MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Is Building Fire Pump Size Affected by Firetrucks?

3/29/2024

11 Comments

 
For multi family buildings, I am being told that for a 4-story building, normally the fire pumps are only 15HP because the standpipes are pressurized by the fire trucks.

My understanding of NFPA 20 is that it would still be required to have a correctly sized fire pump without considering the size of the pump on the local fire trucks.

Is this an industry norm that is allowed by certain AHJ’s or is there code related to multi family that I am missing?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Forward Flow Still Required with Fire Pump Test?

3/28/2024

4 Comments

 
Would we still be required to conduct a forward flow test if we have a fire pump downstream and it's tested annually?

Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Fire Hydrant Required for Small Remote Building?

3/27/2024

11 Comments

 
I have a project that is a building 10-ft x 20-ft and is used only for electrical equipment. The building is remotely located, 10 miles from the nearest town.

Would a fire hydrant be required for such a structure?

If not, what code exception would allow the omission of a hydrant?

Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Area of Basement Included for Fire Flow Calc?

3/26/2024

8 Comments

 
We are trying to determine Fire Flow according to Annex of IFC 2022.

It says: B104.1 General The fire-flow calculation area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building, except as modified in Section B104.3. B104.2 Area Separation Portions of buildings that are separated by fire walls without openings, constructed in accordance with the International Building Code, are allowed to be considered as separate fire-flow calculation areas.

Does this mean we need to add in (include) the area of basement to the floor area for Fire Flow?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Irregular-Room Spacing Apply to Only One Wall?

3/25/2024

9 Comments

 
Hello, First post for me here, thanks in advance for the assistance.

In regards to the irregular room and spacing off the walls, I understand the .75 allowance up to 11'3" for the irregular or less than 90 degree wall (NFPA 13, 2019, 10.2.5.2.2).

​However, I have a set of plans I'm reviewing showing four rooms with only one sprinkler and they are applying this section as one wall in each room is irregular - however - the other walls are all regular 90 degree walls but they are exceeding 7'6" off those walls as well.

In my interpretation, they should only be able to apply the above section for the irregular walls only, not normal 90 degree walls.

In this situation I would request an additional head in each room.

Am I missing something here?
Picture
Thank you.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Mix Standpipe Types in Same Building Complex?

3/22/2024

5 Comments

 
In a 15-story highrise building, can the standpipe system be zoned with an Automatic Dry in the 1st -5th floors of the unheated Parking Garage, and an Automatic Wet in the 6th- 15th floors of the heated office portion?

Are we allowed to mix types?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Saunas Considered "Bathrooms" for Sprinklers?

3/21/2024

12 Comments

 
Are Saunas within dwelling units considered bathrooms?

Bathroom: within a dwelling unit, any room or compartment dedicated to personal hygiene, containing a toilet, sink, or bathing capability such as a shower or tub.

​Would saunas fall under the definition of bathroom, since they are dedicated to personal hygiene and contain a bathing capability?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments

How Much to Flow in Forward-Flow Test?

3/20/2024

10 Comments

 
When doing a Forward Flow on a Sprinkler System what is the Minimum # that Fire Marshals are looking for?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe

10 Comments

Why is Soffit Obstruction Rule Not in NFPA 13R?

3/19/2024

7 Comments

 
This question is regarding obstructions to residential upright and pendent sprinklers.

​The 2016 edition of NFPA 13, 8.10.6.1.2 (4) states that obstructions that are located against the wall and that are not over 24 inches in width shall be permitted to be protected in accordance with Figure 8.10.6.1.2(c). This is a pretty sweet rule, as basically your only concern is the sprinkler distance from the wall and not the obstruction dimensions.

However, the 2016 edition of NFPA 13R does not contain this wonderful rule, even though the rest of the obstruction rules are essentially the same.

Any thoughts on why the decision was made not to include this rule in NFPA 13R?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Attach Restraining Strap to C-Clamp Bolt?

3/18/2024

8 Comments

 
Can a seismic restraining strap, when used in conjunction with a C-type beam clamp, have the locknut on the clamp that's used for securing the bolt also be used to secure the seismic strap?
Picture
Any advice would be great - I'm not able to get a cutsheet for the Caddy 300 clamp and a 35 Seismic Restraining Strap. Thanks for any advice.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Sprinkler System Supported Only by Pipe Stands?

3/15/2024

8 Comments

 
I have an existing penthouse that has limited (no) access to the structure at the roof and requires sprinkler coverage. We have a variance from the AHJ to omit sprinklers from non accessible areas.

Has anyone designed a sprinkler system supported from the floor entirely by pipe stands or pipe racks?

I'm aware of the requirements of NFPA 13-16 CH 9.1.1.2.
Picture
The structural engineer on my project is not eager to get involved so alternative options especially pre-engineered options would be great. I'll push back if there aren't better options but looking for any advice.

​I'm also aware of NFPA 13-22 CH 17.5 however 8-0'' tall pipe stands don't seem especially stable. Preferably I'd like a Unistrut solution a contractor can assemble in field and place as required say every 10-0'' ( see pictures)


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

High Temp Sprinklers at Heaters in Greenhouse?

3/14/2024

11 Comments

 
I have a project where a greenhouse is being built onto the side of a hardware store to be used as a seasonal retail space occupied during the warm season only (so they say).

The greenhouse is required to be protected by a dry sprinkler system as a retail space. The greenhouse manufacturer has also indicated that it needs to be heated to prevent snow accumulation on the roof, so there are unit heaters ranging from 150 mbh to 200 mbh.

Since the roof is entirely glass, I am providing intermediate temperature sprinklers throughout. With the unit heaters, I would be required to put intermediate temperature sprinklers within range of the unit heaters output.

Since I am already going intermediate throughout due to solar gain, should I go high temperature at the unit heaters?

I'm thinking about very cold winter day when the sun is shining, so there would be two sources of additional heat on the sprinklers.

​Thank you very much!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Omit Sprinkler in 8" Gap Above Cloud Ceilings?

3/13/2024

5 Comments

 
I have a situation where the AHJ is requiring sprinklers be installed per NFPA 13 2019 9.3.14.3. My design is based on the fact that the bottom of the clouds (suspended ceiling panels) is 0'-8" below the ACT above. There are no openings in the ACT.

While the Engineers at the AHJ seem to agree with my design, they state there is not a specific exception allowing me to omit the sprinklers above the clouds. When referencing NFPA 13 2019 9.7.2, the expanded material states that historically sprinklers are allowed to be omitted from above the clouds where the cloud is less than 12" from the ceiling above.

​My question is, how can this be addressed with the AHJ if the scenario for omission in question is not specifically addressed in the standard?

Picture
Thanks in advance.

​Sent in anonymously for discussion. Click Title to View | 
Submit Your Question | Subscribe
5 Comments

Sprinklers Req'd for Type I-B Highrise Balconies?

3/12/2024

11 Comments

 
A municipality in which we work is denying my request to eliminate sprinklers on exterior patios and balconies because of 2018 IBC paragraph 903.3.1.1.1, which states that just because one does not want sprinklers in a room or area for whatever reason if it is normally required to be sprinklered.

Then, two paragraphs later, Section 903.3.1.2.1 the code specifically addresses balconies and patios and goes on to discuss when sprinklers are required as if they are normally not required.

How can I explain this?

​Also, the building is a highrise, I-B construction.

Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Amount of Pipe Replacement Following Freeze?

3/11/2024

8 Comments

 
We have a project with a large dry system, installed by another contractor, in a mansard roof that froze and broke.

The insurance company has requested us to replace about 1/3 of the system that was obviously damaged but then confirm that there was no damage to the other portions of the piping and sprinklers.

We have suggested replacing the balance of the pipe since a hydro test and a visual inspection is not conclusive that the integrity of some components were not compromised. The AHJ will only state they want an operable system.

Any suggestions on how to proceed?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

When is PIV Not Subject to Mechanical Damage?

3/8/2024

8 Comments

 
According to NFPA 13 2022 Section 16.9.8.2 it is to our discretion what we consider a location " where they are not subject to mechanical damage?

When installing a Post Indicator Valve, what do you consider "not subject to mechanical damage?"

Where is the line drawn, so to speak?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Sprinklers Req'd for PV Panels Over Parking Lot?

3/7/2024

10 Comments

 
Has anyone been asked to or required to provide sprinkler protection for at grade parking with PV panels overtop?

I've been looking online for what has been done in other jurisdictions but I can't find much. There is a lot of discussion about whether PV panels constitute a roof or not for parking garages, but my question is more along the lines of has there been research done to determine if the sprinklers can be expected to activate properly based on pitch/spacing?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments

Why is Fire Pump Pulling the Underground Dry?

3/6/2024

19 Comments

 
Had a review comment come back and needed to clarify.

I have a 14-inch city main with an 8-inch tap to a backflow in a pit. It then runs to four hydrants, and then turns into the building supplying a fire pump.

The flow test at the hydrant near the tap (#1 on image below) was 49 psi static, 47 psi residual at 920 gpm.

The flow test at a hydrant nearest the building (#2 on image below) was 49 psi static, 39 psi residual at 750 gpm.
Picture
The 95 psi @ 1,500 gpm pump in the building is running the underground dry. The plot curve shows 20 psi at 2,100 gpm, however the pump rep said he barely got 500 gpm at 9 pitot and had to shut it down as the gauges went below 20 psi and air was starting to come out of the 2-1/2" hose valves.

This is a mystery to us - we have five different flow tests all ranging from 750 gpm to 1,060 gpm at 40-32 psi residual.

Why would the pump be pulling the underground so low?

They checked all the valves and rebuilt the backflow in the pit. Water meter is good as well (per the utility department). Looking for suggestions. Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
19 Comments

Design Criteria for 16-ft "Autostore" System?

3/5/2024

7 Comments

 
I have an existing storage warehouse designed with ESLO-20 14.5K sprinklers @ .20/1,500 sqft per the cut sheet.

The owner is installing a "Kardex Autostore" system to 16'-0" high.

The existing system calcs out, my question is has anyone designed a system for these "Autostore" systems and do they require anything above an OH2?

My thought is bin box storage above 12' design criteria, what's throwing me off is the design criteria in the cut sheet for the sprinkler. Something tells me the existing heads aren't intended for this type of storage.

​Anything helps, thanks in advance!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

What does "Shall Be Permitted" Mean in NFPA 13?

3/4/2024

6 Comments

 
The difference between "Should" and "Shall" statements is clearly understood by most of us.

How about "Shall be permitted" (for instance NFPA 13, 2019 9.3.2.2)?

​Splitting frog of hairs but I'm guessing that it equates to "May be allowed"?

​How do you interpret this?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Can Floating Dock with Hose Valves Use PVC?

3/1/2024

13 Comments

 
Can a floating dock standpipe with hose valves in the ocean be ran with PVC pipe?

NFPA 307 doesn’t go into detail about materials used but reverts back to NFPA 20, 22 and 24. This is in Florida. The AHJ wants it full of water so I have to issues, it’s too heavy to mount on the side of the dock, it’s not very big and it will be in the water or very close with high tide, so corrosion is inevitable.

Is there anything stating Schedule 40 or 80 PVC is listed or acceptable for such use?


​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe​
13 Comments

Thanks to Top February 2024 Contributors!

3/1/2024

 
Thanks to all the great discussion this past month. Here's our Top Ten Contributors for February 2024:
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top April '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 45
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT