MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Calcs Required to Replace K3.9 with K4.2?

5/20/2026

8 Comments

 
I have a campus housing situation with a few thousand reliable 3.9k heads that are no longer made, on 16x16 spacing, requiring 17 gpm and 19 psi per the cut sheet.

We are looking to replace these with 4.2k sprinklers, same 16x16 spacing, is 16 gpm and 14.5 psi per the cut sheet.

Question is, I know the 4.2K falls just over the allowed 5% deviation, but these 4.2k sprinklers are more "efficient", so would they require running new hydraulic calcs to verify, or would it be safe to swap out as is?

​Thank you in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments

High Static Pressure Without a Fire Pump?

5/19/2026

12 Comments

 
Has anyone encountered unusually high and consistent static pressures in sprinkler systems where there is no visible fire pump?

I recently came across two examples that raised questions:
- A riser in our major metro showing about 165 psi static pressure.
- A five-story hotel with roughly 125 psi static pressure on every level, consistently throughout the building.

In both cases, I searched extensively for a fire pump and could not find one. The buildings were on normal city water supplies, not private systems or campuses, and there was nothing obviously unusual about the sites.

It made me wonder whether there are situations where some type of booster pump is being used for sprinkler systems without being readily identified as a traditional NFPA 20 fire pump? Or perhaps there is another explanation entirely.

Has anyone else seen this? If so:
- What was the situation?
- Was there hidden pressure-boosting equipment involved?
- Are there municipalities or systems where this is more common?
- Or is there another explanation for maintaining these pressures throughout a building without a fire pump?

Interested to hear what others have encountered.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments

Minimum Height of Pipe in Underground Garage?

5/13/2026

9 Comments

 
Is there a minimum height requirement of pipes in an underground parking garage?

​Is that different than an ordinary occupiable space?

My vehicle is 75.8 inches tall, for instance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Route Diesel Fire Pump Flow Back Into Suction?

5/12/2026

5 Comments

 
I have a DoW project with specifications that require the diesel fire pump flow meter to discharge both into the pump suction and through the test header.

I don't have experience with this setup; in all my previous projects, the diesel fire pump discharged back to the water tank as well as to the test header.

I understand that NFPA 20 allows this arrangement (see attached figure from the 2025 edition), but I'm curious how it works in practice for two main reasons:

1. If we close the tank valve during testing, the pump's suction pipe will receive considerable pressure. Will this repeated pressure adjustment after each test impact the longevity of the soft packing, particularly regarding increased water leakage?

​2. How does a diesel fire pump cool its motor if the heat exchanger water isn't returned to the tank with fresh cool water coming in?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
5 Comments

Sprinkler Entire Attic With One Fuel-Fired Unit?

5/11/2026

9 Comments

 
Do you have to protect the whole attic that has smoke partitions with fire sprinklers if only one area has gas-fueled equipment in it?

​Can you just protect the one area that has the fuel-fired equipment in it?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
9 Comments

Drop-Down Sprinkler for Coffered Ceiling?

5/7/2026

5 Comments

 
We have a coffered ceiling with a 3" drop as per design, and we'd like to have the fire sprinkler drop down 3" automatically when activated.

Is there a product or technique that can be used for this?

It's a high-end commercial space. Thanks in advance.

Moderator's Note: Updated "Chauffeured" to "Coffered." 


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Water Supply Options for Rural Area with Pond?

5/6/2026

12 Comments

 
I am working on a new building in a rural area that will require sprinkler protection. There is no access to a public water supply, only a 30-100 gpm well on site.

Options for fire suppression water include pumping from a large farm pond 150 feet away or installing
a 15,000-gallon water storage tank with a pump.

Any thoughts on
which option is more feasible and cost-effective​, or any alternatives we're not considering?

This is in a freezing climate. Thank you in advance!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments

Alternatives Tank Ideas for Seismic Area Highrise?

5/5/2026

7 Comments

 
I've got a high-rise project in a seismic zone higher than category C. We are required by IBC to have a secondary water supply other than the city supply (IBC 403.3.3). The structural team is pushing to not put the tank on the roof, and our site is extremely limited, so there is discussion about trying to bury the tank.

What pump/tank configurations are available for this situation?

I am aware of either a concrete or fiberglass tank with a vertical turbine pump, but can you tie in the city supply to a vertical turbine submerged in a tank?

Is there a way to appease this rule other than a secondary fire tank that I'm not thinking of?

​Thank you in advance for any help.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

Space Sprinkler to Front or Back of Cabinets?

5/1/2026

3 Comments

 
There is a great debate in my office whether or not we are required to protect to the back of lower/upper cabinets.

NFPA 13 9.2.9.3 (2022) states that we need to cover the area below the cabinets to the back wall. Seems pretty straightforward to me, but someone in my office states that we only sprinkler floor space, without providing any code reference.

Do we protect to the wall, or the face of the cabinet where only floor area is exposed?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Where is Hose Allowance for Combined System?

4/30/2026

3 Comments

 
When hose allowance is added to the sprinkler demand on a Class III Standpipe/Sprinkler wet riser, where on the system are the inside and outside flow and pressure allowances input when calculating the system?

NFPA 13 Chapter 19 states that the allowances are not required when calculating a combined system, which appears to contradict NFPA 14 requirements to include them.

In my case, the sprinkler demand is for OH2 (ceiling higher than 40 ft), resulting in a sprinkler demand plus hose allowance that is greater than the standpipe demand.

​If I don’t include hose allowance in the sprinkler calculation as per Chapter 19, this combined system is not equivalent and robust as two independent systems. Any thoughts?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Are Sprinklers Required In or Below Overhang?

4/29/2026

7 Comments

 
Is sprinkler protection required for the overhang shown in the simplified detail below?

If sprinkler protection IS NOT required, which allowable sprinkler omission does this comply with in NFPA 13 (2022)?

If sprinkler protection IS required, what component(s) are triggering this requirement?

​Thank you!


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
Picture
7 Comments

Can CPVC Be Used for Highrise Sprinkler System?

4/28/2026

9 Comments

 
We have a high-rise building (residential from 5-24 floors).

Can CPVC listed piping be utilized in high‑rise fire sprinkler systems (residential portion), and are there restrictions related to maximum elevation and/or pressure limitations?

​Thanks in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Omit Sprinklers At Entire Bottom Area of Stair?

4/27/2026

7 Comments

 
Under NFPA 13, 2022: in noncombustible stair shafts, can sprinklers be omitted at the entire bottom area of the stairs?

For example, if the first floor is the bottom of the stairs, can sprinklers be omitted under the second floor at the area where you enter the stairwell?

Section 9.3.4.2.3.1 states, "Sprinklers shall be permitted to be omitted from the bottom of the stairwell when the space under the stairs at the bottom is blocked off so that no storage can occur."

Is this only referring to under the intermediate landing and not the entire first floor area of the stairs?

I know that at the beginning of this Section 9.3.4.2.1 states in part "under the first accessible landing above the bottom of the shaft."

​So does the omission apply in this case?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments

ESFRs Allowed on Single Interlock Preaction?

4/24/2026

9 Comments

 
Would ESFR K25.2 be permitted to be installed on a single interlock pre-action system?

I have a system conversion that is currently a gridded warehouse with K25.2 ESFR pendents that the client wants to convert to single interlock. The system will be converted to not be gridded anymore, but I am not seeing any clear information on whether the existing ESFR can remain.

If we were to remove the sprinklers, it would now dive into possible in-racks to protect the class IV storage. Warehouse is 35ft max height, bar joist.

​Thanks in advance.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Will Backflow Dump When Fire Pump Starts?

4/21/2026

6 Comments

 
We have a situation where we need to replace a 40-year-old fire pump where the original RPZ is located downstream of the pump. Our current code requires all BFP's upstream of the pump. We are worried that the RPZ will start dumping every time the pump is started.

Does anyone have experience with this that could lend a recommendation? 

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

Sprinkler Gas Storage Closet from Floor Below?

4/17/2026

4 Comments

 
For a dental office, is a sprinkler required in the gas storage closet (nitrous oxide and oxygen) on the main floor?

The basement is sprinklered, but the main floor is not.

​If sprinklers are required, can the system be tied into the existing basement sprinkler system?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments

How to Design for Pipe Stands at 26-ft?

4/14/2026

6 Comments

 
I have 6" and 8" sprinkler pipes that need to be supported by pipe stands at 26 ft.

​What does NFPA 13 require to be done/designed for this situation?

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments

How to Respond to Unlisted/Unrecognized Tech?

4/13/2026

11 Comments

 
As an AHJ, how do we respond to someone that wants to use new technology that is not recognized by Code / Standard?

Such as Sonic Fire Tech?

https://www.sonicfiretech.com/

Do we recognize it or require UL / FM / "Approval" before allowing it as an approved system?

In other words, what would be the basis for saying "no" at this stage?


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

When to Modify CMDA in a New System Design?

4/10/2026

3 Comments

 
I am doing CMDA overhead sprinklers for in-rack class 4 storage at 15' - a new system.

As I was navigating through NFPA 13 2022 Chapter 21, I came to 21.4, which seems to be where I should be.

My question is: 21.4.1.1.1 is where you start, which states that if it's a new sprinkler system, the demand shall be determined in accordance with 24.4.1.2.2.1. BUT, I skipped that and went on to 21.4.1.2.1.1, which seems to be for the EXACT SAME CRITERIA (unless I cannot read/comprehend, which is possible)!

So when would you use 24.4.1.2.2.1 over 21.4.1.2.1.1?

When we use 24.4.1.2.2.1 with the modification chart, we get a density of 0.297, and when we use 24.4.1.2.1.1, it calls for 0.30.

So they're pretty much the same... but I'm not seeing why you would ever use 24.4.1.2.1.1 since 24.4.1.1.1 directs you to 24.4.1.2.2.1 and bypasses the other. Hopefully, this makes sense.

---
​
21.4.1.1 General

  21.4.1.1.1 Ceiling sprinkler water demand for new systems shall be determined in accordance with 21.4.1.2.2.1 for single and double row racks or...

  21.4.1.1.2 Ceiling sprinkler water demand for the modification of existing systems...

21.4.1.2 Protection Criteria for Single or Double-Row Rack Storage of Class I-IV Commodities over 12 ft Up to and Including 25 ft in Height.

   21.4.1.2.1 New Systems Criteria for Single- or Double-Row Rack Storage of Class I-IV Commodities Stored Over 12 ft Up to and Including 25 ft in Height.

      21.4.1.2.1.1 For single- or double-row racks for Class I, II, III, or IV commodities, encapsulated or nonencapsulated, the ceiling sprinkler demand.... shall be selected from the criteria in Table 21.4.1.2.1.1(a) through Table 21.4.1.2.1.1(c) that are appropriate for... and shall be modified as appropriate by 21.4.1.4.

---

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
3 Comments

Sprinklers Required for Large, Accessible Chase?

4/9/2026

16 Comments

 
In a four-story educational building, we have a large pipe chase that wraps around the men’s and women’s restrooms on each floor. The highlighted area in the attached sketch is the pipe chase area.
Picture
​The wall on the left (with the red arrows pointing at it) is a 1 hour rated shaft wall. All the other walls around the pipe chase are non-rated wall assemblies. There are doors (blue boxes) giving access to this area in three different locations. There isn’t any equipment or sources of ignition located inside the chase, just plumbing pipe.

While the area is not to be used for storage, we are concerned that the presence of the doors will allow people to do so. The Architect/Engineer has directed us not to protect this area with sprinklers.

Are sprinklers required inside this chase or can they be omitted as directed by the A/E?

​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
16 Comments

How to Calculate Diesel Fuel Tank Vent Capacity?

4/7/2026

5 Comments

 
I have a plan reviewer requiring calculations (CFH) for a diesel fuel tank because the vent extends further than the UL label is calculated for.

What are the guidelines and how is this calculation performed?

The comment: "
Provide the required emergency vent capacity, in Cubic Feet Per Hour (CFH), for the primary and secondary fuel tank emergency vents. The venting capacity should be indicated on the UL label on fuel tank. The shop drawings don't list the emergency vent capacity. Note: The capacity listed on the UL label is calculated with the vent within 12 inches of the tank body. If the vent is extended above the tank more than 12-inches, additional calculations are required to account for the additional piping and height above the fuel tank. These calculations are required to be computed by a registered engineer."

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments

Does NFPA 13 Require Redundant PRVs?

4/3/2026

9 Comments

 
NFPA 14 requires PRV redundancy when more than two hose connections are supplied downstream of a PRV.

Does NFPA 13 have a similar requirement for sprinkler systems, or can multiple sprinkler systems be controlled by a single PRV?

​We are proposing to feed a riser manifold controlling (6) sprinkler systems to be supplied by a single ORV without a redundant loop.

Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments

Cellophane Bags for Sprinklers in Dusty Areas?

4/2/2026

11 Comments

 
NFPA 13 Section 16.2.4 concerning protective coverings for sprinklers only references spray booths and mixing rooms.

I have a building that produces particulates in the air (a chip and tortilla factory). The concern is that we replace these sprinklers, and they will quickly need to be replaced again in a couple of years (96 total).

I want to put on cellophane bags to protect them. The existing sprinklers are standard response. I plan to go to the AHJ for their approval, but I wanted to get the opinion of others who may have experienced something like this.

Thank you in advance.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments

Use Fire Pump Test in Lieu of Flow Test for Calcs?

4/1/2026

17 Comments

 
Can a fire pump test report be used in place of a hydrant flow test?

For an existing building, a fire pump flow test has to be done annually. It should include all the information a hydrant flow test provides to perform a hydraulic calculation for an existing building modification.

Is there any code basis for taking this approach?

I have an AHJ that keeps pushing back on this approach for determining the water supply information.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
17 Comments

Does a Water Storage Tank Need to be UL Listed?

3/31/2026

9 Comments

 
Is a water storage tank for an NFPA 13 system required to be UL listed, or does it need to simply be NFPA 22 compliant?

I was always taught that a tank had to be at least UL Listed for fire protection, but I have a supplier telling me otherwise, and the price he offers is less than half that of a UL/FM tank.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
<<Previous
    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top April '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT