropriate? I could very well be overthinking this. Thanks in advance.

​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
0 Comments

Dampers on Clean Agent Releasing or FA Panel?

2/16/2021

7 Comments

 
We are designing a clean agent system for electrical rooms located within a high-rise building. We are proposing having dedicated clean agent releasing control panels for the electrical rooms, and a separate building Fire Alarm Control Panel.

Is it mandatory to connect fire/smoke dampers (and other shutdown devices) in the electrical room with the clean agent releasing panel, or can these be connected to the building fire alarm system?

Thanks in advance.

​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

CMDA & ESFR Options for Lumber Storage?

2/15/2021

4 Comments

 
We have a 40-foot tall steel construction building, with lumber strapped and stacked, stored in 20-foot high solid piles.

The building is unheated. The building owner has been told by another fire sprinkler contractor that this will require ESFR sprinklers. The owner would prefer a dry pipe system.

We have researched NFPA 13, 2019 edition. It looks as if Chapters 20 and 21 will allow a dry pipe system for this application using CMDA sprinklers.

Anyone else have experience with a scenario like this? What path would you recommend?

​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Is a Jockey Pump Necessary with Small 13R Pump?

2/12/2021

10 Comments

 
We have a small project (13,800 sqft total) which is a four-story, all residential apartment building, using mostly CPVC pipe. The system is under NFPA 13R.

The city supply is very poor, so we will have a fire pump that meets NFPA 20 (as is required by 13R). The pump is an 8-HP, 70 PSI at 75 GPM.

Is a jockey pump necessary with such a small fire pump?

Normally, for our large commercial NFPA 13 projects, a jockey pump is not even a discussion because we don't want the main fire pump (500 - 1,500 gpm) cycling on just to support system maintenance pressure.

For such a small project with a significantly smaller fire pump, is there any harm in not providing a jockey pump?

The question is not based on cost - the pump room is microscopic and we're already having trouble fitting in all the equipment and controllers as is.

Appreciate you all - thanks in advance.

​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
10 Comments

Does Deluge System Use Supply or Demand Calc?

2/11/2021

7 Comments

 
This question pertains to hydraulic calculations at the supply and sprinkler sides of a deluge system:

Our example using rough numbers; the deluge system requires 4,000 gpm based on density requirements through the building. This is the system demand.

Now suppose you have a strong water supply. The water supply actually provides 8,000 gpm based on main capacity testing. This is the system supply.

Now my question is, the pipe is wet up to the deluge valve. There is about 50-feet between the deluge valve and the hazard. It is understood that the system demand is 4,000 gpm, but within the pipe network, is it necessary to size the pipe for a deluge system based on 8,000 gpm on the supply side?

Until the water begins discharging through the deluge nozzles, the 8,000 gpm will be surging through the pipe network to reach the nozzles, correct?

​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Sprinkler Clearance from Washer in Small Closet?

2/10/2021

7 Comments

 
Is there a minimum distance clearance required or recommended from the fire sprinkler and the top of a stacked washer dryer in small closet?

What is the reason for the clearance needed?

I heard that 4” is needed for the clearance rather than the standard 18” in a public area.

​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Change Elevator Hydraulic Fluid Permanently?

2/9/2021

5 Comments

 
I am building out a space that has been vacant for multiple years. The space has a hydraulic elevator that travels 1 floor. There is a sub that is ushering the elevator contractor through the certificate milestone with all the adjacent trades.

He has proposed to change out the Class III-B hydraulic fluid with a Hydro-Safe or equivalent non-combustible fluid in order to work around the NFPA 13 requirement for a pit sprinkler and pit detection to be installed.

My question is, does swapping the petrol-based fluid to a bio-equivalent have any long-term effects on the pump, pistol, seals, gaskets, etc.?

Also, how do I make sure this is the fluid that remains in use for the life of the certificate?

​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Heat Trace or Dry-Pipe System for Loading Dock?

2/8/2021

6 Comments

 
We have a project that includes a 3,500 sqft unheated loading dock. We're in the initial design stages of the project.

Based on your experience would you recommend we specify a heat trace or dry pipe sprinkler system for the loading dock?

​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

Thanks to Top January 2021 Contributors!

2/8/2021

0 Comments

 
A special thank you to those who helped bring in the new year with great feedback and discussion. Here's the top ten commenters for January 2021:
1. Franck
2. CJ Bonczyk
3. Dan Wilder
​4. Jesse
5. Glenn Berger
6. Casey Milhorn
​7. Mike
8. Pete
9. HJ
​10. Wayne Ammons
0 Comments

Sprinkler Zone Req'd for IT Rooms, Elevators?

2/5/2021

7 Comments

 
We have a project where the Authority Having Jurisdiction (AHJ) is requiring zone control valves and dedicated pipe from the standpipe to any IT rooms and sprinklers in elevator shafts.

As a result, we have three zone controls for each floor: (1) the floor sprinkler system, (2) IT rooms, and (3) any sprinklers in elevator shafts.

Is there a code or standard basis for this requirement, or would it be specific to the AHJ?

We're doing the work either way for this project since the AHJ is requiring it, but I would like to know for future projects. Thanks in advance.

​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Software or Calculators for CMDA Sprinklers?

2/4/2021

7 Comments

 
I was wondering if maybe there are some calculators or wizards that guide a selection of CMDA sprinklers for storage applications.

We work with multiple standards (Vds, EN, NFPA) and sometimes it takes a long time to find the right point on the curve out of NFPA 13. It would be great to have a tool to verify that density and multipliers were all chosen properly. Thanks in advance.

​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Assembly Exit Allowed Below Grade Level?

2/3/2021

5 Comments

 
We have a building that used to be a business occupancy but the new occupant wants to now use the occupancy as a church (assembly).

The building is not sprinklered and has no fire alarm system. The new occupant load is 279 people.

The problem is the main entrance is on ground level but the second rear exit is below ground level to exit the building. Is the second rear exit below ground level acceptable?

​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Why Are Standby Fire Pumps Not Required?

2/2/2021

9 Comments

 
If a fire sprinkler systems is designed for "life safety" purposes, should not a primary and standby fire pump be provided? Why are standby pumps not required to improve reliability for these systems?

​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
9 Comments

Backflow Allowed Before Fire Pump Suction?

2/1/2021

8 Comments

 
We have a building with a double check backflow assembly on the suction side of a fire pump. Normally there is a minimum of 10 pipe diameters of vertical plane pipe just before the suction flange.

Is the double check backflow allowed within that distance?

Are there requirements for the backflow to have flanges vs. grooved connections?

A colleague said the control valve should be OS&Y rather than butterfly on the suction side only. Why would this be the case? I would assume the OS&Y would reduce turbulence better than a butterfly, but wouldn't the checks also cause turbulence?

Thanks in advance.

​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments

Sprinkler Required in Dust Collection Ductwork?

1/29/2021

4 Comments

 
I have an exhaust system serving a welding and metal fabrication lab at a school. They will utilize 70% ferrous metal and the remaining will be a mixture of stainless steel, coated steel and aluminum.

The largest duct diameter at the building exit is 30" round. The dust collector will be located on the exterior of the building and in a freezing environment.

Will I need to provide fire suppression within the ductwork both inside and outside as well as within the dust collector?

​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Swimming Pool as Fire Protection Water Supply?

1/28/2021

17 Comments

 
​I am currently working on an existing high rise building that requires a fully automatic sprinkler system to be added and the AHJ is requiring a water tank to be added on the property to serve as a secondary supply.

There is no room for a secondary supply.

Can a pool be used to substitute a water storage tank that will supply the building through fire pumps?

What codes could back up this option?

​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
17 Comments

NFPA 13 Have a Maximum Hanger Rod Length?

1/27/2021

2 Comments

 
Is there a maximum all-thread rod length called out in NFPA 13?

This application isn't for seismic, but a general hanger for pipes 2-inch and under in diameter. Thanks.

​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments

Protect Sprinkler Main in Non-Sprinklered Space?

1/26/2021

7 Comments

 
We are working on a project where a feed main is running through an unsprinklered space to get to a sprinklered area. I've heard that sprinkler pipe needs to be protected by sprinklers so we are trying to figure out if this is an actual requirement or not.

We are talking about putting uprights on the feed main in the unsprinklered area to protect the pipe but I can't find anything in NFPA 13 that actually requires the pipe to be protected.

Does anyone know if this is a requirement or not?

​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

What Distance Under Sprinkler Is No Longer An Obstruction?

1/25/2021

7 Comments

 
When would you consider an obstruction no longer an obstruction, vertically below an ESFR sprinkler?

If the top of storage has to be 36" wouldn't 36" be the cut off? Or do the obstruction rules go the floor?

I have a warehouse that has 2 x 4 light fixtures which are 6'-0" below the roof deck, and am wondering whether these are considered obstructions. Thanks in advance.

​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Best Practice for Flushing of Gridded System?

1/22/2021

4 Comments

 
Regarding fire sprinkler system flushing of a wet-pipe gridded system; NFPA 13 Section 16.6.4 “All branch lines on gridded systems shall be arranged to facilitate flushing”.

We are doing a project which has more than 50 branches in a gridded system.

Do all these branch lines need to be provided with a flushing capability? How is this commonly achieved?

FM Global data sheets say to provide a small nipple between two flexible couplings, assuming removal of the nipple to flush the lines. Are there alternatives to this?

​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Why So Much Sludge in Dry Sprinkler System?

1/21/2021

5 Comments

 
I have a project with a typical compressed air dry sprinkler system in an unconditioned attic space (site is at 44 deg latitude). The system is 22 years old.

Site maintenance person reports that they've had issues with this system for at least 15 years. Frequent and repeated leaks, predominately pin holes in the mains. They try to repair before the system gets wet, although not always in time.

They recently replaced a 3 inch main and found that it was about 30% filled with sludge. Sludge was dark brown, almost clay like, sludge.

Any thoughts on how such a large volume of sludge can accumulate in a dry system? 

Thanks in advance.

​​​​​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments
<<Previous
    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​January '21 Contributors!
    1. Franck
    2. CJ B.
    3. Dan W.
    4. Jesse
    ​5. Gleen B.
    6. Casey M.
    7. Mike
    8. Pete
    9. HJ
    10. Wayne


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About