MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Dampers on Clean Agent Releasing or FA Panel?

2/16/2021

7 Comments

 
We are designing a clean agent system for electrical rooms located within a high-rise building. We are proposing having dedicated clean agent releasing control panels for the electrical rooms, and a separate building Fire Alarm Control Panel.

Is it mandatory to connect fire/smoke dampers (and other shutdown devices) in the electrical room with the clean agent releasing panel, or can these be connected to the building fire alarm system?

Thanks in advance.

​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Distance of Nearest FA Speaker to Microphone?

1/20/2021

2 Comments

 
We are working on a mass notification system design. We have always called for any speaker/strobes in close proximity to the microphone to be shutoff during live announcements to prevent feedback.

Is there an actual recommended distance away that all speakers located within this distance should be shutoff? 

​​​​​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments

Heat Detector Capable of Very Cold Environment?

1/13/2021

7 Comments

 
Does anyone have experience installing a heat detector in a cold environment (~ -40 degrees C or F)?

I'm thinking a rate-of-rise detector would probably be the right type based on what I've read but having problems finding a cut-sheet that supports that operating environment. Normally this type of space would get a dry sprinkler but some things have led to trying to think "outside the box" for this project. Thanks in advance.

​​​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Manual Pull Stations Req'd for Overhead Doors?

1/11/2021

5 Comments

 
Under NFPA 72 fire alarm manual pull stations are required on both sides of grouped openings over 40-feet in width and within 5-feet of each side of the grouped openings.

What about grouped loading bays or loading docks? Are manual pull stations required on each side of grouped overhead doors?

​​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Software for Fire Alarm Door/Wall Audibility?

12/4/2020

6 Comments

 
Any good software resources out there for predicting fire alarm signal audibility across walls and doors based on their attenuation values and ambient sound pressure?

​Editors Note: Another fire alarm question today, love it. Keep 'em coming! You can post any fire protection-related question using the "Submit Your Question" link below at any time.

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

Detail Level to Provide for 120V Fire Alarm Power?

12/3/2020

6 Comments

 
As a consultant, what level of detail do you go into for the line voltage (120v) fire alarm plans and wiring?

The line voltage is affected by loads / fuse sizes and affects the disconnect switch size. I'm wondering about the level of detail that an engineer should be showing versus leaving the sizing to the fire alarm and electrical contractors based on their specific system layout requirements.

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

Smoke Detectors Req'd Below Theater Balcony?

12/2/2020

3 Comments

 
We have an auditorium project with a walkway that is constructed beside the seating area at the first and second levels. The second level has been provided with beam-type smoke detectors. 

There is a suspended ceiling below the walkway which is approximately 6-feet (2 m) from the wall. Do we need smoke detectors below this suspended ceiling?
Picture
The design currently has smoke detectors only inside ceiling void spaces below the walkway - is this in compliance with NFPA 72?

The fire alarm contractor is arguing that if a fire originates at the floor level below this walkway, it will be easily detected by the beam detector at the second level due to the smoke buoyancy. 
​
​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments

Is Sprinkler Waterflow Alarm Silenceable?

11/13/2020

3 Comments

 
We have a project where the AHJ is telling us they want the waterflow alarm to be silenceable. Our understanding under NFPA 13-2019 7.7 and 28.2.3.1 is that there must be an audible alarm within 90 seconds (per NFPA 72) and must continue until the flow stops, not when the fire alarm system silences the flow.

Are we correct in that waterflow is a non-silenceable event, by code?

​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments

PE Problem #68

10/13/2020

4 Comments

 
Which of the following would not require a re alarm system?
a. A new second-floor tenant insurance sales office of 60 people
b. An existing four-story fraternity house of 70 people
c. A single-story 80,000 sqft high-hazard warehouse of 90 people
 d. A new single-story 35,000 sqft Class A department store

Solution | Posted 10/14/20

Read More
4 Comments

PE Problem #67

10/12/2020

7 Comments

 
A forensic investigator is trying to determine approximate timing of events after a re within a hospital basement. A quick response sprinkler (RTI of 50 m^1/2s^1/2), Ordinary Temperature (65 deg C) was within a room (2.2 m high ceiling) that has an initial temperature of 70 deg F and was exposed to a ceiling plume at 190 deg F traveling at 2.3 m/s. Approximately how long should it have taken the sprinkler to activate? 
a. 1 seconds 
b. 15 seconds 
c. 23 seconds 
d. 35 seconds

Solution | Posted 10/13/20

Read More
7 Comments

Fire Alarm Devices Req'd to Have Address Label?

10/5/2020

4 Comments

 
Are initiation devices (smoke detectors, manual pull stations, duct detectors) required to have individual labels on them showing the device address?

The project in question is military and is also subject to UFC requirements.

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

PE Problem #57

9/28/2020

4 Comments

 
​Determine the visibility (in meters) for a light reflecting exit sign with smoke that is produced by pyrolysis of plastic. Assume the smoke has a mass concentration of 0.09 grams per cubic meter.
a. 4.4 m
b. 7.6 m
c. 11.7 m
d. 20.2 m

Solution | Posted 09/29/20

Read More
4 Comments

PE Problem #49

9/16/2020

7 Comments

 
The activation time (in seconds) of a standard response (RTI of 85 m^1/2s^1/2), Ordinary Temperature (65 deg C) heat detector within a room that has an initial temperature of 22 deg C and exposed to a ceiling plume at 78 deg C traveling at 2.3 m/s is most nearly what time?
a. 10 s
b. 36 s
c. 54 s
d. 82 s

Solution | Posted 09/17/20

Read More
7 Comments

Pass/Fail Criteria for Fire Alarm Battery Test?

9/14/2020

4 Comments

 
NFPA 72 requires a battery test be run including removal of the main power supply, waiting the full-length standby time, then activating the fire alarm system for the full alarm time. After the alarm time, the battery voltage is required to be tested.

What is the pass/fail mark for the battery voltage?

In theory, if the battery output still has 20.4 V, then the last appliance on a NAC circuit would still get a minimum of 16 V and everything still functions correctly. I just can't seem to find a code reference whether 20.4 V is the correct voltage to use (where a voltage reading below 20.4 V fails the battery). 

Thanks in advance.

​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Residential Hoods in Classroom Req' Monitoring?

9/4/2020

8 Comments

 
I am a municipal fire inspector. We have a new high school, fully sprinklered, that has residential stoves in a classroom. These are protected with UL300A hoods.

Are these hoods required to be connected to the fire alarm?

Common sense would indicate that if there was a fire hot enough to release the UL300A system, that the building occupants could be in danger and the fire alarms should activate, however, I cannot find a code reference for this. The architect is saying the stoves are residential so only residential requirements apply.

​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments

PE Problem #34

8/20/2020

6 Comments

 
A forensic study is being prepared using a fire model to attempt to verify whether arson could be a cause. If the fire's origin room ceiling ceiling (3.3 m) has an initial temperature of approximately 22 deg C and is exposed to a plume along the ceiling at approximately 85 deg C traveling around 1.2 m/s, what is the activation time (in seconds) for a quick response (RTI of 40), Ordinary Temperature (75 deg C) sprinkler?
     a. 61 s
     b. 67 s
     c. 210 s
     d. 230 s

Solution | Posted 08/21/20

Read More
6 Comments

PE Problem #18

7/29/2020

2 Comments

 
​Determine the response time index (in ft^1/2 s^1/2) for a 160-degree F heat detector with a listed spacing
of 30 feet.
a. 44
b. 80
c. 169
d. 180

Solution | Posted 07/30/20

Read More
2 Comments

Duct Detectors Shut Only Associated Damper or All Dampers? How Should they be Controlled?

7/8/2020

7 Comments

 
Should return air duct smoke detectors associated with a fan system close only the associated damper and shutdown the fan or close all dampers on the system (including supply return spill and outside air)?

How should outside air and spill air fire smoke dampers be controlled? Should these to be controlled by fire alarm?

Thanks in advance.

​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe


7 Comments

Adjacent Rooms Require Strobe Synchronization?

6/16/2020

2 Comments

 
I’m confused by the field of view intent of NFPA 72 for synchronization.

Do two adjacent rooms with a door between them each with strobe coverage require synchronization?

​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments

Determine if Ceiling Has Wall-Mount Fire Alarm?

6/4/2020

4 Comments

 
Question for AHJs and inspectors:

Do you occasionally see fire alarm strobes mounted on the ceiling that appear to be for a wall-mounted orientation (e.g. they are rectangular and have the word "FIRE" on the side)?

I know some of these are actually for ceiling mounted applications but I've run across some that are wall-mounted only. I think the Wheelock brand might be an example? Stuff like this is hard to tell in the field for an existing building (with no documented cut sheets for what was submitted).

Anyone have tips or tricks for this?

​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Still Class A Fire Alarm with Long Run to Strobe?

2/28/2020

1 Comment

 
What constitutes a "drop" on a fire alarm Class A circuit?

NFPA 72 12.3.8.1 (2016 Edition): 
"The outgoing and return circuit conductors shall be permitted in the same cable assembly, enclosure, or raceway only under the following conditions:
(1)
 For a distance not to exceed 10 feet where the outgoing and return conductors enter or exit the initiating device, notification appliance, or control unit enclosures.
(2)
 Single drops installed in the raceway to individual devices or appliances.
(3)
 In a single room not exceeding 1000 sq ft in area, a drop installed in the raceway to multiple devices or appliances that does not include any emergency control function devices."


For this project in question an appliance is located approximately 12 feet away from a device. The circuit runs from the device, out 12 feet horizontally, down a wall a few feet, then back up and back to the first device. 

In my opinion, the outgoing and return circuit exceeds 10 feet so it would not qualify as Class A wiring. However, the contractor is calling this a "single drop" to an individual appliance, so he feels it qualifies as exception (2) above.

Is this considered a single drop if it's only serving an individual appliance?

​​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
1 Comment

Shutdown CRAC Unit for Clean Agent Discharge?

2/20/2020

6 Comments

 
Our common CRAC Units (Cooling, Refrigeration and A/C) for data centers only cool the air directly from the data center and back into the data center.

Do these need to be shutdown with the use of a total-flooding clean agent system? 

If the CRAC unit is only exchanging air within the same space then I'm not sure what harm it would do if it's running during or after clean agent discharge. I'm curious if I'm off the mark here, thanks!

​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

Elevator Relay Location With No Machine Room?

1/23/2020

5 Comments

 
When an elevator does not have an elevator machine room, where should the fire alarm relays for the elevator be located?

​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Underground Gate Valves Need Monitoring?

1/20/2020

2 Comments

 
Do underground gate valves for fire main water supplies have to be monitored and supervised?

​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments

Requirements for Exterior Fire Alarm Strobes?

11/25/2019

1 Comment

 
Are there special requirements for fire alarm strobes on the exterior parts of the building (courtyards, etc)? Thinking that direct sunlight may interfere with the strobe.

​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
1 Comment
<<Previous
    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​January '21 Contributors!
    1. Franck
    2. CJ B.
    3. Dan W.
    4. Jesse
    ​5. Gleen B.
    6. Casey M.
    7. Mike
    8. Pete
    9. HJ
    10. Wayne


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About