MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Attic System Removed if NFPA 13R Now Allowed?

1/9/2024

13 Comments

 
Can an assisted living facility that installed a an NFPA 13 compliant system which was only required to be a 13R now remove the dry attic part of the system?

They have had corrosion issues and leaks they are wanting to avoid. The only reason they installed the 13 system is initially they envisioned possible adding a skilled care section which is now not happening.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments
Dan Wilder
1/9/2024 07:11:14 am

You'll run into several issues and questions:

Did the building occupancy change or is it being reclassified? Was it an R-4 with a provision for Condition 1 or 2 or was it classified with I-1 prior?

Were there building allowances taken for being "fully sprinklered"? These would become void by removing the attic space protection, items like allowable floor areas, separation requirements, allowable # of floors, construction type and protection, possibly mechanical/smoke system changes.

For an AHJ to accept the reduction there would be much more than just saying the proposed expansion isn't happening and the installed fire protection is being removed.

On another note, are the corrosion issues due to a bad install, bad maintenance, or a mix of both? Addressing those with preventative measures (dry air or N2 supply) along with a consistent maintenance schedule may be an option.

Reply
Anthony
1/9/2024 07:48:48 am

Yes you can remove the system if the attic protection was above and beyond code requirement. Make sure you have all your ducks in a row as Dan mentioned, this may not be as cut and dry(puns intended) as you think.

Reply
Chad
1/9/2024 11:17:42 am

Not if NFPA 1 applies. Non-required systems stay unless permitted by the AHJ.

Reply
Glenn Berger
1/9/2024 08:15:33 am

Proceed with caution on this subject. Need to do a full code analysis on the exact conditions of this specific facility. I have been to several assisted living facilities and they are more than your basic apartment style buildings.

Reply
James
1/9/2024 08:27:10 am

I agree with emphasis on needing the "full code analysis" part.

Have someone well-versed in the building code and ALL of the code tradeoffs for an NFPA 13 system look at all the different aspects of the building, build a code path, and put in writing that removing the system is allowed by code. I wouldn't want that liability as a contractor (or really as an engineer either). Imagine the immediate lawsuits (right or wrong) if a fire happened in the attic where a sprinkler system was removed.

Reply
Nelson
1/9/2024 08:59:09 am

I agree that a "full code analysis" will be needed.

According to the International Fire Code (2021) Section 901.6, Nonrequired systems shall be either maintained or removed. So, you must PROVE that it is nonrequired.

My first question would be..."Why would a NFPA 13 system be installed here in the first place?" My first guess would be that they exceeded their allowable area for their construction type; thereby gaining a 300% increase in area by adding the NFPA 13 system (IBC Chapter 5).

My next question would be to understand the occupancy type and determine what type of system is required by IFC/IBC Section 903, & 903.3.1.1/903.3.1.2.

Remember, a NFPA 13 system protects life and property while a NFPA 13R system protects property only.

Nelson
1/9/2024 09:05:15 am

Correction........13R is for life safety only. Sorry for the typo.

Todd E Wyatt
1/9/2024 08:54:48 am

Q : Can an assisted living facility that installed a an NFPA 13 compliant system which was only required to be a 13R now remove the dry attic part of the system?
A : It depends on the nature of the attic per the scoping Code (e.g. IBC-2021 903.3.1.2.3 Attics) and the nature of the “residents” (e.g. Condition 1 or 2).

EXPLANATION
An assisted living facility (ALF) is classified as a Group R-4 Residential occupancy. ALL Group R occupancies are required to be protected by an automatic sprinkler system (ASPS) per IBC-2021 903.2.8.

Depending on the “care” provided and the nature of the “residents” … custodial care & capable of responding in an emergency (Condition 1) versus custodial care & requiring assistance in an emergency (Condition 2) … a Group R-4 Condition 1 requires an ASPS which is permitted to meet NFPA 13D (IBC-2021 Section 903.3.1.3) for R-4 Condition 1 or a Group R-4 Condition 2 requires an ASPS which is permitted to meet NFPA 13R (IBC-2021 Section 903.3.1.2). Regardless of these “permissions”, a NFPA 13 ASPS was installed including protection of the attic.

The scoping Code (e.g. IBC-2021) determines WHERE an ASPS is required (e.g. based on Occupancy Classification = Group R-4, Condition 1 or 2) and WHERE an ASPS can be omitted.

“IBC-2021 903.3.1.2.3 Attics” identifies (3) parameters WHERE attic protection by an ASPS is required. If this existing building does not meet 1-3, attic protection by an ASPS is NOT required. If the building is classified as Group R-4, Condition 2 occupancy, 903.3.1.2.3 (4) permits the omission of ASPS attic protection “not required by Item 1 to have sprinklers shall comply with one of the following” … see a, b, c, or d in REFERENCES below. If the building is classified as Group R-4, Condition 1 occupancy, only 1-3 of 903.3.1.2.3 is required to be followed.

Modification of an existing ASPS will require submission of Drawings to the local AHJ. Additionally, since this facility may be licensed by a state agency, this ASPS modification may/should be forwarded to them for their review and approval.

REFERENCES
IBC-2021
Chapter 9 Fire Protection and Life Safety Systems
Section 903 Automatic Sprinkler Systems
903.2 Where Required
Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12.
903.2.8 Group R
An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout ALL buildings with a Group R fire area.
903.2.8.2 Group R-4, Condition 1
An automatic sprinkler system installed in accordance with Section 903.3.1.3 shall be permitted in Group R-4, Condition 1 occupancies.
903.2.8.3 Group R-4, Condition 2
An automatic sprinkler system installed in accordance with Section 903.3.1.2 shall be permitted in Group R-4, Condition 2 occupancies.

903.3 Installation Requirements
Automatic sprinkler systems shall be designed and installed in accordance with Sections 903.3.1 through 903.3.8.
903.3.1.1 NFPA 13 Sprinkler Systems
903.3.1.2 NFPA 13R Sprinkler Systems
Automatic sprinkler systems in Group R occupancies shall be permitted to be installed throughout in accordance with NFPA 13R where the Group R occupancy meets all of the following conditions:
1. Four stories or fewer above grade plane.
2. The floor level of the highest story is 30 feet (9144 mm) or less above the lowest level of fire department vehicle access.
3. The floor level of the lowest story is 30 feet (9144 mm) or less below the lowest level of fire department vehicle access.
4. The number of stories of Group R occupancies constructed in accordance with Sections 510.2 and 510.4 shall be measured from grade plane.
903.3.1.3 NFPA 13D Sprinkler Systems
Automatic sprinkler systems installed in one- and two-family dwellings; Group R-3; Group R-4, Condition 1; and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D.

903.3.1.2.3 Attics
Attic protection shall be provided as follows:
1. Attics that are used or intended for living purposes or storage shall be protected by an automatic sprinkler system.
2. Where fuel-fired equipment is installed in an unsprinklered attic, not fewer than one quick-response intermediate temperature sprinkler shall be installed above the equipment.
3. Where located in a building of Type III, Type IV or Type V construction designed in accordance with Section 510.2 or 510.4, attics not required by Item 1 to have sprinklers shall comply with one of the following if the roof assembly is located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access needed to meet the provisions in Section 503.
a. Provide automatic sprinkler system protection.
b. Construct the attic using noncombustible materials.
c. Construct the attic using fire-retardant-treated wood complying with Section 2303.2.
d. Fill the attic with noncombustible i

Reply
Todd E Wyatt
1/9/2024 08:55:40 am

REFERENCES continued ...

4. Group R-4, Condition 2 occupancy attics not required by Item 1 to have sprinklers shall comply with one of the following:
a. Provide automatic sprinkler system protection.
b. Provide a heat detection system throughout the attic that is arranged to activate the building fire alarm system.
c. Construct the attic using noncombustible materials.
d. Construct the attic using fire-retardant-treated wood complying with Section 2303.2.
e. Fill the attic with noncombustible insulation.

Chapter 3 Occupancy Classification and Use
Section 310 Residential Group R
310.5 Residential Group R-4
Residential Group R-4 occupancy shall include buildings, structures or portions thereof for more than five but not more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised residential environment and receive custodial care. Buildings of Group R-4 shall be classified as one of the occupancy conditions specified in Section 310.5.1 or 310.5.2. This group shall include, but not be limited to, the following:
Assisted living facilities

310.5.1 Condition 1
This occupancy condition shall include buildings in which all persons receiving custodial care, without any assistance, are capable of responding to an emergency situation to complete building evacuation.
310.5.2 Condition 2
This occupancy condition shall include buildings in which there are any persons receiving custodial care who require limited verbal or physical assistance while responding to an emergency situation to complete building evacuation.

Reply
Pete H
1/9/2024 09:48:04 am

Agreeing with everyone else, it theoretically can, but if the architect used anything that required the building to be NFPA 13 or fully sprinklered for ICC code compliance, you've now opened that can of worms by changing the system.

On the bright side, if you're repairing a system with corrosion issues that is now 13R, decent odds you can get CPVC pipe to work which Lubrizol keeps assuring me is better at resisting/mitigating corrosion.

Reply
Jesse
1/9/2024 10:21:27 am

I would recommend doing a full analysis of applicable code. There's a reason the original install was full 13 and not 13R.

Reply
Todd E Wyatt
1/10/2024 08:43:23 am

"The only reason they installed the 13 system is initially they envisioned possible adding a skilled care section which is now not happening."

"Skilled care" would result in the building being classified as a Group I-2 IF the patients (versus residents) are incapable of self-preservation without assistance. Group I-2 buildings are required to be protected by NFPA 13 sprinkler systems.

Reply
Sean
1/10/2024 07:26:56 pm

Removal of systems is difficult, time consuming, and does not always work out.

Don't make this the building / fire department issue. Prove your thesis then present it.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Sept '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 221
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    October 2026
    September 2026
    August 2026
    July 2026
    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT