MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Press. Reducing Valves Req'd for Dry Standpipe?

5/16/2024

8 Comments

 
When are pressure reducing hose valves required on a dry automatic standpipe system?

I have a project where I have been asked to evaluate an existing sprinkler system for an 8-story apartment building. The original installation falls under NFPA 13/14/20 2013 edition. The building is served by four dry automatic standpipes and a separate wet sprinkler feed. The standpipes are not combination sprinkler/standpipes.

The fire pump churn pressure is 212 psi and there is a pressure reducing valve provided for the wet system supply.

There is no pressure reducing valve for the dry automatic standpipes. The hose valves on the standpipes are the pressure restricting type. Not pressure reducing.

When reviewing the data sheets for the hose valves, it states "Adjustable restriction of pressures up to 175 lbs....at residual flow" but the valves themselves are rated to 300 psi. At normal, non-fire conditions, the standpipes have 23 psi static pressure of air, but if the dry valve were to trip for any reason, (non-fire or not) the standpipe exceeds 175psi static pressure on the 1st-7th floors.

NFPA 14 2013 states that "7.2.3.2* Where the static pressure at a 21⁄2 in. (65 mm) hose connection exceeds 175 psi (12.1 bar), an approved pressure regulating device shall be provided to limit static and residual pressures at the outlet of the hose connection to 175 psi (12.1 bar)."

Would the static pressure be considered the normal air pressure or the static pressure if the dry valve trips?

My assumption here would be that the pressure restricting valve needs to be swapped for a pressure reducing type.


Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Anthony
5/16/2024 08:20:48 am

There are pressure regulating hose valves and pressure reducing ones. I intemperate 7.2.3.2 as requiring a maximum static pressure at 175 psi. I think to prevent initial blow back on the hose when the fire fighter opens the nozzle. This is a case where I'd use the corker 5500 SERIES NON-ADJUSTABLE PRESSURE REDUCING VALVE or the field adjustable one at the standpipe. Or I'd use a pressure reducing valve manifold as called for in 14 for 2 or more hose valves.

Reply
Steve Cooper
5/16/2024 09:33:10 am

In the snip of NFPA 14 above, it uses the word limit. When they use the word limit it makes me think they would want a pressure restricting since they don't want it going higher. But the pressure limiting valves I have seen limit 100PSI not higher.

The Croker 5500 PRV sheet doesn't state how much it reduces by. Would that affect your ability to use that? I have not used them before, but I do see a note saying they are factory set. Do you notify the company when ordering the psi requirements you have?

Reply
Dan Wilder
5/16/2024 09:47:59 am

What was the originally approved installation? What has changed that would justify the change from the (assumed) approved installation? Section 1.3 for Retroactivity provides allowances to avoid having to change already approved and installed (correctly) systems.

Is there any signage or coordination with the Fire Department concerning the static pressure being above 175PSI on initial charging of the hoses? Once they start flowing water, the pressure will drop to the more normally encountered <175PSI.

Most trained fire departments can handle these pressures initially with knowledge prior. If the SOP has changed or the responding FD/Insurance wants things changed, yes, recommend the change the valves as needed.

As to the Normal Working Pressure, the definition below (From the 2019 NFPA 14), I would say that the working pressure would be the automatic pressure one would see without use of the FDC under working conditions (valve tripped).

3.3.24 System Working Pressure.
The maximum anticipated static (nonflowing) or flowing pressure applied to standpipe system components exclusive of surge pressures.

Not specific to standpipes but some good reading.

https://nfsa.org/2022/11/08/system-working-pressure-and-fdcs/

Reply
GRAHAM N
5/16/2024 03:06:31 pm

The approved installation shop drawings show one detail of the standpipe with pressure restricting hose valves (with note: "typical for floors 1-7) and then the drawings also show a separate cross-section view of: building, standpipe, and static pressures with a note that pressure reducing valves are required on floors 1-7.

Pressure restricting valves were installed so this has me scratching my head.

Reply
Jack G
5/16/2024 11:34:30 am

Agree that the valves should be changed out to prv s. The factory set type is ordered with the pressures of your specific jobs, however I prefer the field adjustable type that the fire department can adjust.
I was involved with the Meridian fire where I made adjustment rods ( from all thread rods ) and showed the fire fighters how to open the prv s to fullly open) prvs were new to the area back then.
To no avail. We found out that fittings in the basement used to make the cut ins were only approved——- some to only 75 psi.
On automatic dry standpipes I would add ( emergency pull stations) so that when you pull them it opens a half inch valve to bleed the air. Easy to close later. ( in trim of deluge valves)

Reply
Casey Milhorn
5/17/2024 08:47:37 am

I agree with Jack on this one but also Dan to what is your exact scope? It sounds like you have been contracted to evaluate and make suggestions, and to Jacks point not a big fan of the factory set type of pressure restricting valves. That's a chance to suggest replacing these existing valves, maybe not from a code perspective but from a practical and possibly life saving perspective for the responding fire fighters.
The field adjustable are rated to take up to 400 psi and reduce down to an acceptable range approved by the actual user, the fire responding fire department. They can be evaluated on a regular basis and adjusted to match current conditions of the pump and city combined supply.
Again, if your scope is evaluate based on "is it an approved installation based on the applicable standards at the time" then I think this suggestion to change out the PRVs is just that, a recommendation but not a code deficiency. imo.

Reply
Graham N
5/22/2024 04:02:26 pm

Casey,

Since the building was recently taken over by a new owner and property management group, I was asked to restore the building fire protection to full operation and then to check compliance with the original installation shop drawings and applicable codes.

The sprinkler system has been unmaintained for over two years and was not operational when I first visited the site. The sprinkler system also has discrepancies as to what was designed vs what was installed.

The local AHJ is pretty much nonexistent despite this being a high-rise building.

To your hose valve question,

Per the listing of the pressure restricting valves that are installed, they can only restrict pressures up to 175psi. The static pressure on the dry standpipe (when the dry valve is tripped) is 210psi and then falls as you increase in building height. The static pressure (When the dry valve is tripped) exceeds the pressure restricting valves listing to restrict pressure.

My initial recommendation was the install pressure reducing hose valves or install a PRV before the dry valve for the standpipe.

Reply
Casey Milhorn
5/22/2024 04:37:42 pm

That makes sense and the fact that the existing pressure restricting valves are only listed for 175 psi should trigger a recommendation by you at the very least. I would be very careful with the install of a master PRV (which actually you would need to install 2 of them in series, with bypass assembly, as shown in NFPA 14). You might end up restricting the pressure to below 100 psi at the top @ 500 gpm. Not to mention these master PRVs can be unreliable (from stories I've heard). The field adjustable pressure regulating hose valves is probably the way to go. If you are not a PE or FPE, I would highly advise recommending that one be brought in to bless the changes. Just put it as an add price in your contract and if the owner elects to not pay for that option, that at least should reduce some liability on your part. This all sounds like a commonsense solution until the PRVs aren't tested and adjusted on a regular basis in the future and a firefighter and/or building occupants perish due to owners failure to maintain the system. But in this case, it does sound like the owner is interested in doing the right thing.




Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Dec '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT