MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

When is a Storage Tank Req'd with a Fire Pump?

12/7/2020

10 Comments

 
I'm putting together design-build requirements for a new single-story construction building. The flow test pressure is borderline in my opinion so I'll be calling for a fire pump.

When is a water storage tank required with a pump?

I don't think the system needs one, but I just want to be sure.

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
10 Comments
Dan Wilder
12/7/2020 08:43:42 am

You will need a tank when the water supply cannot meet the required GPM for the pressure and/or duration required per (typically) Appendix B of the Fire Code and/or the sprinkler demand plus any outside hose stream (whichever is greater). There are several other methods available depending on the AHJ adopted methods (ISO, NFPA, etc.)

There was a blog spot on it here:
https://www.meyerfire.com/blog/how-to-determine-fire-flow-ifc-method

The FPRF has a good write up on the process as a whole.
https://www.nfpa.org/-/media/Files/News-and-Research/Fire-statistics-and-reports/Emergency-responders/RFEvaluationofFireFlowMethodologies.ashx?la=en#:~:text=Fire%20flows%20range%20from%201%2C500,at%2020%20psi%20residual%20pressure.&text=For%20one%2D%20and%20two%2Dfamily,1%2C000%20gpm%20for%201%20hour.

Reply
Franck
12/7/2020 09:26:46 am

If your flow test pressure is borderline, this is a good thing to plan for a dedicated fire pump.
All the more since the characteristics fo a city water grid may vary over the time (seasonality, or even during the day), in addition to potential future decrease (or increase, sometimes, which is then a good news).

In additionn you may need to provide backflow preventers (to avoid a pollution of the city grid from your static water sprinkler system) which will add additional friction losses to the initial test performed on the city grid.

The choice for the water tank is depending on your supply.

If you have more than enough flow, and the only issue you have is related to the pressure delivered, you may opt for a booster pump (which will increase the pressure of your city grid water supply).
Otherwise, you need a storage tank.

This has many advantages:
- you determine the amount of water for the required duration
- no bad surprise of available duration over the time (unless you change the occupancy/commodity classification...)
- you have an independent water supply for your sprinklers from the water supplies for the hydrants (manual fireighting). No competition bteween both of them.

Some disadvantages (as always):
- possibe issue with the quality of water (depending on what you use to fill it). Raw water may be problkematic for pendent sprinklers, for example
- possible impairment when you need to maintain the tank
- possible freezing issues with the tank
- Space... the tank may take a large volume...

For industrial facilities, I normally recommend to have a water tank + fire pump (sometimes several, depending on size of the facility... a very large automotive plant or a Nuclear power Plant, for example) and try to keep the manual firefighting from an independent source (city grid or another dedicated tank+pump).

Note that depending on the flow available, you may opt for a break tank instead of a full size tank.
If you refill the break tank (automatic refill) at a sufficient flow with your city water grid, it may be an option to limit the volume of your water tank.
The tank should be sized for a minimum operation of the fire pump at 150% of its rated capacity during 15 minutes without refill,
Note that the tank volume is not based on the highest demand point from the system, but on the rated flow of the fire pump.
The capacity of the public supply must be at least equal to 150% of the pump rated capacity + the deamn,d for the hydrants (public or private).

I normally don't recommend it (unless in case of lack of space) as this is less reliable than having a dedicated full size water tank (you are dependent from the refill line).

Reply
Casey Milhorn
12/7/2020 10:24:36 am

These gentlemen covered it pretty well. As an example of how this would work in your case, lets say your flow test was 50 psi static, 40 psi residual, at 400 gpm. Now lets say your building was classified as ordinary hazard 2 and 22' tall (so reduced area is out). Now lets say you estimated a demand of 50 psi @ 350 gpm. It's pretty evident from this that you will definitely need a booster pump (or let the sprinkler sub try and VE it out if the owner is up for it). So you could specify a 40 or 50 psi pump and that would take care of the pressure issue. The gpm in this pretend scenario is enough in the test without being close to that 20 psi minimum we all worry about. Also as Dan and Franck talked about, be very very careful about IFC fire flow demand, which will dwarf the sprinkler system demand typically. If private hydrants are coming off a new tap for this building, you can be stepping into a bear trap here. So other things to watch out for is if your flow test didn't actually perform to the gpm required, then I would recommend another flow test with two outlets or more open so that your demand point is within a real curve and not extended out into a projected area of the curve. Also if your flow test is flirting with 20 psi residual at or near your demand, then I would be nervous about using only a fire pump.

Reply
Casey Milhorn
12/7/2020 10:44:53 am

Also, I failed to mention the 250 gpm hose demand in my pretend scenario and where it is added into the calculation based on public or private hydrants locations could definitely have an affect on the pump and tank sizing and requirements.

Reply
Pete D.
12/7/2020 12:07:39 pm

The IFC appendix allows for a 75% reduction for fully sprinklered building with AHJ approval. Also, the tabulated duration typically only comes into play with a tank or pond. A lot of folks don't realize, if you have an automatic fill valve you can subtract the fill rate and reduce the tank size. [Required Fire Flow (0.25) - fill rate] * duration = tank volume.

Reply
Franck
12/8/2020 03:03:34 am

Yes

This is the principle of the break tank.

NFPA 20 and 22 also address the conditions for break tanks installations.

NFPA 20 allows the use of break tanks for the following reasons:
• As a backflow prevention device between the water supply (water supply from the city water grid, process water supply system…) and the fire pump suction pipe
• To eliminate fluctuations in the water supply pressure and provide a steady suction pressure to the fire pump (water supply from the city water grid, process water supply system…)
• To provide a quantity of stored water on site where the normal water supply will not provide the required quantity of water required by the fire protection system (existing water tank, too small for the required needs).


Note anyway that the refill rate, per NFPA is depending on the initial size of the tank (if capacity is less or more than 30 minutes supply of the most demanding area, it makes a difference).
For example, dual automatic refill lines are required if the capacity is less than 30 minutes.

Reply
Dale Morris
12/8/2020 10:37:45 am

I worked on a project where we had to provide a tank due to it's Seismic classification. The building was a mixed use residential high rise, and was required to have two sources of water. The way the piping in the street was designed, there was no way to use a service that was separate from the only service in the street. So, a tank was installed in the parking garage to serve as the second source. The building has a roof top pool, and that was considered to be used in lieu of a tank. I don't remember what swayed them from not using the pool and installing the tank instead.

Reply
Frank V
1/6/2021 12:15:34 pm

That's the situation we're facing on a very similar project here in Atlanta where we just learned of a heightened Seismic category. A couple of questions. 1) I assume since the tank is to serve as a second water source, that you cannot subtract the fill rate in order reduce the tank size, correct? 2) What flow rate and duration is ultimately required for the tank size - required flow or 150% of pump? Sixty minutes or what?

Reply
water storage tanks for agriculture link
9/13/2023 09:40:29 pm

Water security has become a deep concern across Australia, as a result of inadequate dams, expanding population, and the effects of global warming, culminating in frequent catastrophic droughts.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Dec '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT