MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Valve for Hose Connection on Sprinkler System?

9/20/2023

7 Comments

 
We're working on a one-story school. The AHJ (Fire Marshal) is requiring inside 2 1/2-inch hose valves at the exit locations.

These hose valves are fed directly off the wet sprinkler system main - not fed from a dedicated standpipe main.

1. I'm having trouble finding code regarding feeding hose valves off of the wet system main.

2. I'm trying to determine if the pipe, off the main, to these hose valves, needs a control valve installed.

Appreciate the tips and insight. 

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments
David Kendrick
9/20/2023 08:18:38 am

This may be a local requirement memorialized in addition to the building standards.

You should be able to ask for or access the current adopted codes and standards with any modifications.

There you may have your answer.

Reply
Todd E Wyatt
9/20/2023 08:37:41 am

It is permissible to request the AHJ provide the section of the adopted Code and/or Standard for this "requirement."

Review of the scoping Code (e.g. IBC-2021) and the referenced standard (e.g. NFPA 13 - 2019 Standard for the Installation of Sprinkler Systems) did not yield results for "requiring inside 2 1/2-inch hose valves at the exit locations."

If this school (Group E Occupancy Classification) is >12K SF and has an Occupant Load >300, then an automatic sprinkler system (ASPS) is required per IBC-2021 903.2.3.

The referenced ASPS standard (NFPA 13 - 2019 Standard for the Installation of Sprinkler Systems) includes (7) references of "EXIT" but none address your specific conditon.

REFERENCES
IBC - 2021
Chapter 9 Fire Protection and Life Safety Systems
Section 903 Automatic Sprinkler Systems
903.2 Where Required
Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12.
903.2.3 Group E
An automatic sprinkler system shall be provided for Group E occupancies as follows:
1. ​Throughout all Group E fire areas greater than 12,000 square feet (1115 m2) in area.
2. The Group E fire area is located on a floor other than a level of exit discharge serving such occupancies.
Exception: In buildings where every classroom has not fewer than one exterior exit door at ground level, an automatic sprinkler system is not required in any area below the lowest level of exit discharge serving that area.
3. The Group E fire area has an occupant load of 300 or more.

NFPA 13 - 2019
Standard for the Installation of Sprinkler Systems

Search for "EXIT" = (7) References
9.2.3.4 ...Sprinklers shall be permitted to be omitted from an exterior EXIT corridor where the exterior wall of the corridor is at ...
D.1.1.9.2 ...and service elevators shall be permitted to open directly onto EXIT passageways, provided that all of the following criteria are met: ...
D.2.23.2.2 ...and service elevators shall be permitted to open directly onto EXIT passageways, provided that all of the following criteria are met: ...
D.1.1.10.2 ...and service elevators shall be permitted to open directly onto EXIT passageways, provided that all of the following criteria are met: ...
D.2.24.2.2 ...and service elevators shall be permitted to open directly onto EXIT passageways, provided that all of the following criteria are met: ...
D.2.4.1.1 Protection of Vertical Openings. ...2) EXIT access stairs from lighting and access catwalks, galleries, and gridirons ...
D.2.3.1.1 Protection of Vertical Openings. ...2) EXIT access stairs from lighting and access catwalks, galleries, and gridirons ...

Reply
Casey Milhorn
9/20/2023 08:59:39 am

I think what they are asking for are hose connections from the A/S system, not a full hose valve and standpipe system. Below is from NFPA 13, 2016 ed.

8.17.5.2 Hose Connections for Fire Department Use.
8.17.5.2.1 In buildings of light or ordinary hazard occupancy,
21⁄2 in. (65 mm) hose valves for fire department use shall be
permitted to be attached to wet pipe sprinkler system risers.
8.17.5.2.2* The following restrictions shall apply:
(1) Each connection from a standpipe that is part of a combined
system to a sprinkler system shall have an individual
control valve and check valve of the same size as the connection.
(2) The minimum size of the riser shall be 4 in. (100 mm)
unless hydraulic calculations indicate that a smaller size
riser will satisfy sprinkler and hose stream allowances.
(3) Each combined sprinkler and standpipe riser shall be
equipped with a riser control valve to permit isolating a
riser without interrupting the supply to other risers from
the same source of supply. (For fire department connections
serving standpipe and sprinkler systems, refer to Section 6.7.)

Depending on how the above code section is interpreted, you may not be allowed to connect to an A/S system downstream of the control valve/riser.

If these are considered "horizontal exits", you might be required to provide a full NFPA 14 Class I system and connecting to the sprinkler system downstream of the system control valve may not be allowed.

But if this is just an ask from the AHJ, you also need to clarify how much gpm and pressure they are expecting at this valve? I wouldn't calculate any less than 250 gpm. Pressure probably won't matter to them as they expect to have to connect to the FDC with the pumper truck to get what they need out of it. I would highly recommend adding signage that says manual wet hose valve, or some wording like that.

Reply
John link
9/20/2023 09:56:32 am

I've seen the 2 1/2" hose valves in glass cabinets in schools on the wall near exit signs.

Reply
Dan Wilder
9/20/2023 11:21:52 am

What is the intent of the Fire Department for use of the hose valves? Are they being used for secondary, ancillary cleanup or direct fire fighter operations?

NFPA 13-22' Section 16.15 (and 20.14 but this isn't storage) is specific to hose valves attached to sprinkler systems but this is not for direct fire fighting applications because they are not calculated the same as an NFPA 14 design. The only requirement is to add the 50GPM per valve up to 100GPM to satisfy Inside Hose requirements. Minimum pipe size to be 2.5" for feeds (in my experience) but I've gotten away with 2" with approval.

I would suggest against an additional control valve controlling the hose valve in lieu of signage and maybe a gauge at the connection.

Reply
Jesse
9/20/2023 11:42:15 am

We see this a lot with large footprint buildings and it has to do with distance from the fire apparatus lane. We handle with just a 2.5" drop from the AS main to a hose valve.

Reply
Sharon
9/21/2023 09:57:10 am

We have been required to provide these on schools lately because they are bringing in the "Mall" criteria. This has been allowing the architect a bit more flexibility with building locations, etc.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Feb '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT