MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Standpipe Hose Connection Allowed in Corridor?

7/16/2025

8 Comments

 
Looking for clarification on NFPA 101 Section 30.2.5.1.2, which provides an exemption for exit staircase remoteness. NFPA 14, however, requires a standpipe system in all exit staircases.

We are working on an 18-floor high-rise apartment building that has two exit staircases eligible for the remoteness exemption outlined in 30.2.5.1.2.

I would like to install a standpipe riser in the exit access corridor leading to exit staircases instead of within the exit staircase, as NFPA 14 specifies.

Is locating the hose valves in the corridor in-between allowed rather than within the exit enclosure?

Picture
Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Will Brass Clappers Hold 12 psi of Supervisory Air?

6/26/2025

3 Comments

 
We're installing a manual dry standpipe system that will have 12 psi of supervisory air. This is my first supervised dry standpipe in [redacted by original author to protect author's extreme age] years in the industry.

The FDC has 3 brass clappered snoots supplying a 6" main.

I'm assuming we'll need to install a 6" rubber-faced check valve near the FDC to hold the air. However, you know what they say about 'assuming'.

Therefore, I'll ask the FP Pro world: Is there any chance those brass clappers will hold 12psi of air?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Reason to Omit Bypass Around PRVs in Series?

5/29/2025

4 Comments

 
A fire pump supplies a combination riser for sprinklers/standpipes.

Between the combination riser and the fire pump, there are 2 pressure-reducing CLA VA in series. It appears that 2024 NFPA 14 10.2.5 requires a bypass assembly for these 2 CLA VA.

​Is there any reason or justification to delete this bypass around the CLA VA assembly?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

Are Standpipes Required for Open Stairs?

4/22/2025

7 Comments

 
I have a new build design where standpipes are required due to height. An area of the building is lower than the height requirement. This area has a partial floor above another that looks over an open emergency planning room area. There are two open stairs at either end. They appear to be the only stairs.

I view these as required interior exit stairs, and since I have never found an exemption to areas of the building below the height requiring standpipes, I've included hose connections.

The Architect wants them removed because they are open stairs.

Are standpipes allowed to be omitted for open stairs in the portions below the required heights for a standpipe?

Any thoughts or input are appreciated.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Clearance Required for Hose Valve in Cabinet?

4/3/2025

7 Comments

 
Valve Cabinet Clearance Is there any code which requires a minimum clearance for a valve cabinet. I typically say 36” or 1m (in Canada) as that is the typical clearance required in front of equipment. But I have been asked if there is any supporting reference for this specifically and I can’t find one for hose cabinets.

Just hose valves in a cabinet or where they are not to obstruct egress. Looking to see what others use and if they have any code reference.

Along a similar thought - does anyone know if equipment access clearances can overlap, or do they need to be independent of each other?

Can clearances overlap?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Does Every 2½" Hose Valve Always Need 100 psi?

3/31/2025

9 Comments

 
NFPA 14 states that "hydraulically designed standpipe systems shall be designed to provide the waterflow rate required by Section 7.10 at a minimum residual pressure of 100 psi at the hydraulically most remote 2½" hose connection and 65 psi at the outlet of the hydraulically most remote 1½" hose connection" (Section 7.8.1, 2019 edition).

So does this mean if you have a single 2½" hose valve on your project, you need 100 psi residual at that valve?

This seems pretty cut and dry, but I've been thinking about this, and off the top of my head, I can list at least 5 projects that had 2½" hose valves and less than 100 psi of static pressure on the ground floor, let alone 100 psi residual on the 4th floor.

Not only projects that I have personally witnessed get signed off, but also buildings I have found myself walking through that have had gauges on the hose valves, and those gauges more often than not (in my area at least) read a pressure less than 100 psi static.

Are these just all designed wrong?

​Or am I missing something?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Interior Hose Valve if Over 130-ft from Exterior?

3/18/2025

8 Comments

 
I am designing a wet pipe fire sprinkler system in a one story Group B occupancy (16-ft high). The building is about 90,000 sqft in area. The building will be fully sprinklered with two zone control valve assemblies.

The fire department is asking to add fire hose valve cabinets as the interior remote areas of the building are more than 130 feet from an exterior door, only citing that its required by IBC 2021.

Is this correct?

I can't find this requirement. Any help is appreciated.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Is Sprinkler/Standpipe Combined or Separate?

3/3/2025

9 Comments

 
What specific criteria or code references determine whether a standpipe system is classified as 'separated' rather than 'combined'?

I've seen AHJs state that even though the sprinkler system and the standpipe have separate vertical riser assemblies (control valve, check valve, and supervision), they are fed from the same underground supply (one underground service main) and will still be considered combined.

We are working on a project where the AHJ has deemed the building 'partially sprinklered,' requiring the standpipe to be upgraded from 4" to 6" (which would necessitate a pump) but only if it is a combined system. We are looking for clarification or language that supports the distinction between a combined and a separated standpipe system to explore options that may avoid the need for a pump.

Additionally, does anyone have thoughts on how we might be able to keep the standpipe at 4" or explore alternative approaches to avoid the pump requirement?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Two FDCs When Building Permiter(s) Over 900ft?

2/6/2025

14 Comments

 
In NFPA 14, Sections 7.12.2.2(2) (2019) or 10.7.2.2(2) (2024) state that a "minimum of two FDCs shall be provided for each zone for the following: (1)* High-rise buildings (2) Buildings or multiple attached buildings exceeding 900 ft (274.3 m) perimeter distance."

Neither edition defines "perimeter".

Is it measured where the building meets grade?

Should it account for all exterior walls?

Two building which share similar "A" length and "B" width dimensions can produce vastly different "perimeters" depending how they're measured. (See image below.)
Picture
Thanks in advance.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
14 Comments

Why Use Fire Engine for Bldg FDC that has Pump?

1/1/2025

7 Comments

 
Operationally, why would a fire department with a 1,500 gpm pump on a fire engine connect to a building FDC that has a 1,750 gpm pump?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Any 5-Year Testing for Manual Wet Standpipe?

12/4/2024

3 Comments

 
What is involved in a 5 year inspection/test for a manual wet standpipe?

I see in NFPA 25, 2017 edition that manual wet standpipes are not required to be flow tested or hydrotested when part of the sprinkler system.

So my question again is are there any specific requirements for 5 year testing for manual wet standpipes?

​Thank you all!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Where are PRV Hose Valves Req'd in a Highrise?

10/30/2024

8 Comments

 
How would you recommend determining when PRV hose valves should be used in a highrise?

I am designing a 12-story hotel. The highest outlet is at 125'-5".

Our flow test is mid-50's static and residual at 1,500 gpm. I did the standpipe calculation using a combined source of the city and fire pump. I sized the pump to what the demand was at 750gpm @ 174.26 psi. In turn I put in a 750gpm @ 125psi fire pump and had a 6.45lb buffer.

Do I then do another calculation to find out the maximum static pressure available on the supply side at each level and minus out the elevation loss?

Can anyone give me a guide on how to find out which level needs a PRV FHV and which doesn't?

​Thank you in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Concern with Draining Standpipes Back to Tank?

9/3/2024

4 Comments

 
We're designing a small footprint high rise with 2 stairs/standpipes, and 3" drains in the stairs for floor control valve drains and testing/verifying hose valves.

Primary water is supplied from a vertical turbine pump and tank. Local codes don’t allow direct outdoor drains so it’s either into the tank or into large hub drains.

Owner is very ‘green’ and looking for ways to reduce water usage.  We’ve already got the fire pump test flows back into the tank.  We’re considering flowing the stair’s drains into a hub with a bypass into the tank -- hub for system draining, tank for PRV and flow switch testing. 


Is it advisable or preferable to run these stair drains back into the tank?

​Concerns include flowing black, stinky water into the tank and possibly adding pipe scale into the tank


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

City Pressure Req'd to Calc Higher than Demand?

8/28/2024

7 Comments

 
Where is the code section that states the numbers (calcs) on the supply side shall be greater than the numbers at the base of riser (system side)?
 
Does the code address this with a code section?

​Thanks in advance.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

2-hr Shaft Req'd for Standpipe at Horizontal Exit?

8/15/2024

6 Comments

 
We have a multistory building with horizontal exits which require additional hose valves on each side of the door.

International Fire Code Section 905.4.1 addresses the protection of the standpipes, stating it must be equivalent to the rating required for the vertical enclosures of the building (e.g. egress stair) and the exception relieves the requirement for shaft protection of the laterals (e.g. interconnection).

However, there is no relief for protection of the vertical standpipes supplying the additional hose valves.

In the past, I have typically seen the additional vertical standpipe risers in the corridor wall separating the corridor from the units (1 hour) and fire stopped at the floor penetrations. However, according to this code section a 2-hour shaft is required.

Is there some relief of the 2-hour shaft requirement for additional standpipes outside of the stair enclosure?

If so, can you please guide me to the code reference?

If the shaft enclosure is required, would it also apply to the 2-1/2" feed serving the valve on the opposite side of the horizontal exit door?

​I appreciate the insight.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

How to Meet Highrise Second Supply Req'ment?

8/1/2024

4 Comments

 
Our high-rise facility consists of apartments, condominiums, retail on the bottom floor, restaurant tenants on the top floor, and (3) levels of underground parking. We are 9 stories tall out of the ground.

They have great water pressure at the site with 140 static
 and 118 residual, flowing about 1,900 GPM, but with our floor-to-floor distances, I cannot get 100 PSI at the top of my standpipes. The building footprint is spread out, so I will need (8) standpipes to cover the hose lay inside the building (fully sprinklered). I'm assuming one 1,000 gpm pump will cover all the standpipe demand.

To complicate matters, this is in a seismic area D classification, and with it being a high rise, I am required to have a secondary on-site water supply. The intent was to install an underground tank to supply the fire pump or pumps, if necessary.

My thought was to supply water directly from the city main to the tank, and if there is ever a break in the city supply line, the pump would be served from water in the tank, which would have enough capacity to serve the facility for 30 minutes.

Is 30 minutes the duration I need?

What do you think about how I plan to serve the building
? Would that meet the requirement for a secondary water supply?

Do I consider the standpipe demand when sizing the underground tank, or just the most demanding area of my sprinklers?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

How do Firefighters Handle Air from Standpipe?

5/30/2024

7 Comments

 
I've always wondered, how do the responding fire personnel holding the nozzle of a hose attached to a standpipe deal with the slugs of compressed air?

What happens with a hose/nozzle when a large, class I dry manual standpipe system is getting slammed with 150 psi (or more) of water pushing all that air?

Do they purge air before hooking up the hose?

How about a wet manual standpipe where the FDC is several sticks of 6" pipe from the check valve?

What's it like on the end of the hose when that slug of air arrives with 150-175 psi of water in front and behind it?

​Are there any firefighters out there experienced in standpipe operations who care to share?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Press. Reducing Valves Req'd for Dry Standpipe?

5/16/2024

8 Comments

 
When are pressure reducing hose valves required on a dry automatic standpipe system?

I have a project where I have been asked to evaluate an existing sprinkler system for an 8-story apartment building. The original installation falls under NFPA 13/14/20 2013 edition. The building is served by four dry automatic standpipes and a separate wet sprinkler feed. The standpipes are not combination sprinkler/standpipes.

The fire pump churn pressure is 212 psi and there is a pressure reducing valve provided for the wet system supply.

There is no pressure reducing valve for the dry automatic standpipes. The hose valves on the standpipes are the pressure restricting type. Not pressure reducing.

When reviewing the data sheets for the hose valves, it states "Adjustable restriction of pressures up to 175 lbs....at residual flow" but the valves themselves are rated to 300 psi. At normal, non-fire conditions, the standpipes have 23 psi static pressure of air, but if the dry valve were to trip for any reason, (non-fire or not) the standpipe exceeds 175psi static pressure on the 1st-7th floors.

NFPA 14 2013 states that "7.2.3.2* Where the static pressure at a 21⁄2 in. (65 mm) hose connection exceeds 175 psi (12.1 bar), an approved pressure regulating device shall be provided to limit static and residual pressures at the outlet of the hose connection to 175 psi (12.1 bar)."

Would the static pressure be considered the normal air pressure or the static pressure if the dry valve trips?

My assumption here would be that the pressure restricting valve needs to be swapped for a pressure reducing type.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Standpipe Flow/Pressure Req'mts in 1960's, 70's?

5/9/2024

7 Comments

 
Does any one know in 1960's and 1970's, what the flow and pressure requirements of 1-1/2 inch standpipe system hose of NFPA 14?

This would be for a Class II system. Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

"Low Pressure FDC" Allowed Upstream of Pump?

5/6/2024

9 Comments

 
I have seen this method of arranging fire suppression components (see attached schematic) several times where I live. The attached is a partial re-creation of the fire water entry schematic for a high-rise building with a fire pump. The system has low and high pressure zones.

The underground parking dry systems are served by the municipal water directly, and the standpipes and aboveground sprinklers are fed by the pump.

Picture

Questions: 1. Can you have a FDC serving the low pressure zones as shown on the suction side of the pump per NFPA-14 6.4.3.1?

2. If not, how should the schematic be arranged instead?

3. What could happen if the Low Pressure FDC were pressurized as shown?

​This project was built under the 2013 editions of NFPA-13, 14, and 20. I am asking because I am beginning design of a sprinkler system for a 22 story high-rise. Thanks for your help.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Is Building Fire Pump Size Affected by Firetrucks?

3/29/2024

11 Comments

 
For multi family buildings, I am being told that for a 4-story building, normally the fire pumps are only 15HP because the standpipes are pressurized by the fire trucks.

My understanding of NFPA 20 is that it would still be required to have a correctly sized fire pump without considering the size of the pump on the local fire trucks.

Is this an industry norm that is allowed by certain AHJ’s or is there code related to multi family that I am missing?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Mix Standpipe Types in Same Building Complex?

3/22/2024

5 Comments

 
In a 15-story highrise building, can the standpipe system be zoned with an Automatic Dry in the 1st -5th floors of the unheated Parking Garage, and an Automatic Wet in the 6th- 15th floors of the heated office portion?

Are we allowed to mix types?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Standpipe Required if Stairs are 470-ft Apart?

1/8/2024

13 Comments

 
Is there any requirement for a standpipe to be installed due to travel distance between stairwells in a 3-story R-2 building?

I am reviewing plans of a U-shaped apartment building with two stairwells on the ends. The distance between them is about 470 feet. We are under the 2018 IFC.

If not required by code, would you as the AHJ consider requiring them for improved fire operations?

Thanks for any feedback.

​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Use 65 or 100 psi for Manual Class III Standpipe?

9/26/2023

6 Comments

 
What is the required pressure for a manual Class III standpipe, 65 or 100 psi?

We're working on a 44'-4" high, 5-story, Type V-B construction building that has a 1-story garage and amenities. The upper floor is R-2. 

The local code says I can have Class III standpipe. As I go through NFPA 13 and NFPA 14, it circles back around to 2-1/2" outlets, except with 2-1/2" x 1-1/2" reducers and caps.

It's going to be fully-sprinklered with a combination standpipe in one stairwell, and just one standpipe riser in the other.

Does this sound correct given the project?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Valve for Hose Connection on Sprinkler System?

9/20/2023

7 Comments

 
We're working on a one-story school. The AHJ (Fire Marshal) is requiring inside 2 1/2-inch hose valves at the exit locations.

These hose valves are fed directly off the wet sprinkler system main - not fed from a dedicated standpipe main.

1. I'm having trouble finding code regarding feeding hose valves off of the wet system main.

2. I'm trying to determine if the pipe, off the main, to these hose valves, needs a control valve installed.

Appreciate the tips and insight. 

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments
<<Previous
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top June '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 45
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT