MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

OK to Have an Oversized Fire Pump with Tank?

2/26/2024

9 Comments

 
I have a project with Miscellaneous Storage of Class I commodities up to 12'-0" and Group A plastics up to 5'-0".

The water supply is a tank fed from a well. Based on NFPA 13-2016 Table 13.2.1, I designed to Ordinary Hazard Group 2 with a 90 minute duration of available water. My original demand was 57 psi at 385 gpm.

Our pump supplier provided a vertical in-line pump rated to 80 psi  400 gpm. The client is now unhappy about the volume of water being required so they are removing the Group A plastics from their building so we can calculate to OH I with the new demand being 41.5 psi at 304 gpm.

We have already installed most of the system and the pump is ready to be delivered soon.

Is it okay to have an oversized pump?

Can it be limited to a smaller flow to accommodate the new demand?

​My worry is that it will flow at the rated capacity and if we are sizing our tanks 10,000 gallons less than originally planned we would run out of water.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe​​
9 Comments
J Golden
2/26/2024 08:09:05 am

Side note;
Do you not add water capacity for hose / Fire Dept use?
Or do you have other water available?

Reply
sean
2/26/2024 01:16:11 pm

The code does not require that a tank include hose allowance as the system is not designed to support line personnel pulling off the same water supply (tank).

Reply
Jack G
2/26/2024 02:53:16 pm

I believe it’s only hose , or if a hose rack system the hose demand.

Reply
Dan Wilder
2/26/2024 08:15:18 am

Some thoughts

-Yes, no issue oversizing a pump for the stated demand. While not normally provided (costing and water usage), there is nothing prohibiting it.

-Can the pump be modified, possibly yes, but likely not a path that would be pursued. This would involve changing the pump characteristics, specifically the impeller which would mean the factory would need to make the changes and recertify (additional time in the factory and $). The connections to the fire pump will also be oversized due to the larger casing and the potential lesser rating (if this is available from above).

-Testing of the fire pump should not be an issue with the lesser tank volume as that duration should not be near the 90 minutes of total flow in either hazard design and likely piped back into the tank anyway. Propose a flow meter keeping the actual discharge of water reduced to every 3 years.

-The other option possible is to keep the fire pump as is and install a flow control valve feeding the system (Viking J-1 for example).

In all of these, I am a little suspicious that an owner is going to arbitrarily just going to remove his ability to store items simply based on water usage from a tank. If there is buyer's remorse from paying for a larger tank, is it going to get better when they have to pay for it twice when they get caught storing those same commodities?

Ultimately, the time for changes has likely passed and the fixes to solve the issue will likely be more expensive than accepting the system as proposed unless there is some mitigating factor like refill times (8 hours) but that can be overcome via manual means IF the need arises and a basic SOP as a backup to detail any deficiencies (water trucks, metered hydrant tie-in...).

Reply
Glenn Berger
2/26/2024 08:19:43 am

A 400 gpm fire pump for a water demand of 385 gpm is not considered oversized. The pressure rating of 80 psi v. 57 psi could be a manufacturer available size.

Need to be careful about balancing demand with supply condition. Based upon the information I do not see an issue, but curious to see what others will say.

Reply
Jack G
2/26/2024 08:55:01 am

Assuming the problem is 150% for 90 minutes and not having a large enough tank,
The fire pump will only flow to the amount of sprinklers that open.
The system piping could be sized so ithe system only flows X amount of water with little overage like a deluge system..
or use a flow control valve where the aperture opens to Y amount of pressure.
I would do a supply calc and reduce pipe sizes so there is not much overflow. I.E. the supply calc equals the demand calc.
Then only the system flow determines the tank size.

Reply
Jesse
2/26/2024 10:03:55 am

There used to be a day when we'd just throw a monster pump in a building and call it good.

First, your pump isn't oversized. And even it were, there's no code prohibition against that.

Consider a rack storage warehouse with Group A with ESFR supplied by a 2,000GPM @ 100-psi pump. That pump is still supplying the office area which is 0.10 / 900 (w/ QR reduction). That demand is less than 150-gpm and we would still be good.

Is the concern in the stored volume of water?

Reply
Casey Milhorn
2/26/2024 03:17:01 pm

I think others have covered it fairly well.

We don't do calcs based on what the system will ACTUALLY do during a fire event, just that it meets the minimum based on preset variables (location of fire event, shape of area, number of heads, density, end head pressure, etc.). One head flowing looks a lot different than 12 heads flowing, and which ones flow, and in what order they are activated, etc.... that's a slippery slope to play on if we start saying "what if"...

My opinion, tank size should only be based on your most demanding calculation x duration (with any hose when applicable). Not based on the fire pump capacity itself. (We hope whoever sits on the NFPA committees have thought about duration with plenty of safety margin built in).

Tank sizing is not an exact science as it doesn't take into account how much could flow in any given scenario. I would say there are cases where 3 or 4 heads located immediately off a large main and close to the riser would actually flow more than 8 or 10 heads off of small branch lines located at the end of your system. Unlike HVAC systems where air flow is actually balanced in a system that has open diffusers all the time, we are playing in at what if this area, with these many heads, in this shape were to activate. That's what kills me when someone picks apart a calc like that.

Great question!

Reply
Rodney
2/29/2024 04:48:00 am

An oversized pump is fine, but the tank should be sized according to the duty point, plus dead water and freeboard. There control valves can likewise be sized accordingly with pump delivery being restricted by using equivalent lengths of pipe, similar to an orifice plate but with a more linear flow impact. Essentially replacing a pre calculated length of distribution mains above the alarm valve with a smaller diameter pipe over the calculated length then reverting to the designed diameter. This solution provides for a quick correction of a system’s flow delivery characteristics where you have a fixed water supply and or need to adjust an existing system’s delivery curve.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top June '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 45
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT