MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Why Pressure Loss Between Street and Backflow?

1/8/2021

17 Comments

 
We are inspecting an existing fire sprinkler building for an upgrade to an Extra Large Orifice (ELO) system.

We performed a hydrant flow test and noticed a 14 psi static loss between the hydrant, 185-ft of 8-inch ductile, 2 elbows and 8 feet of elevation rise to the supply side of the RPZ backflow preventer.  We recorded 73 psi at hydrant and 59 psi at the number 1 test cock on the RPZ while static.

I spoke with the water authority and they confirmed no meter or check valve on the 8" fire line; it is straight into the valve room plus 2 elbows. The building is 20 years old and the pump test provided 120% of rated capacity.

Any idea how the static pressure inside the building is 14 psi less?

​​​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
17 Comments
Dan Wilder
1/8/2021 08:27:30 am

Check your gauges for calibration and try to use the same type for both. Using a glycerin filled 100# and an Air/Water 300# will not be equal when comparing them.

Do both gauges move equally with changes in the static pressure (up and down)?

I'm assuming the RPZ is doing it's job and there is an additional loss across the valve? Not that this makes a difference on the static, but just making sure the valve is doing its job.

Reply
Mike
1/8/2021 09:06:09 am

Check the gauges.

Reply
Andrew K
1/8/2021 09:14:46 am

I can only agree with previous responses. In general, we should consider the the pressure gauges as a possible source of psi discrepancy. I would offer that if you have the opportunity to use one certified pressure gauge for both locations, it may eliminate any discrepancies between different gauges.

Reply
Jesse
1/8/2021 09:30:58 am

First of all check the gauges. We've all seen way too many mis-calibrated gauges. If the gauges are good, it's likely the UG pipe is fouled. I ran a basic HW manual calc presuming a flow of 1000-gpm. Your friction loss is in the area 1.38 psi. Your 8-ft rise in elevation accounts for a loss of 3.46 psi for a total loss of 4.84 psi. You've lost 14 psi, so we're at the point where the culprit may be scale buildup on your UG pipe. If this is the case, you'll need to replace the UG.

Reply
Jesse
1/8/2021 09:37:41 am

Sorry - I just re-read the original post. Earlier my brain registered the pressure differences while flowing, not static.

This one's weird. Thinking its the gauges.

Reply
Casey Milhorn
1/8/2021 09:38:51 am

Completely agree with checking the gauges. Also make sure you are doing them at the same exact time. Sounds like you are in an industrial area and water usage can spike up and down dramatically affecting the static pressure available, especially if the city water main is a dead end line and/or undersized. Other than that, physics is physics.

Reply
Franck
1/8/2021 09:56:56 am

For the same elevation, static should be the same everywhere in your system.
If you have a difference, it may come from a pressure gauge reading (as indicated above), a possible change in elevation, or the provision somewhere of a pressure reducing system.
By elimination, you can guess where is the answer...

But first thought is of course to check the calibration of the pressure gauges.

If difference is coming while flowing the system, then it comes to friction losses, as indicated by Jesse. If more difference than expected, then it may come from a smaller pipe size than expected (smaller diameter installed, or smaller inside diameter because of scale build up, MIC, improperly opne valves...

Reply
Glenn Berger
1/8/2021 10:13:24 am

After checking the gauges (easy answer), you might have underground piping that has a problem (internal or external). Do you know if there are soil corrosive issues?

Reply
Shane
1/8/2021 10:29:52 am

my best guess there is a small leak, due to corrosion, in the underground piping or at a fitting connection after the backflow.

Reply
C.T. Carbonari
1/8/2021 10:34:50 am

I always check testing equipment & methodology (i.e. gauges, connections, locations,piping configuration) whenever unexpected hydraulic anomalies occur.

Assuming the hydrant is public and on a dead end line, there is typically a key valve near the property line at point of connection with the city water supply.
I would check to ensure it is fully stroked open.

Reply
C.T. Carbonari
1/8/2021 11:06:58 am

Also, this sounds like a Fire Service Main Flow Test (as opposed to a traditional hydrant test)

Knowing how much flow (gpm) you achieved during your test would help in assessing your pressure drops.

@ Q=1500 gpm for 8" DI ; c=100 (existing) w/205 ft equiv. pipe
your pressure drop should be in the 4.5 psi range.

A 14 psi residual drop is an indicator of a restricted orifice.
(Heavy Corrosion, Valve partial open)

Reply
Louie Lincoln link
1/8/2021 02:42:32 pm

I doubt that all of the gauges are that far off. With the pump only flowing at 120% if the original was 150%, there is a flow restriction.
The flow loss would account the 30% difference. It would be helpful if you could get your hands on the original pump start report.

Reply
Felipe Pedraza
1/8/2021 07:09:22 pm

If the guages have been checked.and are of the same make and kind, proceed to checking all roadway valves near the source and make sure that they are fully open and in working condition. I have found some of them close and even broken in the past. Also check with utilities for any watermain repair near the area, or waterline taps to the main and the cut out line donut went into the main and is either blocking a watermain roadway valve ir is blocking the water at the BF.

Reply
Tony Brown
1/9/2021 08:22:30 am

I have come across this situation three times. Once was due to a throttled down curb valve, the other two was because a neighbor had tapped into my clients incoming service.
My gages are always checked before leaving the shop and I have them checked and calibrated on a regular basis, even brand new ones so if you are confident that your gages are okay then check all valves between the hydrant and the backflow. 14 psi loss on 185 + of 8" ductile is a huge loss so I would check for a mechanical cause, i.e., valves, broken pipe,

Reply
FRED WALKER
1/11/2021 10:08:11 am

1. Check gauges, ensure calibration, easy first check swap gauges.
2. If gauges check and you have 0 flow through the backflow preventer; then you have a leak, an undocumented tap, or some other condition creating flow between the hydrant and the backflow preventer.

If the hydrant is located on a distribution main and there is a Tee-off to the backflow preventer you may need to take static at hydrants on either side of the Tee as well as the backflow preventer to account for flow in the distribution main.

Reply
C.T. Carbonari
1/14/2021 10:58:07 pm

I hope the OP responds with clarification when this issue is resolved.
Knowing the actual field solutions to these more empirical types of questions benefits all of us!

Reply
Jesse
1/15/2021 07:40:17 am

Agree with C.T. Would be beneficial to all of us if the OP circled back with the resolution. Differential diagnosis are great, and this created some great discourse. We're all better at what we do because of it.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​October '20 Contributors!
    1. SK
    2. Franck
    3. Dan W.
    4. Jonathan ​5. Casey M.
    6. Sean
    7. Colin L.
    8. Mike
    9. Jonathan J
    ​10. Daniel G.


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About