MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Calculation Method for Wet, Manual Standpipe?

10/30/2020

8 Comments

 
We are designing a residential building that will have a manual wet standpipe in a fully-sprinklered building. The building itself is less than 75-feet high.

I need to calculate the wet manual standpipe but would like to check my approach. 

Do I need to calculate the remote standpipe at the two most remote hose valves at 100 psi, 250 gpm each, plus one more hose valve closer to the source at 250 gpm all the way back from a supply at the fire truck?

​Thanks in advance for any feedback.

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments

Standpipes for Existing Building Connected to New, Taller Building?

10/28/2020

7 Comments

 
We have an existing building were the highest occupied floor is less than 30'-0 above fire vehicle access. This building is being renovated.

Part of the renovation involves the construction of a new building to be connect to the existing building. The new building is higher than 30'-0 above fire vehicle access. The exit stairwells in the new building need a standpipe system.
Picture
Does the existing building need a standpipe system since it is connected even though the existing building stairways and floors are not higher than 30'-0 above fire vehicle access?​

​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments

Do Standpipe Penetrations in Stair Require Seal?

10/27/2020

8 Comments

 
We have a project where the general contractor is stating that the vertical penetration in the stairwell landing, where the standpipes are located, need to be sealed.

They are not asking for it to be a fire-rated seal, but they say some sort of seal will be required. I know on past projects this typically was never a requirement. I have searched NFPA and the IBC with no luck on finding something that would insinuate that no seal is required for the vertical standpipes openings within the rated stair.

Is a seal required for these stair landing penetrations?

Any input is much appreciated.

​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments

Add FDC to Sprinkler Main or Standpipe Location?

10/16/2020

4 Comments

 
Adding a new Fire Department Connection to an existing building with a 4-inch combination standpipe and 2-1/2 inch mains feeding each level. The standpipe is significantly farther from the new FDC location; however, the 2-1/2 inch feed main is located closer to the new location.

Is it acceptable to connect the 4" FDC pipe to the 2-1/2" main, or do we need to route the pipe back to the standpipe location?

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Use Standpipe Hose Valves for Fire Pump Test?

10/2/2020

2 Comments

 
In an existing building with no fire pump test header, is it permissible to use Standpipe 2-1/2" fire hose cabinet valves to conduct a flow test for smaller pumps?

I believe NFPA 20 (2019) 4.22.3.1.3 (2) indicates that this approach is acceptable, but I would like to confirm.

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments

Include Hose Connections at Stage in Hydr. Calcs?

8/13/2020

6 Comments

 
We are working on a new addition to an existing high school. Part of the addition is a new auditorium with a full stage. The stage will be the highest hazard and our calculation area, Ordinary 2. The stage will also have (2) 1-1/2" hose stations with fog nozzles, one on each end, north and south, to protect the stage. They will be supplied from the same fire sprinkler system protecting the stage.

Do we need to include the hose station(s) discharge in the hydraulic calculations?

If so, what would be the flow criteria from those hose connections, and is that separate from the outside hose allowance or part of it?

Thanks all for your input.

​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

Valve, Check, Flow Switch Req'd on Standpipe?

8/4/2020

3 Comments

 
We have a 5-story building with wet manual standpipes in three stairwells. A single FDC connects to the end of a manifold in the riser room that has a 4-inch dry system, a 4-inch wet sprinkler, and a 6-inch riser that supplies the three standpipes. Each standpipe has a separate isolation valve at its stair tower. One of the standpipes is a combination standpipe/riser with sprinkler floor control valves for levels 2-5.

Regarding the 6-inch standpipe riser off of the manifold:

Is a control valve required, or allowed?

Is a check valve required?

Is a flow switch required, or recommended?

This project is under NFPA 14-2013 Edition. Thanks.

​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments

Mall Hose Connections Considered a Standpipe?

7/9/2020

2 Comments

 
I have a covered mall under 30' tall that requires hose valve connections in accordance with the International Building Code, Section 905.3.3.

Do these hose valve connections count as a standpipe that requires a monitored isolation valve as per NFPA 14 6.3.2?

​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments

Fire Department Hose Loss vs. Standpipe?

6/26/2020

10 Comments

 
I’m a Fire Inspector/Design Reviewer and I have a problem that I’ve been trying to tackle.  NFPA 14 systems are designed for high volume low pressure firefighting tactics, but the majority of fire departments in America use high pressure low volume equipment.  Here are the key points: 

NFPA 14 Type 1 standpipe systems provide 250 gpm at 100 psi with 200 ft to most remote location in a sprinkled building.  In the firefighting world this equates to a fire attack with 250 ft of 2.5” hose and a 1-1/8” smooth bore nozzle.  The 250 ft comes from, 50 ft to stretch to the hose connection on the floor below the fire floor and 200 ft to most remote location on the fire floor.  Fire ground friction loss calculations for 250 gpm through 2.5” hose is 15 psi loss per 100 ft.  A smooth bore nozzle requires 50 psi to operate properly.  We are stretching from the floor below so we have roughly 6 psi head loss.  So the required pressure at the hose valve is 93.5 psi.  You can see that the NFPA 14 design requirements are in line with the use of this higher volume lower pressure equipment.  

The problem is that 2.5” hose is very heavy and requires a lot of man power.  2.5” attach lines are used by large city departments like Seattle, New York, and Chicago.  Many smaller city and town departments don’t have the staffing to stretch such big lines.  We may only have a couple firefighters stretching an attack line where as the big cities would have 6 or more.  So we use smaller more maneuverable hose and more pressure demanding fog nozzles.

A more typical firefighting set up in the majority of fire departments would be 1.75” or 2” hose and a 75 psi or 100 psi fog nozzle flowing between 150-200 gpm.  I’ll use Bozeman as an example.  We use 1.75” hose, a 75 psi fog nozzle, and a target flow of 175 gpm.  In our experience the pressure loss per 100-ft of 1.75” hose with 175 gpm is 50 psi.  So if we need to stretch 250 ft of hose, we would need 206 psi at the hose valve on the landing below the fire floor.  Add in that the tallest building we have is 11 stories, and a 25 psi pressure loss adjustment for pumping the FDC, and we are up to 285 psi required at the FDC.  

There seems to be a disconnect between the design world and the firefighting world.  This poses all sorts of problems such as compromising sprinkler systems and old standpipe systems since they may have components that are not rated for such high pressures.  Even worse are systems with pressure reducing hose valves that wouldn’t even allow us to pump the FDC to get anywhere near the pressures we need with our equipment (see One Meridian Plaza fire in Philadelphia).  

I think that Fire Departments need to communicate their design needs to designers, and Fire Departments also need to look at the equipment they use, and see how they can make changes to operate more closely to what NFPA 14 systems are designed for.   

If you have any knowledge on this topic I would love to hear it, thanks in advance.

Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
10 Comments

Isolation Valve After Dry Valve in Standpipe?

6/8/2020

4 Comments

 
Are isolation valves allowed to be installed after dry valve for a standpipe system?

​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Standpipes Not Req'd for Large Industrial Facility?

5/22/2020

3 Comments

 
NFPA 1 Section 13.2.2.2, a Class I standpipe is not required in buildings less than three stories or less than 50-ft high above grade. 

If we have a huge industrial complex or storage occupancy of 60,000 square meters (645,000 sqft), should we not require a standpipe system if it is only one floor above grade with a total height of 40-feet? Looks strange to me.

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments

How to Protect Standpipes in Parking Garages?

4/3/2020

6 Comments

 
How do you see standpipes and hose valves protected from physical damage in parking garages where the area is large enough to require standpipes outside of the exit stairs? Bollards? Pipe guards? No protection?

​​​​​​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

Would Penthouse Elevation Require Standpipes?

3/19/2020

5 Comments

 
Would a mechanical penthouse be considered a “story” in terms of the 30-ft. standpipe threshold?

If the mechanical penthouse is not occupied, does it still apply for the 30-ft limit? Although that would be logical, I can’t the word “occupied” used anywhere except related to high-rise.  I suppose a mechanical penthouse could be considered a mezzanine, I see some commentary that a mezzanine should be no more than 1/3 of the related floor.

The project has three floors where the top classroom floor is 28 feet above fire department access.  But, there’s a mechanical level above that is much higher. It’s accessible, is it a “story” in terms of standpipe?  It would seem logical that this penthouse doesn’t count.  But I’m not 100% sure code backs me up on this.

Of course the thing that bites us, is whether or not the standpipe is manual or automatic – we have fond this to be totally up to the discretion (sometimes whim), of the AHJ.  Sometimes based on good reasoning, sometimes it has causes the unnecessary (IMHO) requirement for a fire pump.

​​​​​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Design Guidance for Pipe Expansion Joints?

3/10/2020

5 Comments

 
I'm working on a project with a very extensive horizontal standpipe; it is about 2000 feet long and in a loop, so almost 5,000 linear feet when all said and done.

Where can I find guidance on providing expansion joints?

Due to the system being so long, we're worried about providing some flexibility in the instance of extreme temperature swings (Virginia). Would seismic flexible joints be appropriate?

​​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Riser with 3" PRV Upstream of Zone Control?

3/5/2020

14 Comments

 
During a hotel stay in NYC over the weekend I noticed the combination standpipe included a 3" pressure reducing valve just upstream of the 3" zone control assembly.

An indicating valve was not installed on the inlet side of the Cla-Val (model 90G-21 with no pressure gauges). A filler piece between the PRV outlet and the butterfly valve included a pressure gauge which was at 60 psi. The 2-1/2" fire hose valve was standard pressure and the express drain was only 2".

This arrangement is not something I would expect to see in the DC metro area, but is it typical of NYC?

​​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
14 Comments

Standpipe/Riser Clearance in Floor Openings?

3/4/2020

1 Comment

 
We have a combination sprinkler/standpipe riser through floor-level landings in a stairwell of our building. There is a project requirement to provide a pipe sleeve and "required clearance per NFPA 13". 

NFPA 13 gives very clear guidance on clearances in Section 9.3 (NFPA 13 2016 Edition), but that doesn't apply to this project as it is not required to be designed for seismic (Seismic Design Category B).

Where can I determine what clearance needs to be between the pipe and the hole in the concrete stairwell floors/ceilings? I'm not seeing any clearance requirement, but I surely could be missing something. Thanks in advance!

​​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
1 Comment

Requirements for Cane-Detection at Standpipes?

1/22/2020

5 Comments

 
Within stairwells, how are standpipes addressed in regards to cane detection with ABA/ADA rules? Are there any special cane-detection requirements (anything special to allow a visually-impaired person to detect a vertical standpipe)?

​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

Does Standpipe Riser Need to Be Visible?

12/18/2019

6 Comments

 
Where exactly in the International Fire Code or International Building Code (or NFPA standards) does it state that a standpipe riser must be visible or unobstructed? 

Is there anything that prohibits me from sheetrocking the standpipe riser os installing it inside a wall? Of course the hose outlets will be exposed - but what about the riser?

​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
6 Comments

Run Fire Standpipe on Exterior of Building?

12/17/2019

5 Comments

 
Can we run a 6-inch standpipe for a highrise building (24-story) fully on an external wall? The main would come out of the pump room and take branches for each floor from the riser. This new building has a major space shortage and it's not possible to run the pipe within a shaft inside the building. There is no issue of freezing as the temperature does not drop to the freezing point.

​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
5 Comments

When Use Standpipe Pressure Reducing Valves?

11/29/2019

4 Comments

 
On a combination Class I standpipe/sprinkler riser with automatic standpipes, what is your process to determine exactly where pressure reducing valves should be used?

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Standpipe Demand OK Over Fire Pump Rating?

8/9/2019

4 Comments

 
NFPA 20 permits the demand for a suppression system to be between 90% and 140% of a fire pump's rated capacity (NFPA 20-2019 4.10.1 and Annex A.4.10.1). The pressure demand must always be less than the pressure supplied by the pump's performance curve along this range.

Does this concept apply to standpipes? For instance, could a 750 gpm pump provide 1,000 gpm demand for standpipes since it would be running at 133% of its rated flow?

If it can be done, is it good practice?

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Does ADA Apply to Standpipe Hose Connections?

6/12/2019

4 Comments

 
For standpipe hose connections within stairwells, does ADA (Americans with Disabilities Act) restrictions apply to the dimensions of hose valves coming off pipe? 

ADA - 2010 Standard

307.2 Protrusion Limits. Objects with leading edges more than 27 inches (685 mm) and not more than 80 inches (2030 mm) above the finish floor or ground shall protrude 4 inches (100 mm) maximum horizontally into the circulation path.


307.3 Post-Mounted Objects. Free-standing objects mounted on posts or pylons shall overhang circulation paths 12 inches (305 mm) maximum when located 27 inches (685 mm) minimum and 80 inches (2030 mm) maximum above the finish floor or ground. 
​

In particular, I'm wondering if the 4" protrusion limit applies to standpipe hose connections off of a vertical standpipe, and if it does, if it only applies if the standpipe hose connection is pointed into the path of egress?

I would imagine there's some life safety experts that could explain this better than I surely am.

Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
4 Comments

Distance from FDC to the Nearest Hydrant?

5/20/2019

17 Comments

 
For years on my code calls I have asked the Authority Having Jurisdiction what the maximum distance the nearest hydrant is allowed to be away from a building's fire department connection. I get answers that range from 50 feet to 400 feet or even more.

I was looking into the code basis behind this question, and the only applicable section that I found is the International Fire Code, Section 507.5.1.1 that addresses hydrant locations for standpipe systems:

"Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet (30 480 mm) of the fire department connections. Exception: the distance shall be permitted to exceed 100 feet (30 480 mm) where approved by the fire code official."

Is there any relevant requirement for hydrants near fire department connections for sprinkler-only systems?

Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
17 Comments

Full Flow Test Required for Manual Standpipes?

5/8/2019

3 Comments

 
NFPA 14 requires standpipes to be full flow tested for the acceptance testing.

Automatic standpipes are fairly straightforward to test, but how have you seen this applied for manual standpipes in mid-rise buildings?

Is this a worthwhile test that will uncover design/installation flaws?

Also, is there any compromised method to meet this requirement?

Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
3 Comments
    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​October '20 Contributors!
    1. SK
    2. Franck
    3. Dan W.
    4. Jonathan ​5. Casey M.
    6. Sean
    7. Colin L.
    8. Mike
    9. Jonathan J
    ​10. Daniel G.


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About