MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Who Provides Two-Way Communication Systems?

10/6/2020

9 Comments

 
Have a four-story project that is under 2015 IBC and NFPA 101. NFPA 101, for fully-sprinklered buildings with accessible floor levels (floors 2-4 included) - designates the entire floor level as accessible and an area of refuge. Reference NFPA 101 7.2.12 and NFPA 72 24.10.

Along with that designation includes a requirement for a two-way communication system generally next to the elevator bank for the building. There's not much detail out of NFPA 101, and I'm finding very few people are familiar with these systems.

Who typically specifies and provides details/locations on these systems?

It is not tied into the fire alarm system - yet is related to life safety - so we're getting some feedback that these systems should be shown on fire alarm plans. However, the fire alarm subcontractors have nothing to do with these systems. Low voltage / specialty consultants are stating that the systems are code mandated and aren't looking to coordinate these locations with fire marshals and plan review.

It's not a cost item and no one is pointing fingers - but I am trying to understand going forward where these systems are typically shown on plans and who should be specifying them? 

Thanks in advance.

​​​​​​​​​​​​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
9 Comments
Jeanne Tebera
10/6/2020 10:10:28 am

The area of rescue (or refuge) two-way communications system is typically specified in Division 28 (not 27) by the electrical engineer or the fire protection engineer. The best place to show the system is on the fire alarm plans. The two-way communications system must be monitored by the fire alarm system, so these monitoring points should be indicated as supervisory signals on the fire alarm matrix.

Reply
Will
10/6/2020 12:49:45 pm

Jeanne,

Where is the requirement to monitor this system by fire alarm?

Reply
Rusty Scott
10/6/2020 10:22:46 am

This has been a hot topic for our firm as well. Since it is mentioned in NFPA 72 to provide emergency communication systems, our AHJs are now requiring them to be shown on our engineered FA drawings for permit yet we have to provide pricing notes stating that if two-way comm. type systems are not in FA contractor scope please notify G.C. & architect and indicate in pricing package that this is not included. That way the flag is waved that it needs to be priced and sent to the appropriate contractor for bid. It's unclear to use if low voltage/specialty type contractors know to look on fire alarm for these systems. In our region, FA contractors don't touch these systems yet in other parts of the country we've worked in they do.

We have an internal firm debate on who should show these types of system between our telecom drawings or fire alarm. Right now we agree it should be on telecom yet AHJs require them to be on the engineered FA drawings and will not let us reference telecom drawings since telecom aren't being submitted to the AHJs.

(Also believe you are supposed to monitor the power supplies of the emergency comm. systems.)

Our telecom group explains it in a pretty simple way, that it's basically a dedicated P.A/paging system that can go both ways with some added safety features and survivability requirements.

To add to your question, if the main control panel is located in the fire command center, is it fire alarms responsibility?

Reply
DS
10/6/2020 11:07:38 am

NFPA 72 cannot require the installation of any system. It is only a standard for installation, testing, and maintenance. I would visit this with your AHJ.

Reply
Rusty Scott
10/8/2020 10:53:24 am

@DS - Correct poor terminology on my part, the IBC requires it and it's installation standards are in NFPA 72 which is why our AHJs requires it to be shown on our FA drawings.

Marc Vieno
10/6/2020 10:40:22 am

I know that the City of Portland requires location callouts on the life safety floor plans, and typically it's checked that it is mentioned in the code summary as well. After that we (I was a Commercial Plans Examiner there) just assumed that the next place we'd see it is during inspections.

As a building and fire code consultant, I recommend the life safety sheets as a minimum - typically the permit set is also the bid set so it's fine to leave the system design up to the bidder.

Reply
Sean Kyer
10/6/2020 12:32:52 pm

In Colorado it is the fire alarm contractor that typically provides the systems. In Denver it is required for a fire alarm contractor to do so. But, I know of a company that only installs two way systems and I they are telecommunication contractors. As with anything it seems that if you are qualified that is all that matters. Check with Rath Communications or Kings III. They may know of a contractor in your area. As for plans, my company will often submit a separate set of engineered plans just for this special system.

Reply
Felipe Pedraza
10/6/2020 12:38:13 pm

DS, you are correct, NFPA 72 does not require the 2 way communication but it does talks on how and what equipment to use for the installation. This is found in section 24.10 of NFPA 72.

NFPA 101 chp, 7 does talk about the requirements in providing an Area of Refuge and providing 2-way communication for Life Safety reasons. Also, IBC 2015 and 2018 section 1009.6.5 makes the requirements of 2-Way Communication in the Area of Refuge. IBC 2015 and 2018 section 403.5 also mention Stairway communication System. These requirement's were also found on the 2009 and 2012 IBC section 1007.6.3 and the Stair communication section 403.5.3.

The IBC also talks about Emergency Radio Coverage for first responders and it is found in section 915 of IBC 2012, 916 IBC 2015 and 918 of IBC 2018. All these section are only 1 sentence long, which refer you to the IFC chapter 5 section 510 the installation requirement.

These requirements area for areas of refuge in new construction, significant remodeling, or change of building use regardless if the building is sprinklered or not.

Reply
David Secoda
10/12/2020 02:50:47 pm

Hi All - In design, I've seen plans for two-way communication systems on fire alarm and on technology drawing sets.

During construction, it's usually the fire alarm subcontractor that provides the equipment and programming of the two-way comm system.

One factor contributing to the confusion is that the model code (IBC) does not reference NFPA 72 for the installation of two-way communication systems.

Designers, contractors and AHJs are left to interpret the meaning and intent of model code language that (paraphrasing) states "A two-way communication system shall be provided..." More precisely, the model code (IBC) should reference the installation standard, for example "A two-way communication system *installed in accordance with NFPA 72* shall be provided..."

A two-way communication system IS an emergency communication system (ECS) which installation is covered by NFPA 72. In my opinion, the two-way comm system should be supervised by the building fire alarm system.

The interface for supervision should be shown on the fire alarm drawings - similar to the points of supervision shown for emergency responder radio coverage systems (ERRCS).

Supervision should be provided for the two-way comm system power supply and possibly other points depending on the system manufacturer.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​October '20 Contributors!
    1. SK
    2. Franck
    3. Dan W.
    4. Jonathan ​5. Casey M.
    6. Sean
    7. Colin L.
    8. Mike
    9. Jonathan J
    ​10. Daniel G.


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About