MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

What Distance Under Sprinkler Is No Longer An Obstruction?

1/25/2021

7 Comments

 
When would you consider an obstruction no longer an obstruction, vertically below an ESFR sprinkler?

If the top of storage has to be 36" wouldn't 36" be the cut off? Or do the obstruction rules go the floor?

I have a warehouse that has 2 x 4 light fixtures which are 6'-0" below the roof deck, and am wondering whether these are considered obstructions. Thanks in advance.

​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments
Sarah Swan link
1/25/2021 09:09:39 am

We have actually asked the NFPA 13 committee what their intent was for this. Unfortunately, the response was that anything can be considered an obstruction to and ESFR sprinkler, no matter the distance from it. We questioned if this applied to things like rails near the floor to protect walkways from forklifts, and were told that it does.

Reply
Bruce Seiler
1/25/2021 09:15:36 am

Obstruction rules still apply. ESFR sprinkler heads have very specific requirements. NFPA 13 2019 Edition Chapter 14. Section 14.2.1.2 would cover the light fixtures, specifically Item (2). "Additional sprinklers shall not be required where the obstruction is 2 ft. or less in width and the sprinkler is located horizontally 1ft. or greater from the nearest edge of the obstruction. Spacing of lights should follow this standard. The standard does not provide a specific distance below the sprinkler head that obstructions become a problem. It distinguishes between Obstructions at or Near Ceiling for non-continuous obstructions and continuous obstructions.

Reply
Mike
1/25/2021 09:24:19 am

Looking at the Tyco ESFR data sheet, under Obstruction Criteria they say to Refer to FM 2-0 Section 2.2.

https://www.fmglobal.com/-/media/Documentum/Data-Sheet-Individual/02-Sprinklers/FMDS0200.pdf?isGated=true&itemId={993E5163-0BFB-47CB-BD99-442324FE7F93}

This has been pretty strict. In the past I have had to add ESFR's underneath 4" and 6" roof drain lines.

There's always a trade off using ESFR and CMSA heads vs. standard spray heads. Might use less heads at the roof but you have to add heads for obstructions.

Reply
Franck
1/25/2021 11:02:29 am

For that reason, in my previous company, we were saying that you have to build a warehouse around an ESFR protection (to avoid all these issues).

Providing an ESFR protection within an existing building is most of the time a nightmare (air velocities, presence of heating devices near the ceiling, obstructions from the building structures, from the components (ligths, pipes...), from the draft curtains, presence of skylights...)

Reply
CJ Bonczyk
1/25/2021 10:50:04 am

Unfortunately all obstruction rules currently stated in code apply whether it be FM Global or NFPA requirements. I prefer to follow the installation guidelines as outlined in FM Global. They provide a clear pictorial view of what is required. In your situation it does not matter whether the obstruction is greater than 36" below the bottom of the deflector.

NFPA does not clearly call out a maximum cut off distance other than the following:

NFPA 13 2019 14.2.11.2 discusses isolated obstructions below elevation of ESFR sprinklers. Sprinklers are required below unless the obstruction is 2' or less in width and a minimum of 1' horizontally or greater from the nearest edge of the obstruction. It also states that additional sprinklers shall not be required where the obstruction is 2" or less in width and located a minimum of 2' below the elevation of the sprinkler deflector or is positions a minimum of 1' horizontally from the sprinkler. Note that it does state that sprinklers special obstruction allowances shall be installed according to their listing.

Check the cut sheet of the ESFR sprinkler and see what minimum code requirements are to be followed for both FM & NFPA. Ensure the elevation tolerances for the sprinkler can be met.

FM Global provides the following:
Also as stated previously FM Global provides guidelines for storage sprinklers (FM Data Sheets 2-0 & 8-9). 2-0 specifically address umbrella discharge patterns for ceiling level storage sprinklers in 2.2.3.5 & 2.2.3.5.1. The remaining information, tables and figures are of great information as well and should be strictly followed.

Word of advice is to provide a preliminary layout of the ESFR sprinklers with the steel background should be provided to the client/GC for in-depth coordination of lights/HVAC/plumbing/HVLS fans etc. The spacing of the sprinklers is critical obviously and many times you can have the MEP be adjusted to accommodate the ESFR spacing because the ESFR's are limited to the steel locations and code limitations.

Reply
Franck
1/25/2021 10:55:20 am

Same rule applies for all sprinklers (even though more restrictive in term of width with ESFR):

Whatever the distance below the deflector, any item can create an obstruction to the sprinkler water discharge pattern and prevent water to reach the fire.

This apply for lights, groups of cables/pipes, but also applies for wooden shelves within rack arrangements (difference between open and solid shelves).

Only acceptable exceptions are listed by NFPA, such as removable tables...

You have to check the obstruction rules within NFPA and provide sprinkler underneath if you don't fall under an exception.

Reply
Brian Hoole
1/25/2021 12:24:36 pm

2019 NFPA 13:8.12.6 Clearance to storage (Early Suppression Fast Response Sprinklers). The clearance between the deflector and the top of storage shall be 36 in. or greater.

Any obstruction large enough to cause an obstruction to the ESFR below the top of storage would hinder the ability to pick commodities from the shelving with fork lifts. Utilizing catwalks would likely require in-rack protection under the additional walkways.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top April '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT