MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

How to Fix Fluctuating Pressure on Pump Suction?

4/14/2023

5 Comments

 
Hi everyone - thanks for answering my previous questions and for checking out today's as well.

I have three projects all connected to the same central fire pump assembly. It's a huge network of pipe running for miles. 

The client is having a problem with the fluctuating pressure (up and down) on the network for some reason that affects the fire pump's suction pressure. It's in series, and connected to each project.

The client refuses to add a break tank and cut the fluctuation. 

In your experience, is there any alternative solution available? 

Would a pressure relief valve help? What would happen when the pressure is less than design?

Thanks in advance!

​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
5 Comments
Jesse
4/14/2023 08:15:52 am

With the mention of a break tank, I presume the water source is municipal? How wildly are the pressures at the intake flange fluctuating?

Reply
Eric R
4/14/2023 08:40:14 am

If your water supply pressure is dropping below the point where the fire pump discharge is no longer able to provide the required system demands then that is a pretty big problem.

Since a break-tank would require the installation of a new fire pump anyways, perhaps a less expensive option would be to keep the municipal connection but replace the fire pump to one that can provide the system demands even at worse case suction pressure.

This would likely create a situation where at pump churn you exceed the 175psi pressure rating of your systems, so the fire pump will likely need to be paired with a master pressure reducing valve to keep pressures downstream of the pump under control.

You will want to make sure that during times of low residual pressure you aren't creating dangerously low-pressure condition upstream of your pump at whatever your peak system flows are.

I had a similar situation at an industrial plant that we resolved in this way, and using a PRV to control the pressures across the entire site worked wonders, and made the NFPA 25 testing procedures so much easier at the facility.

Reply
Franck
4/14/2023 12:03:56 pm

I think you are spreaking about a Pressure Relief Valve (PRV) not a Pressure Reducing Valve.
A Pressure Relief Valve is commonly used on fire protection systels and are quite reliable.
A Pressure Reducing Valve is normally limited to some situations, such as the lower floors of a high rise building with a pump delivering a high pressure to reach the upper levels.
They are less desirable for fire protection systems because of the additional friction losses (not always accounted in hydraulic calculations) and possible maintenance issues on them.

Reply
Dan Wilder
4/14/2023 08:50:44 am

Trying to understand the setup...

1 main fire pump (supply from municipal or tank)
1 fire pump for each of the 3 projects attached?
Any large elevation changes?

If the site is setup more like a tree than a loop, try adding check valves immediately after the tees to the downstream systems to help retain pressures?

Maybe the first jockey pump is undersized for the amount of underground leakage for the site as a whole (underground loss volume near equal to the capacity of jockey pump)?

14-22' Ed - 4.27.3 Pressure maintenance pumps shall have rated capacities not less than any normal leakage rate.
Enhanced Content - An exception to this general rule is when older underground systems leak excessively. In such a case, the jockey pump capacity should be increased further, based on the leakage rate of the underground system.

Is there a possibility to close the supply to the whole system - or sections of that system - and monitor pressure loss over a time period to allow some guess of how many gallons are being lost through the UG system? You would need to know the volume of the water and PSI loss to some accuracy (digital gauges and accurate UG routing).

I had a recent project that the jockey pump was sized correctly as to PSI, but the GPM was oversized causing a water hammer when the JP kicked on, saw the PSI increase and shut off, the system would have a PSI wave drop and the JP would kick back on again....this cycled 3-5 times and would trigger the fire pump to come on. We replaced the JP with a lesser GPM pump (same PSI) and the issue went away. First time I (and many others) had seen that issue in a system.

Reply
Casey Milhorn
4/14/2023 11:57:07 am

Check out the Zurn low suction control valve, copied the text below for you. If you are having mostly low suction issues, this may solve it. I'm personally leery about restricting flow to a fire protection supply, but it might be the trick you need.

If you are having high pressure issues, then a PRV on the discharge side would take care of that.

Before installing both on the same system (or anything for that matter) I would reach out to the guys at Zurn. They are extremely knowledgeable about their products and pressure control in general.

I would also put some money in there to monitor the suction and discharge pressures during testing (at the common times for peak fluctuations) and also a 24 hour monitor/recorder for a week or two to see how everything is working.

Just my two cents.

ZW215FP
Fire Pump Suction Control Valve
The ZW215FP Fire Pump Suction Control Valve, with grooved connections, is used to control suction pressure for Fire Suppression Systems to prevent fire pumps from over-drawing from the water supply, causing damage to the pump or supply network due to low or negative pressures on the fire pump suction side. The ZW215FP prevents cavitation and potential backflow conditions by maintaining a minimum inlet pressure to a Fire Protection Pump. Its internal and external epoxy coating resist corrosion, and the test cock on the sensing port allows for quick bleeding of the sensing line.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Nov '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT