MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Variation in Fire Sprinkler Safety Factors

8/29/2017

6 Comments

 
NFPA 13 does not clearly identify a required safety factor for hydraulically designed fire sprinkler systems. What safety factors are commonly required by jurisdictions in your area?

Note: This is a Daily Discussion question submitted anonymously to us. Submit a Question or Discuss This Here.
6 Comments
Kristen E Nich
8/29/2017 05:47:43 am

I am not sure what is the minimum required by most AHJs, but my company standard is 10 psi. On an existing system sometimes we will allow less if most of the existing piping is to remain.

I have also heard of people using 10 percent as the factor of safety, but at least on many projects I've done, that would be less than 10 psi so we aim for 10 psi and require it in our specs.

Reply
David
8/29/2017 08:16:39 am

Our state has mandated a 10 psi safety factor.

With as-built plans being required we had always tried to get a 15-20 psi safety factor depending on the site and job conditions. since additional fittings and piping can be added in the field and affect your calculations.

Reply
Patrick Turner, P.E.
8/29/2017 08:19:29 am

NFPA 13 does not have a specific Safety Factor requirement because NFPA 13 has numerous safety factors built into the code. For instance, a standard spray upright or pendent is required to have 7 psi minimum, and is required to be no more than 7'-6" off of a wall horizontally (except for small room rule which allows up to 9'-0" off one wall in one direction only with other stipulations as well). At Oklahoma State University, they have a Sprinkler Lab and they tested a standard spray upright at 7 psi (put a gauge on the bull head side of a tee just before the upright and throttled the control valve supplying the sprinkler until the gauge read 7 psi). They then had a circular "ruler" on the floor from the center of the sprinkler and at 7 psi, the sprinkler sprayed up to 12 feet.

My point is that NFPA 13 has numerous safety factors built into the code and therefore does not have a specific pressure safety factor other than that the demand point is below the supply curve.

Many AHJ's do not have a specific safety factor requirement either (although I do know of one here in the OKC Metro area that requires a 10psi safety factor). However, I do see, quite regularly, that the Architectural/Engineering Firm reviewing the subcontractor's submittals specify their own safety margin requirements whether the AHJ has them or not. They are usually either 10 percent or 10 psi. I have seen as much as 20 percent required by an A/E.

Reply
Barry
12/4/2018 09:21:20 pm

Thanks for your post. I am still amazed at the result of the study. I have a light hazard job, wood truss, that I will be lucky if I can find straight shot through the truss. It' looks like they put one half of the building offset or reversed. Need to survey more thoriughly. May need to add some 90s or 45 easier on the calcs. Cant get a hold of designer, till Friday.
My plans state saftey margin +18.843 or 31.3%

Reply
Pete
8/29/2017 09:19:13 am

While safety factor is not required by NFPA 13, having a 5-10 psi is a good engineering practice to account for fluctuation and deterioration of the available water supply.

In addition to the safety factor, it is a good idea to contact the local water utility company to determine low hydraulic gradient of the system, and account for it in hydraulic calculations.

While it may be a conservative approach (and may trigger installation of a fire pump), it ensures that your sprinkler system will operate as designed even in worse case condition.

Reply
Marc
8/29/2017 06:04:54 pm

The 10 PSI seems to be common. I do a lot of freelance design all over the country and I've seen quite a range of requirements. Portland, OR degrades your flow test by 80%. Colorado requires a 10% minimum up to 100 PSI then a flat 10 PSI. Montgomery County, MD requires 20 PSI. As a rule, the 10% seems to be the most prevalent. I agree that NFPA is extremely conservative in it's requirements. I have observed several fire tests and the sprinklers usually out-perform expectations. There are a lot of factors that need to be considered when performing calculations. If an area has a dense population, and is built out, I'll use more of the available flow than an area that is relatively new and still has potential impact on the water supply. Potential for field revisions, upgrades such as tenant build-outs, all weigh in for consideration in the design of a fire protection system.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​October '20 Contributors!
    1. SK
    2. Franck
    3. Dan W.
    4. Jonathan ​5. Casey M.
    6. Sean
    7. Colin L.
    8. Mike
    9. Jonathan J
    ​10. Daniel G.


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • CODE CALLS
  • LOGIN
  • STORE
  • About