MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Use One 20x20 Sprinkler in NFPA 13RĀ Calculation?

2/14/2023

10 Comments

 
The installation contractor and I have had an argument about how sprinklers should be spaced and calculated in a 13R system.

I have argued that per NFPA 13R Section 7.1.1.3.1, we should calculate 3 sprinklers in the greatest hydraulic demand area. This area is furthest from the riser and the calculation permits 16x16-ft spacing for the area that has the most sprinklers.

Section 7.1.1.3.1:
For each of the following situations, the number of sprinklers in the design area shall be all of the sprinklers within a compartment, up to a maximum of four sprinklers, that require the greatest hydraulic demand:

The contractor wants to remove a sprinkler in a single room and move a sprinkler 10 feet off of the exterior wall, but in NFPA 13R makes no mention of a single sprinkler proof calculation that could justify such a move.

There is no mention of a single sprinkler calculation in NFPA 13R permitting a spacing of 20x20, and so all sprinklers on the project can be only 16x16 if the greatest hydraulic demand is permitting it.

In NFPA 13D, it makes no mention of a single sprinkler calculation either, but does refer to single sprinkler operations in A.10.1. I did not feel comfortable designing a sprinkler system that was not up to code standards and need an outside opinion on this matter. Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
10 Comments
Peter Howard
2/14/2023 06:35:55 am

Why can't a residential head that is listed for 20 x 20 spacing (at the correct pressures) be calculated for 20 x 20 spacing?

Ultimately, this does mean that if you have any compartments with more than one sprinkler in it on the same floor, that likely is now your more demanding compartment as it will require more sprinklers to activate.

But 13R's calculation requirements don't dictate sprinkler spacing, the listing of the residential head does.

Reply
Anthony
2/14/2023 07:20:06 am

Yes you definitely can calculate only one sprinkler if there is only one sprinkler in the compartment.

You should also calculate several areas if you have several different design bases.13D and 13R use compartment based hydraulic analyses not overall area.

So for your example you would prove that the 20x 20 room works and the 16x16 room works. heck, you can calculate every room for the most efficient design (don't though).

Final thought, do you have a corridor calc? That might be your most demanding calculation as that would probably require 4 heads.

Reply
danefre
2/14/2023 07:44:21 am

Contractor is correct. Yes, you can have a 1 sprinkler calculation in 13R if that's the compartment that produces the greatest demand. Also, very common to reduce number of heads and increase spacing for hydraulic purposes. Each compartment is calculated separately and you can either prove all of them or the ones that logically make the most sense.

Example your kitchen has 2 heads at 14 x 14 but the 3rd floor bedroom with 1 head at 20 x 20 is more demanding. Doesn't mean that the kitchen has to be calculated at 20 x 20. And you should show both calculations because it's not evident which one is more demanding.

I have had reviewers take your side thought - not sure where this approach is coming from... there's nothing in the standard that implies that.





Reply
Alex
2/14/2023 08:05:40 am

Yes, you can only calculate a single sprinkler head if only one head is protecting the entire compartment. Like others have mentioned, if you have a compartment on the same floor that is protected by (2) sprinklers, I would run both calcs (1 with 2, the other with the single head) to ensure both designs work.

Reply
Jesse
2/14/2023 08:15:24 am

Oh how I wish GCs would stick to GC things and let fire people do fire things.

He's almost right. You can do a single sprinkler calc and you can space it 20x20.

But, and this is big but - this may move the hydraulically remote area. A lot of times those unfamiliar with what we do think "remote" area equals physical distance from the base-of-riser. It does not. Well, not necessarily. He wants to change to aa 1 sprinkler calc presumably because it calculates better. But in doing so, you may shift the hydraulically remote area to another area that has multiple sprinklers in a compartment that prove to be more hydraulically demanding.

Reply
Dan
2/14/2023 08:33:16 am

We provide this kind of proof calculation on a normal basis in our residential designs. It allows us to provide layouts for the couple different situations we find during install.

Rooms with 1 sprinkler are designed to 20x20 (or 18x18) so any obstruction (ceiling fans) can be kept to a minimum by creating the largest available space for a single sprinkler to be placed. Additional calculations are provided for the largest room with the most sprinklers (typically it's the 2 or 4 sprinkler calc) at a lesser spacing just due to the obstructions in the middle pushing a 2 sprinkler wide layout. I've not had an issue with plan review when providing both calculation options.

Reply
Casey Milhorn
2/14/2023 09:03:34 am

Everyone covered it really well, the only thing I would add is that MAKE SURE you are meeting the definition of a compartment per NFPA 13R. Then yes, a 1 head calc could prove 1 head at 20x20, with the rest being at 16x16.

Reply
Joshua Bush
2/14/2023 10:49:41 am

I had a similar issue just last week. I had a contractor place a ceiling fan in the main room of an apartment. Because of this change I had to adjust the head to be just over 9'-0" from the farthest wall. For calculation purposes that sprinkler would demand a higher pressure to work properly. I still had 2 other heads in that same room that were spaced at 16'x16'. So, I kept the pressures required for those heads at the 7.0 PSI. Now I have 1 head with a pressure requirement of 16.7 PSI and 2 heads at 7.0 PSI. My plans were rejected from the reviewer with the reasoning that if I increase the pressure of one head in a remote area calculation, all heads have to be calculated at that higher pressure, even if they are spaced in a way that does not require higher pressures to provide coverage. In the end I was told I had to increase the pressure requirements for all 3 heads to16.7 PSI for the calculation to be correct. I was told that I was not able to pick and choose pressures in a remote area calculation. So from my understanding, if I have a multi head room, I must calculate all sprinklers with the pressure requirements of that single head that requires increased pressure. Does this sound correct? I feel like I am either missing something or the plan reviewer is. I'm happy either way. I'd just like to know which is correct so that I do things the proper way.

Reply
Cliff Schulze
2/14/2023 12:50:59 pm

The reviewer is partially right. The 7 psi is a minimum but if another head in the same room has a higher pressure, it will drive up the pressure to the other heads. If one head in the room needs 16.7 psi, the other heads in the room are going to see the higher pressure as well. The only caveat is the pressure can be reduced by manipulating the pipe sizes; i.e. larger pipe size to the head requiring 16.7 psi, smaller pipe size to the heads requiring 7 psi.

Reply
danefre
2/14/2023 03:02:03 pm

What Cliff said is true. The 14x14 will flow more than the minimum due to the 20 x 20 causing it to overflow.

BUT, I don't agree with the reviewer... you're not required to set a higher minimum pressure for the 14x14 to match the 20 x 20. NFPA 13R (2013) Figure A 7.1.1.1 doesn't agree either. The Handbook notes in that section are very informative as well. Check out the Reliable Residential Design Guide too.

Compartment calculations are different than density/area and a lot of "rules of thumb" that reviewers use stem from the density/area method. Yes - the pressure will creep up in a density/area method because by definition you have to calculate branchlines off the same crossmain. You don't have to do that for 13R calcs.

You could have a completely separate 1" riser to the 14 x 14 and it will definitely have a lower pressure than the 20 x 20. Residential jobs very commonly have 1" risers to sidewalls from the floor below.



Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​Feb 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 30B
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT