MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Second Valve Required on a Fire Service Main?

6/7/2023

13 Comments

 
I'm working with a city inspector who is adamant that we add a second non-rising stem valve (NRS) in the fire sprinkler service main just before the building. The first valve being in the street at the live-tap location with the roadway box.

Is a valve required on the service main before the building?

The requested location would place the valve under the sidewalk, accessible by T-handle wrench only, prohibiting reliable supervision of any kind.

I can't seem to find any language in NFPA 24 that I can use to argue against the second unsupervised valve. I don't see any value in the position the inspector has taken and requested a copy of the city ordinance requiring the additional valve.

Installing the second valve wouldn't be a huge deal but certainly seems like an unnecessary opportunity for an unsupervised valve to get closed or fail. I would like to hear what others in this community think and if anyone has something to offer.

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
13 Comments
Pete H
6/7/2023 06:37:10 am

This sounds like it could be a local ordinance requirement. I can't think of any code that would require additional control between the riser inside the building and the curb box valve

Reply
M
6/7/2023 08:15:57 am

Try NFPA 24 §6.6.1, it provides direction when sectional control valves are needed. It is based on the number of fire protection connections - 6. This includes hydrants, lead-ins, risers, etc.

This requirement may be requested due to the number of fire protection connections b/w the point of connection and lead-in.

Reply
Glenn Berger
6/7/2023 08:25:57 am

If the city inspector requires it, you will need to check the city regulations to validate.

Be careful of a Catch-22 condition - PIV distance from the building in accordance with NFPA 24.

Reply
JH
6/7/2023 08:34:17 am

A valve is required. All criteria for compliance must be met for whichever valve assembly is chosen.

NFPA 24:6.2.9 All connections to private fire service mains for fire protection systems shall be arranged in accordance with one of the following so that they can be isolated:
(1)*A post indicator valve installed not less than 40 ft (12 m)
from the building
(a) For buildings less than 40 ft (12 m) in height, a post
indicator valve shall be permitted to be installed
closer than 40 ft (12 m) but at least as far from the
building as the height of the wall facing the post indicator valve.
(2) A wall post indicator valve
(3) An indicating valve in a pit, installed in accordance with Section 6.4
(4)*A backflow preventer with at least one indicating valve not
less than 40 ft (12 m) from the building
(a) For buildings less than 40 ft (12 m) in height, a backflow
preventer with at least one indicating valve shall
be permitted to be installed closer than 40 ft (12 m)
but at least as far from the building as the height of
the wall facing the backflow preventer.
(5)*A nonindicating valve, such as an underground gate valve
with an approved roadway box, complete with T-wrench,
located not less than 40 ft (12 m) from the building
(a) For buildings less than 40 ft (12 m) in height, a nonindicating
valve, such as an underground gate valve
with an approved roadway box, complete with
T-wrench, shall be permitted to be installed closer
than 40 ft (12 m) but at least as far from the building
as the height of the wall facing the non-indicating
valve.
(6) Control valves installed in a fire-rated room accessible
from the exterior
(7) Control valves in a fire-rated stair enclosure accessible
from the exterior as permitted by the AHJ

Reply
Brett
6/7/2023 08:44:21 am

If none of the requirements listed by "JH" apply, then ask the inspector to provide the code citation he is using to make his request.

Reply
SCHULMAN
6/7/2023 09:45:52 am

Required here ... usually satisfied by the Backflow Preventer

Reply
Jon
6/7/2023 09:58:27 am

The leading cause of sprinkler "failures" is a closed valve. The more valves on a system (either interior or exterior), the greater chance that one could be closed - whether intentional, inadvertent, neglected, or forgotten.

Yes; the city utility often requires a shut-off for various legitimate reasons (broken pipe, water supply maintenance, non-payment, etc.) but not sure that a second shut-off gains anything.

More is not always better when it comes to fire protection systems.

Reply
Alex
6/12/2023 06:44:42 am

Late to the game here. I agree with Jon. I would verify with the city ordinances but would avoid adding the valve if possible.

Reply
Eric R
6/7/2023 12:46:11 pm

I wonder if this is maybe a regional thing, but from my experience there is always a secondary underground valve on the private property for underground lines.

In my area the valve that is directly at the tapping saddle on the primary street main is owned by the water purveyor, and we are strictly not allowed to touch these valves as a private contractor. Then a second underground valve is installed on the feed once it crosses onto the private property as the start point of the 'private fire service main'. We are allowed to touch this valve in case repair work is needed on the private line.

Personally I think this valve is important to have as it allows for repair/replacement of the first aboveground control valve, or the backflow preventer. Both of which generally need servicing before to long.

It does add an extra valve that needs to be inspected/tested, but is not required to be monitored since it is below grade and can only be accessed with a special tool.

NFPA-25 could probably more clear about the specific testing requirements for curb valves, but FM Gobal inspections do require that the valve be physically tested to confirm full open monthly, and fully exercised yearly.

Reply
Casey Milhorn
6/12/2023 02:43:00 pm

Late in responding to this one, but JH has the correct section cited. I'm pretty sure NFPA 24 used to say (in order of preference, or something along those lines but not anymore). Technically you only need ONE valve per NFPA and it can be anyone of those listed (with the exception of additional valves for sqft limitations and sectional control valve requirmements). This could be the tapping valve at the street, a property line valve, a PIV outside, a Wall PIV, a valve on the riser without direct outside access, etc.... BUT a lot of AHJs do have a preference on what they prefer or require. As others have stated, the least amount of valves the better (especially unsupervised ones). Typically the water department is going to get whatever they want (1 valve or 10 valves) up the property line. The AHJ (fire marshal or codes) can ask for whatever they want after the property line and inside the building, BUT you may want to ask for the amended code or reference on where they are getting that from to cover your tail.
My personal feelings on valves are:

1. The fewer the better
2. First choice is a remote PIV away from the building (for protection of the fire fighters)
3. Second choice is a wall PIV
4. Third choice is a riser room with direct outside access
3. Supervised remotely whenever possible and avoid additional UG NRS gate valves.

Reply
Todd Delisle
6/14/2023 08:24:39 am

I've had projects for MIT that have required this; Cambridge (MA) Water Department:

Please Note: CWD requires a permanently installed valve, acceptable to the fire sprinkler design engineer of record, inside the building and just upstream of the backflow device. This valve allows for the efficient removal of the backflow device, for any reason, without the need to shut the service off at the water main in the street.

It is published on their website for "Conditions for Approval" and was cited at the time plans were being developed. Nice that they provided narrative for reasoning.

A little different with the valve being inside the building where it was afforded a tamper and low pressure switch if I recall correctly.

Reply
Dave Auman
7/31/2024 11:16:53 am

We have a Fire Main that has a valve off the water main. From there it feeds three buildings. Two of which have an isolation valve. The third is a new building and they don't want to put in an isolation valve outside the building before the backflow. so, if there is any issue with the #1 valve on the backflow, we will have to stop water to two other buildings. Is this ok

Reply
Jack G
1/16/2025 10:28:33 am

I agree with Todd/Casey.
Usually not permitted to touch the street valve if a second valve is furnished , wall post or post indicator, or another valve/ curb box and key the street can be isolated if the back flow “ assembly “ needs replacing.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Nov '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT