Does a Duct Near Ceiling Need Sprinkler Above?

1/31/2024

11 Comments

 
I understand if a duct is wider than 4-ft (1 m) that there needs to be a sprinkler under the duct.

But what if the duct is just below the ceiling? Does a sprinkler also need to be above the duct?

I have a group of ducts with a combined with of 16'-6" (5 m) with the highest point of the duct 10 inches (25 cm) under the ceiling.

Does there need to be a sprinkler above and below the ducts?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Does Fire Separation Negate Need for Sprinklers?

1/30/2024

10 Comments

 
I purchased a commercial condo recently. It’s been vacant and unfinished since 2013. It’s a shell, picture is below. It has 5 residential condos on top and 5 commercial condos on first floor, in a 3 story building. All residential units were sold and have been occupied since. One commercial unit was also built and has been occupied as a salon with a U & O.
Picture
There are no sprinklers, no fire room. They were going off of 2006 IBC code.

My architect prepared stamped plans with no sprinklers using the separated building scenario. It has a 2-hour horizontal separation, 3-5 hour vertical, no access to second floors. The plan was denied for sprinklers to be installed.

Now, I certainly understand safety, but it’s almost impossible to install now after 12 years.

Can you help me decipher mixed use B (1st floor) and R-3 (2nd and 3rd one unit)?

Is this approach allowed by code, or is the code official correct?

Is a self-contained fire area allowed to be its own building?

Please help, thanks.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments

Advice for a Designer Without Field Experience?

1/29/2024

20 Comments

 
Designers and engineers get knocked (rightfully so) all the time for not living "in the real world".

I'm one of those designers. I've never installed any of these systems myself, but I want to know what advice those in the field would wish their designers and engineers knew.

What is one error or issue that you've seen that was due to a designer having a lack of field experience?

Pipe lengths? Obstructions? Elevators? Heights? Fab methods? 

What have you seen missed that could have been right the first time if they had field experience?

Looking for ways to keep the field from hating me while acknowledging that I don't come with that level of experience. Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
20 Comments

Allowed to Run 4 Diesel Pumps Simultaneously?

1/26/2024

15 Comments

 
We have a project and have gotten into an internal debate. The project has four diesel fire pumps in one pump house. 

During testing, are we allowed to run all four at the same time?

Or do we need to run each separately as we do normally to reduce the chance of blowing out a main?

Anyone have insight on this?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
15 Comments

How to Address Warehouse with Boats on Racks?

1/25/2024

11 Comments

 
Does anyone have experience in designing suppression for a warehouse that will store boats on racks?

I will appreciate any information. 

Which standard would even be applicable? Do we treat them like high-piled combustible storage per Chapter 32 of the IFC?

What will be target hazard considering the fuel in the boat? Is there any limitation that how much they can keep inside the boat?  

Thanks for the input on this; I'm having a hard time on where to get started.

Editor's Note: A Fire Protection Research Foundation on Marina and Boatyard Indoor Rack Storage Sprinkler Protection has been submitted and can be viewed here: PDF LINK

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

How to Seal a Drain Through a SCIF Wall?

1/24/2024

6 Comments

 
We have a project that includes a Sensitive Compartmented Information Facility (SCIF).

How do you properly seal an open drain that travels through a SCIF wall to the outside?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe​
6 Comments

Any Experience with Oxygen-Reduction Systems?

1/23/2024

15 Comments

 
I had a client ask about Oxygen-Reduced Systems (ORS), aka Hypoxic air technology (displacing ambient oxygen in an enclosed environment such as in warehouses). I did a quick read with what's available on Wiki, FM and NFPA. But even my go-to suppression people have hardly encountered these. Testing has been very specific.

Just to increase my knowledge, does anyone here have an practical experience in these?

Are these systems really being installed?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
15 Comments

Can Close Walls Create Obstructed Construction?

1/22/2024

6 Comments

 
Can full height walls within a room create an obstructed construction situation in an otherwise unobstructed construction building?

As an example, you have a room with full height walls and a single exposed beam (in noncombustible construction) with the distance from the centerline of the beam to both parallel walls less than 7'-6".

If allowed to define this as obstructed construction, a single sprinkler 1" to 6" below the bottom of the beam may be sufficient. If not, it may require a sprinkler on both sides of the beam.

In a multiple-office type of occupancy this could save a lot of sprinklers. This example is assuming following all the rules for obstructed construction and the depth of the beam being such that you can't use the obstruction to sprinkler discharge rules to avoid the obstruction.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Single-Interlock Subject to Water Delivery Time?

1/19/2024

5 Comments

 
Topic: Water Delivery Time in Single Interlock Preaction Systems Question:

I'm currently designing a single-interlock preaction system and I'm seeking clarification about the water delivery time requirements under NFPA 13 (2013).

Section 7.3.2.2 mentions that the system size cannot exceed 1,000 automatic sprinklers but doesn't specify the water delivery time for single interlock systems.

On the other hand, Section 7.3.2.3 clearly states that double interlock preaction systems must deliver water within no more than 60 seconds.

Does this mean that single interlock systems are not required to adhere to a specific timeframe for water delivery?

In my view, it makes sense to not include a delivery time for single interlock systems, since water should already be at the sprinkler prior to activation. I'm interested in others' views or experiences in this area.

Thanks in advance!

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Is NFPA 13R OK for Any Type of Live/Work?

1/18/2024

7 Comments

 
I am working on a permit for a 1,500 sqft (750 sqft/ floor) new construction live/work building R-2 in California (2022 California Building Code, which is based on IBC). It has a 1-bedroom apartment above with only "work" space below.

The building code allows for Live/Work R-2 to be protected with NFPA 13R. In the building code the only uses not allowed in the "work" area of Live/work are Group H & S.

Where all of this gets hazy is that I interpret the code as 13R being allowed to protect this whole building regardless of use except for uses S or H.

For instance would a small pizza joint be allowed in this "work" space as long as it did not have special hazards that would require an ANSL or NFPA 13 system?

Or is Live/Work with 13R just purely limited to office, barber, professional space, etc.?

From multiple angles I am trying to understand the true limits of Live/work when there are no local ordinances that limit the "work" space use except S & H.      

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Is FDC and PIV Required to be 50-ft Apart?

1/17/2024

15 Comments

 
I have a building that has both a free standing fire department connection (FDC) and a post-indicator valve (PIV) out at the drive entrance to the single-story building as requested by the Fire Marshal.

Construction has now started up for the site and the Fire Marshal is saying there is a code requirement for the PIV and FDC to be 50-ft apart and wants them moved. He is unsure of the exact distance, but he insists this is a code requirement and that it's not a local requirement.

For reference, we are under the 2015 IBC/IFC and 2013 NFPA code editions.

Is there any requirement for the PIV and FDC to be 50-ft apart?

I cannot find any requirement like this in the IBC, IFC, or NFPA 13 or 24. There are sections in both NFPA 13 and 24 that vaguely say PIVs shall be protected against mechanical damage, but they give no minimum distance from objects. IFC/IBC both list minimum 36-in clearance around the FDC.

I think the Fire Marshal might be confusing the 40ft requirement from buildings for the PIV, or, this is a local preference, but they do insist otherwise.

I know at the end of the day the Fire Marshal gets whatever they want for the PIV and FDC placement, but I really want to make sure that there is not some hidden requirement I cannot find.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
15 Comments

A Limit to Tire Storage in Unsprinklered Building?

1/16/2024

8 Comments

 
We have a storage building that is non-sprinklered, it only has fire alarm. The ceiling height in some areas of the building with storage of tires is up to 10-ft in height, and others up to 15-ft in height.

How many tires can be stored?

Is there a limit to the amount of storage?

Does storing on tread or on side matter?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Use Sprinklers at Window Instead of 1-Hr Glazing?

1/15/2024

12 Comments

 
I have a project in the Miami area where there are some exterior glass panels that need to be 1-hour fire rated.

I specified the glass to be fire rated type, but it prices are coming back too high. The contractor is looking into an alternative of providing fire sprinkler protection on the inside face of the glass.

Is this a feasible idea?

The wall that the glass is part of requires the rating due to its being within 10' of some adjacent exterior glass.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments

Options for Air Release Valves in Tight Space?

1/12/2024

9 Comments

 
We have a fire sprinkler tree system that has a 6" centerline down from a metal deck (mains and lines).

Since an air release valve is required at the end of the system, what are our options for installation?

All the options I can find are too tall to fit with our piping so close to the deck. We are not able to lower the piping due to other trades.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Does a Pendent (Horizontal) Meet NFPA 409?

1/11/2024

8 Comments

 
We have a steel aircraft storage hanger Group 1. It's approximately 50-ft high with exposed steel columns requiring a fire rating per NFPA 409-2022 Edition.

The steel will not be fireproofed but will be protected with sprinklers in accordance with NFPA 409 5.6.3.4.

Can pendent sprinklers, installed sideways, be used to satisfy NFPA 409 for column protection?

In the past we have protected the columns with sidewall sprinklers spaced according to 409 and on alternating sides of the column. Then the sidewalls were changed to pendent sprinklers installed horizontally to provide better spray distribution on the columns as the sidewall spray tended to (in theory at least) bounce the spray back in stead of vertically.

This approach has been accepted by EOR and AHJs alike.

NFPA 409 states that "wetting of the lower sprinkler should be considered" although multiple level sprinklers were never used. I'm not sure how this plays in.

I recall reading that pendents installed horizontally could be used for column protection due to better spray distribution, however, I cannot find that in code.

The client is not open to fireproofing or intumescent paint; column sprinkler protection is in the bit and is going to be used.

All is appreciated!

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Where is History of Standpipe Pressure Changes?

1/10/2024

13 Comments

 
Does anyone know of any literature summarizing standpipe design changes history for the last 130 years or so?

Something to the effect of:
  • 1993 to Current - 500gpm flow most remote, 250gpm each additional, residual pressure at 100psi
  • 1970ish to 1993 - 500gpm flow most remote, 250gpm each additional, residual pressure at 65psi
  • 1950ish to 1970 - 500gpm flow most remote, 250gpm each additional, residual pressure at 50psi

With more enforcement of 5-year standpipe flow testing in our area we find ourselves spending a lot of time trying to locate older versions of NFPA and NBFU to see the design basis at the time of construction to determine testing procedure.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Attic System Removed if NFPA 13R Now Allowed?

1/9/2024

13 Comments

 
Can an assisted living facility that installed a an NFPA 13 compliant system which was only required to be a 13R now remove the dry attic part of the system?

They have had corrosion issues and leaks they are wanting to avoid. The only reason they installed the 13 system is initially they envisioned possible adding a skilled care section which is now not happening.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Standpipe Required if Stairs are 470-ft Apart?

1/8/2024

13 Comments

 
Is there any requirement for a standpipe to be installed due to travel distance between stairwells in a 3-story R-2 building?

I am reviewing plans of a U-shaped apartment building with two stairwells on the ends. The distance between them is about 470 feet. We are under the 2018 IFC.

If not required by code, would you as the AHJ consider requiring them for improved fire operations?

Thanks for any feedback.

​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments

Is AR-SFFF Allowed to Discharge to Storm Drains?

1/5/2024

10 Comments

 
Are foam system test headers allowed to flow outside and discharge the foam to the ground/storm water?

I see more and more places are banning AFFF from storm water.

What about flowing AR-SFFF to storm?

Any recommendations for capture if its not allowed to be send down the storm drain?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments

Size Rod to Trapeze Separately than Rod to Pipe?

1/4/2024

8 Comments

 
In regards to a trapeze pipe support, isn't there an option to size the rod that connects structure to the trapeze pipe separately from the rod from the trapeze pipe to sprinkler pipe?

Couldn't that be two separate calculations considering there are two rods for the trapeze and only one to the sprinkler main?

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

Congratulations to the Top 2023 Contributors!

1/3/2024

1 Comment

 
You all are awesome. The quality and diversity of perspectives here is second to none - and I'm very thankful for the contributions everyone has made these last few years. The quality of discussion and insight is far better than I could have hoped for when first starting this Forum back about five years or so ago now.

Thank you to everyone for continuing to make this Forum such an insightful success and help to share ideas and best practices for the industry.

Here are the Top Forum Contributors in 2023 (in alphabetical order):
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture
Picture

As a thank you from our team for helping shape the industry in a positive way, each Top Contributor will get a plaque like the one shown above. We'll also make note with a flag next to each person's name in future leaderboards.

Thanks for being a part of the community and helping move the industry forward!

​- Joe Meyer
1 Comment

Pressure Gauge Req'd on Both Sides of Backflow?

1/3/2024

11 Comments

 
Would you require a pressure gauge on the bottom side of the backflow device?

NFPA 13 says pressure gauges shall be installed above and below each “alarm” check valve or “system riser” check valve where such devices are present.

Is the backflow preventer considered an alarm check or riser check valve?

Picture

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Requirements for an Indoor Diesel Storage Tank?

1/2/2024

11 Comments

 
We have an indoor amusement park (skiing activities) which has a back of house space where in machines are being repaired and refueled. There is a diesel storage room which a 1,320 gallon tank (5 cubic meters).

The room does not have any fire resistance rated walls and is also used for storing paint thinners (Class 2 flammable liquid). Just outside this room is a welding space.

Is there guidance, somewhere, on what needs to be considered here for fire and life safety?

I tried using NFPA 1, NFPA 30, and NFPA 101, but since this diesel tank is inside the space, I've not been able to find a reasonable solution in terms of fire and life safety requirements.

Thanks for the input.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

CPVC Allowed Exposed Through Storage Room?

1/1/2024

10 Comments

 
Is CPVC allowed to be run exposed through a small storage room?

Thanks in advance.
​
​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Oct '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT