MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Dampers on Clean Agent Releasing or FA Panel?

2/16/2021

7 Comments

 
We are designing a clean agent system for electrical rooms located within a high-rise building. We are proposing having dedicated clean agent releasing control panels for the electrical rooms, and a separate building Fire Alarm Control Panel.

Is it mandatory to connect fire/smoke dampers (and other shutdown devices) in the electrical room with the clean agent releasing panel, or can these be connected to the building fire alarm system?

Thanks in advance.

​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments
Matt
2/16/2021 09:16:11 am

not sure about the code - but if the dampers play any role in the agent containment, you will want to make sure they close before the agent is discharged.

Reply
Pete
2/16/2021 10:09:28 am

I agree with both Matt and Doug. Depending on the age of the building FACP the functionality can be reduced from that of a modern panel, however, using solid state (solenoid) relays tied into fire alarm relays, there are a lot of options for setting up your action sequence.
The releasing panel could trigger programmed pre-action events, such as in the case of the Quell releasing panels starting the fire pump before releasing the solenoid on riser clapper.
Conversely, the detection pre-action triggers (smoke or heat) could theoretically be relayed through the sub-panel to send Trouble signals to the FACP which could in-turn initiate your shunt trips or whatever else you want to coincide with an alarm. I would consider these factors: 1) whether or not the shunt trip devices and dampers are already programmed to be performed by the FACP (if you're simply adding an initiating trigger to an existing program that is already wired to perform the desired operation, it would be far less work than starting from scratch), 2) whether you want the peripheral device events to be globally controlled (for ex. for a one stop bypass @ the FACP of notification appliances and shunt devices during inspections or during a fire emergency), and 3) if not code-mandated for the peripheral functions to precede the alarm event, are the shunt trip and baffles something you want to live with being inoperable for a clean agent system trouble until you get the system fixed? (smokes notoriously get dirty, go off in low temps, or just need to be changed out. If the system is shutting down the AHU in a freezing climate, are you willing to go without heat until an alarm tech comes out to change the smoke?

On the latter point, I would consider getting non-addressable, non-proprietary detection devices installed as pre-action devices for the proposed system. Then you could keep a spare stock, and a maintenance employee could pop the bad smoke out, install a new one out of the box, and reset the system.

Reply
Doug link
2/16/2021 09:29:00 am

If the clean agent panel is sending alarm, supervisory, and trouble signals to the building’s Fire Alarm Control Panel (FACP), both panels make up one fire detection and alarm system. If the main fire alarm system detects a fire, using staged evacuation, the main FACP will evacuate the building. If the clean agent panel goes into alarm and sets off an alarm in the main building’s FACP, the main FACP will evacuate the building.

Even though they are two different boxes on the wall, in two different locations, from the point of view occupant, and from the point of view of the firefighters entering the building, a fire is a fire.

OK, the firefighters deal with the fires differently if the fire is in the hallway, or if the fire is in the electrical room, but they’re there to put out a fire.

If your dampers and other shutdown devices are shut down by an alarm on the building’s FACP, an alarm on the clean agent panel, having activated the main FACP into alarm, will shut down the devices.

Reply
Darrell Wright
2/16/2021 01:21:47 pm

I just did an acceptance test on this exact situation. It was done exactly as Doug says. FM-200 system has its own panel that sends signals to the main FACP for the entire building. The main FACP controls all the other functions such as dampers, fire doors, evac, etc.

Reply
chad putney
2/16/2021 02:39:18 pm

As the clean agent system is designed to minimize down time and losses, you should minimize the potential points of failure in its execution.

The releasing panel should have its own output to the dampers. Otherwise you are relying on the main FACP to do the work.

Not to say that the main FACP cannot control the dampers in parallel however, if the connection to the main FACP is lost or the programming somehow is changed, etc, etc, the clean agent system won't work if the room isn't properly contained.





Muneer
2/17/2021 10:08:51 pm

As per NFPA 2001, 2018 edition,

4.3.3.9 All devices for shutting down supplementary equipment
shall be considered integral parts of the system and shall
function with the system operation.

As per my understanding, all shutdown devices shall be connected with Extinguishing control panel as per above clause of NFPA 2001.
Now, can we use this clause on Main Fire Alarm Panel of Building as Extinguishing control panel will be interfaced with it.

Reply
KANG
2/16/2021 04:45:41 pm

Connecting damper shutdown signal from clean agent panel to HVAC panel is not mandatory. Building fire alarm panel which is connected with fire detector can deliver confirmed fire signal to both HVAC control panel to shutdown damper and clean agent panel to release gas.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​January '21 Contributors!
    1. Franck
    2. CJ B.
    3. Dan W.
    4. Jesse
    ​5. Gleen B.
    6. Casey M.
    7. Mike
    8. Pete
    9. HJ
    10. Wayne


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About