MeyerFire
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
ALL THINGS FIRE PROTECTION | SUBSCRIBE NOW

Split-Case Fire Pump with Suction Under -1.5 psi?

10/23/2020

7 Comments

 
Can a split-case fire pump be used with a suction that is below negative 1.5 psi of pressure (below 1.0m)?

Would this be acceptable under NFPA 20?

Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments
Michael Fertal
10/23/2020 10:06:15 am

Can you provide additional info on the conditions? Is the supply city-fed or a water tank. Is the basis of the question from a design or NFPA 25 inspection?

Reply
Cameron Spence
10/23/2020 10:06:51 am

NFPA 20 permits up to -3 psi at the pump suction flange when pulling water from a storage tank that has its outlet at or above the pump suction elevation. Other than that, I believe 0 psi or greater is required at the suction flange when pulling from a water supply.

Are you getting the -1.5 psi at the system demand or at 150% of pump capacity?

Reply
Glenn Berger
10/23/2020 10:25:32 am

Simple answer - Do not use a split case fire pump in that application. NFPA may permit it - but the mfg or the water supplier may not.

Reply
Franck
10/23/2020 11:20:53 am

It depends on many conditions and if the AHJ allows you to do so.

If you have -1.5 psi at 150% because of friction losses in the suction pipe, this is related to NPSH and probably a too long suction piping that is not desirable.

If it is because you are taking suction under lift with an horizontal split case pump (your water level is below your pump level), it is normally not approved by NFPA as you should use a vertical pump in that case (NFPA allows the use of horizontal split case pump under head).

In Europe, we often have horizontal fire pumps under lift. And it was possible in older versions of NFPA 20 (prior to 1974).

In that case, we use a priming tank.

But remember this is not anymore in line with NFPA... NFPA 20 does not allow horizontal fire pumps taking suction under lift since its 1974 Edition, after several foot valve failures that caused the loss of the priming water destroyed the pumps running them dry. ...

But the following arrangement (if approved by AHJ) may prevent you to have problems with your current installation...

The maximum depth from which the pump would suck should not exceed 10 ft 6 in.
In practice, the pump should be installed at the nearest position to the suction location. When sucking from deeper points, separate suction lines should be arranged for each pump instead of a single collector in multi-pump systems.

The suction pipe should be immersed in water with an elbow, and a filter flap (or foot valve) should be installed to the suction pipe end side to keep water between the water level in the tank/pond/river and the pump casing.
There is no need to install a shut-off valve onto the suction line. The filter at the suction flap end should be occasionally cleaned up and prevented to be clogged with dirt and foreign substances.

A priming tank should be installed to fill the volume between the backflow preventer and the foot valve (upstream and downstream).
• The bottom of the priming tank should be at least 5 ft above the top of the pump
• Automatically filled tank only are accepted: volume at least 130 gal. or 3 times the volume of the suction pipe + pump casing, whichever is the greater
• The priming tank should be connected to the pump discharge upstream of the check-valve, with minimum 2 in. diameter pipe
• The priming connection should be fitted with a gate valve and a check-valve, as close as possible to the pump
• The priming tank should be fitted with a low level gauge, set at 2/3 of tank volume, to automatically start the pump on a low level condition, and allowing tank refill through a calibrated orifice

Reply
SK
10/23/2020 01:56:19 pm

If you are taking the suction from storage tank, then it's allowed as per NFPA 20. Section 4.15.3.2 otherwise not less than o psi. This means NPSHa can be lower when using tank.

NFPA 20, A.4.15.3.2. It is permitted that the suction pressure drop to –3 psi (–0.2 bar) for a centrifugal pump that is taking suction from a grade level storage tank where the pump suction elevation is at or below the water level in the water storage tank at the end of the required water flow duration. This negative suction pressure is to allow for the friction loss in the suction piping when the pump is operating at 150 percent capacity.

Reply
koray uluç link
10/25/2020 11:34:22 am

NFPA20 permits 0,2bar negative pressure at %150 flow when pump room floor and atmospheric water storage tank bottom is at same level.
This means that any NFPA20 fire pump must have NPSH required value at %150 flow lesser than 0,8 bar approximately.
Pump manufacturers should achieve this performance to be listed.
if your pump require less NPSH (Net positive suction head) than it can still supply enough pressure at %150 flow according to its curve even your suction line is not applicable according to NFPA20.
Keep in mind that generally low rpm pumps require less NPSHr

Reply
SHOAIB
10/31/2020 05:52:54 am

"This means that any NFPA20 fire pump must have NPSH required value at %150 flow lesser than 0,8 bar approximately."

Sir, Do you have any reference for this sentence?
If yes, would you please provide this reference number?
I need to know this.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​February '21 Contributors!
    1. Dan W.
    2. Franck
    3. Jesse
    4. CJ B.
    ​5. Brian G.
    6. Mike
    7. Matt
    8. Casey M.
    9. Jay R.
    10. Glenn B.

    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Picture
Home - About - Blog - Contact - Exam Prep - Store

​Copyright © 2021 MeyerFire, LLC

The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About