While doing a sprinkler inspection it was found that the main check valve for the system failed. The system was installed before backflows were mandated on sprinkler systems.
I know that a backflow preventer needs to be installed in its place, but have been unable to find any code that says it does. Anyone able to help? Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
11 Comments
Anthony
10/6/2022 07:38:21 am
This will be part of the plumbing or heath code not from NFPA 13. Check your state or local building code for backflow prevention requirements.
Reply
Corey Eppinghaus
10/6/2022 08:05:00 am
As Anthony noted it will be in the plumbing code or health code you may also want to check to see if the municipality has a backflow prevention program, they might be able to force them to install one/repair.
Reply
Robb
10/6/2022 08:08:43 am
agreee 100% with Anthony. AWWA and UPC requires these, not the fire code. Is your sprinkler connected to Potable water system (public drinking water)- than yes a BFD is required. if connected to a private fire main -and not cross conencted to the city or campus water mains - than not required.
Reply
10/6/2022 08:14:37 am
Here in Metro NY backflow devices are initiated by the local Water District for their review and then forwarded if required, to the County Health Department.
Reply
Jesse
10/6/2022 08:16:53 am
This is part of the plumbing code. You won't find it in 13.
Reply
Dan Wilder
10/6/2022 08:41:56 am
The system was installed with a check valve and assumed approved with that installation, its failure during a 25 inspection means repair or replace like for like not add a backflow and potentially change the hydraulics of the system.
Reply
Alex
10/6/2022 08:43:40 am
Hi,
Reply
HJ
10/6/2022 09:21:37 am
NFPA 1 (2018) contains the following:
Reply
Brian
10/6/2022 11:33:36 am
The type of system wasn't stated. If this is a dry system then only the single check in addition to the dry riser should be needed. Also is there a fire service main with a pit where the backflow device could already be located?
Reply
Mark Harris
10/6/2022 12:29:21 pm
Agree that plumbing codes and water suppliers are where you will find the requirements. But think they are trying to conform to the EPA Safe Water Drinking Act of 1974 but as I recall fire sprinkler systems came into play with the 1986 amendments.
Reply
James Art
10/12/2022 01:12:44 pm
Backflows Devices are forbidden in CA:
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop November '24 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
January 2025
PE PREP SERIES |