MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

What Distance Under Sprinkler Is No Longer An Obstruction?

1/25/2021

7 Comments

 
When would you consider an obstruction no longer an obstruction, vertically below an ESFR sprinkler?

If the top of storage has to be 36" wouldn't 36" be the cut off? Or do the obstruction rules go the floor?

I have a warehouse that has 2 x 4 light fixtures which are 6'-0" below the roof deck, and am wondering whether these are considered obstructions. Thanks in advance.

​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments
Sarah Swan link
1/25/2021 09:09:39 am

We have actually asked the NFPA 13 committee what their intent was for this. Unfortunately, the response was that anything can be considered an obstruction to and ESFR sprinkler, no matter the distance from it. We questioned if this applied to things like rails near the floor to protect walkways from forklifts, and were told that it does.

Reply
Bruce Seiler
1/25/2021 09:15:36 am

Obstruction rules still apply. ESFR sprinkler heads have very specific requirements. NFPA 13 2019 Edition Chapter 14. Section 14.2.1.2 would cover the light fixtures, specifically Item (2). "Additional sprinklers shall not be required where the obstruction is 2 ft. or less in width and the sprinkler is located horizontally 1ft. or greater from the nearest edge of the obstruction. Spacing of lights should follow this standard. The standard does not provide a specific distance below the sprinkler head that obstructions become a problem. It distinguishes between Obstructions at or Near Ceiling for non-continuous obstructions and continuous obstructions.

Reply
Mike
1/25/2021 09:24:19 am

Looking at the Tyco ESFR data sheet, under Obstruction Criteria they say to Refer to FM 2-0 Section 2.2.

https://www.fmglobal.com/-/media/Documentum/Data-Sheet-Individual/02-Sprinklers/FMDS0200.pdf?isGated=true&itemId={993E5163-0BFB-47CB-BD99-442324FE7F93}

This has been pretty strict. In the past I have had to add ESFR's underneath 4" and 6" roof drain lines.

There's always a trade off using ESFR and CMSA heads vs. standard spray heads. Might use less heads at the roof but you have to add heads for obstructions.

Reply
Franck
1/25/2021 11:02:29 am

For that reason, in my previous company, we were saying that you have to build a warehouse around an ESFR protection (to avoid all these issues).

Providing an ESFR protection within an existing building is most of the time a nightmare (air velocities, presence of heating devices near the ceiling, obstructions from the building structures, from the components (ligths, pipes...), from the draft curtains, presence of skylights...)

Reply
CJ Bonczyk
1/25/2021 10:50:04 am

Unfortunately all obstruction rules currently stated in code apply whether it be FM Global or NFPA requirements. I prefer to follow the installation guidelines as outlined in FM Global. They provide a clear pictorial view of what is required. In your situation it does not matter whether the obstruction is greater than 36" below the bottom of the deflector.

NFPA does not clearly call out a maximum cut off distance other than the following:

NFPA 13 2019 14.2.11.2 discusses isolated obstructions below elevation of ESFR sprinklers. Sprinklers are required below unless the obstruction is 2' or less in width and a minimum of 1' horizontally or greater from the nearest edge of the obstruction. It also states that additional sprinklers shall not be required where the obstruction is 2" or less in width and located a minimum of 2' below the elevation of the sprinkler deflector or is positions a minimum of 1' horizontally from the sprinkler. Note that it does state that sprinklers special obstruction allowances shall be installed according to their listing.

Check the cut sheet of the ESFR sprinkler and see what minimum code requirements are to be followed for both FM & NFPA. Ensure the elevation tolerances for the sprinkler can be met.

FM Global provides the following:
Also as stated previously FM Global provides guidelines for storage sprinklers (FM Data Sheets 2-0 & 8-9). 2-0 specifically address umbrella discharge patterns for ceiling level storage sprinklers in 2.2.3.5 & 2.2.3.5.1. The remaining information, tables and figures are of great information as well and should be strictly followed.

Word of advice is to provide a preliminary layout of the ESFR sprinklers with the steel background should be provided to the client/GC for in-depth coordination of lights/HVAC/plumbing/HVLS fans etc. The spacing of the sprinklers is critical obviously and many times you can have the MEP be adjusted to accommodate the ESFR spacing because the ESFR's are limited to the steel locations and code limitations.

Reply
Franck
1/25/2021 10:55:20 am

Same rule applies for all sprinklers (even though more restrictive in term of width with ESFR):

Whatever the distance below the deflector, any item can create an obstruction to the sprinkler water discharge pattern and prevent water to reach the fire.

This apply for lights, groups of cables/pipes, but also applies for wooden shelves within rack arrangements (difference between open and solid shelves).

Only acceptable exceptions are listed by NFPA, such as removable tables...

You have to check the obstruction rules within NFPA and provide sprinkler underneath if you don't fall under an exception.

Reply
Brian Hoole
1/25/2021 12:24:36 pm

2019 NFPA 13:8.12.6 Clearance to storage (Early Suppression Fast Response Sprinklers). The clearance between the deflector and the top of storage shall be 36 in. or greater.

Any obstruction large enough to cause an obstruction to the ESFR below the top of storage would hinder the ability to pick commodities from the shelving with fork lifts. Utilizing catwalks would likely require in-rack protection under the additional walkways.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​January '21 Contributors!
    1. Franck
    2. CJ B.
    3. Dan W.
    4. Jesse
    ​5. Gleen B.
    6. Casey M.
    7. Mike
    8. Pete
    9. HJ
    10. Wayne


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About