We have a situation where we'll have a piece of equipment in one control area that has a closed-use pipe arrangement with oxidizing gases that goes through different control areas. I've gotten conflicting feedback on this. How do you figure the amount of "in-use" for each control area? Here's a sketch of the concept: The equipment that is using the oxygen is on the fourth floor Control Area 2. The tanks that feed it are (2) 200 CF oxygen tanks that are in the second floor Control Area 1.
Which of the following two scenarios is the proper way to tally up the "in-use" quantity for the fourth floor Control Area 2 when comparing against the Maximum Allowable Quantities (MAQs)?
My initial gut reaction was that the second option is correct, but now I’m not sure. My reasoning being that if there is an event in 4th floor control area 2 that causes a leak or something like that, it’s not going to just leak out what is physically within the control area… it’s going to leak out everything in all of the piping, all of the equipment, and all of the hooked up tanks. This is all presuming there are no safety devices to stop this from happening. Assuming my initial gut reaction was correct, is there a way to limit the amount so that it stops at the control area wall? As in: is there a safety device such as an automatic shutoff valve we can put at the wall such that in the event of a leak or other event, the automatic valve will shut off and then we only have to count the amount of gas between the equipment and the shutoff valve? I’ve looked in the IBC and its commentary for more info, but couldn’t find anything helpful. I’ve also reached out to a number of different people and there seems to be a variety of different opinions on it. Thanks in advance. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
12 Comments
Chad
2/2/2023 08:22:02 am
#2
Reply
chad
2/2/2023 08:24:52 am
IMO, this applies and that fits in use.
Reply
Mike
2/2/2023 01:04:47 pm
This will only apply if NFPA 400 is the charging document within the project jurisdiction. In jurisdictions that use IBC, NFPA 400 is not a referenced standard and is therefore not enforceable. IFC does reference NFPA 400, but not for defining in-use systems. It does reference it for quantities of oxidizing liquids and solids, but not gases.
Mike
2/2/2023 01:00:46 pm
According to IBC/IFC, though... in-use DOES count towards storage. Sub-Note B applies:
Reply
Mike
2/2/2023 01:10:10 pm
Apologies, I just re-read your original comment and see that you are saying the same thing: the whole thing is considered in-use.. everything hooked up to the system is in-use.
Glenn Berger
2/2/2023 09:01:35 am
This question would be best answered by someone specializing in health care / hospital design.
Reply
Mike
2/2/2023 12:45:47 pm
Glenn,
Reply
Todd E Wyatt
2/2/2023 09:02:23 am
Oxygen is a “Class 2 Oxidizer.”
Reply
Mike
2/2/2023 12:54:51 pm
Todd,
Reply
Alex
2/2/2023 11:45:43 am
Hi,
Reply
chad
2/2/2023 11:48:13 am
Agreed, no device would alleviate. Most places limit themselves to the 375 CF to avoid CA's
Reply
Tom
2/15/2023 08:42:50 am
NFPA 99 covers this I believe. Sorry not in a place I can research/reference it
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop September '24 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
October 2024
PE PREP SERIES |