When retroactively adding a Double Check Valve Assembly (DCVA) to an existing system, we need to verify that the new DCVA does not adversely affect the system's performance.
If no significant adjustments are required, I usually use the hydraulic placard information and compare it to a new hydrant test to determine the system's available pressure. I then subtract the pressure loss from the DCVA at the flow rate indicated on the placard. How do people deal with adding a DCVA to a pipe schedule system with no existing documentation? Thanks in advance! Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Pete H
7/18/2024 06:35:41 am
With no existing documentation?
Reply
Dan Wilder
7/18/2024 07:36:55 am
As most of my AHJ's require a letter submittal when adding in backflows retroactively, we perform a new flow test, calc the existing system via survey or as-builts (it is rare that the hydraulic placard is still on the valve), and provide those results in a writeup to the AHJ...inspector comes out to verify the calc plate being installed.
Reply
Anthony
7/18/2024 07:53:13 am
A pipe schedule system "calc" must be completed which is just a the elevation loss of the highest sprinkler and the loss through the backflow subtracted from the curve at 850 gpm (For OH). if you have 20 psi left you're compliant.
Reply
Anthony
7/18/2024 08:07:17 am
I miss typed I mean though 11.2.2.7 * in NFPA 13-16ed
Reply
NK
7/18/2024 08:07:30 am
Pete and Dan hit the nail on the head. The system needs to be recalculated with a current flow test to ensure the hydraulic calculations aren't compromised by adding a new backflow preventer (either based on field verified as-built fire sprinkler drawings or by resurveying the existing system).
Reply
Jesse
7/18/2024 10:20:32 am
I'd definitely calc the system. An insurance company I did a lot of work for in the past never would accept placard data (the VP of engineering was on 13), so we calc'd EVERYTHING.
Reply
Glenn Berger
7/18/2024 12:25:04 pm
Like others have said - Get new hydrant flow test and then hydraulic calculate the system. There used to be assumption information in some of the old FM Design Guides.
Reply
Jack G
7/18/2024 05:03:10 pm
The AHJ usually wants you do survey , new flow test and calculate.
Reply
Kyle R
7/18/2024 08:03:50 pm
I agree w/Anthony above. For an existing Pipe Scheduled system, NFPA 13 is pretty descriptive of how to retroactively add a BFP and the 'Calc' that is required.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop August '24 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
September 2024
PE PREP SERIES |