MeyerFire
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • ALL-ACCESS
  • LOGIN
  • STORE
  • About
Picture
ALL THINGS FIRE PROTECTION | SUBSCRIBE NOW

Sprinklers Required Underneath Large Tanks?

8/5/2020

8 Comments

 
I have a water treatment plant with 3 tanks, 9 feet in diameter. The fire protection contractor feels we need to install a sprinkler under each tank, following the greater than 4 wide rule for obstructed construction. The tanks are located on a concrete floor. The tanks are supported on legs, and the clearance from the bottom of the tank to the floor is about 2 feet.

​Remembering that code tells us where to install sprinklers; my argument is this is not an occupiable space and sprinklers are not needed. The tanks are part of a water filter system, and not a hazardous type chemical storage.

Are sprinklers required underneath these tanks?

Any thoughts or input is most graciously appreciated.

​​​​​​​​Submitted anonymously and posted for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments
FIREPE25
8/5/2020 10:10:34 am

Sprinklers are required. Any obstruction greater than 18" below the deflector that is greater than 4' wide needs sprinklers. I believe the 2016 edition of NFPA 13 added some context about not needing them if the obstruction was close enough to the ground, but I am not sure on the exact language.

Reply
James
8/5/2020 10:11:40 am

Additional protection under the tank should not be required provided the bottom of the tank is 24" or less from the floor.

8.5.5.3.1.4 Sprinklers shall not be required under noncombustible
obstructions over 4 ft (1.2 m) wide where the bottom of the obstruction is 24 in. (600 mm) or less above the floor or
deck.

Reply
Paul
8/5/2020 11:16:13 am

Keep in mind, the 24 inch clearance was only added in the 2016 Edition of NFPA 13, so may not be adopted everywhere. This has not stopped me from submitting a variance/equivalent design to the AHJ's for approval, which most circumstance a valid argument/discussion allowed it to be approved.

Also, what are the sprinklers protecting, contents of the tank? The standard upright/pendent may not be applicable, just make sure.

Reply
GLENN BERGER
8/5/2020 11:58:23 am

Sprinklers are required. It will be easy for combustibles or other materials to eventually find its way to this "obstructed" space.

Reply
Mark C.
8/5/2020 01:34:03 pm

Is there a possibility to enclose the area below the tanks? If a noncombustible or limited-combustible concealed space is created, Section 8.15.1 allows for certain concealed spaces to not require sprinkler protection. If access for any type of piping or maintenance is required below the tanks, 8.15.1.2.2 specifically may still apply:

8.15.1.2.2 Concealed spaces of noncombustible and limited-combustible construction with limited access and not permitting
occupancy or storage of combustibles shall not require sprinkler protection.

Reply
Jonathan Joseph
8/5/2020 01:49:43 pm

I would put some kind of wired mesh screen and wrap around the legs so debris will not collect under the tanks if that is an issue.

Paul and James have mention the codes that meets the requirements of not having sprinkler protection as long as it is not over 24 inches in height and the contents inside the tanks are not hazardous storage.


Reply
Franck
8/6/2020 10:44:55 am

I'm afraid that every body is right (or wrong) and all refernecs are correct (even though they might be contradictory).
This will all depend on your AHJ or Insurance company and their interpretation of the situation.

I would personally not require a sprinkler underneath the tanks (but again, personal opinion) as long as we ensure that:
- the tank is non combustible
- the content of the tank is non combustible/flammable
- there is no other tank with flammable/combustible liquid in the same area
- there will be no combustible storage underneath (with 2 feet, there is little chance anyway to have combustible storage).

This being said, if combustible/flammable liquids are present in the area, it is a good practice to provide a sprinkler protection underneath. The same with combustible storage of goods.
With fl. liquids, sprinklers are usually installed upside down (i.e. pendent sprinkler in the upright position) to cool down the underneath of the tank, as it was required by a standard named Discuss (used for the process of distilleries of alcohol) which is quite a good document if you can read it.
The purpose of that sprinkler is that there is no pool fire underneath the tank that could expose the flammable/combustible liquid inside.

Be careful with the 4 in. rule and sense of judgement is of high importance.
There is no requirement, for example, to provide a sprinkler protection underneath tables, even though they are more than 2 ft, because it is highly improbable that storage will be present underneath.
The 4 ft dimension is justified, according to NFPA handbook, through past practice and experience, not through fire testing.
But some AHJ apply the zero-tolerance rule... And no argument can convince them.

Reply
Dale Morris
8/10/2020 10:57:31 am

I want to thank you all for your input. At the time I posted the question, I was not informed of the actual space under the tank. The clearance is 9 inches from the bottom of the tank to the floor. I love the idea of placing some mesh around the bottom to keep trash from accumulating under the tank.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​February '21 Contributors!
    1. Dan W.
    2. Franck
    3. Jesse
    4. CJ B.
    ​5. Brian G.
    6. Mike
    7. Matt
    8. Casey M.
    9. Jay R.
    10. Glenn B.

    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Picture
    Why Sponsor?

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    IMC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 90A
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Picture
Home - About - Blog - Contact - Exam Prep - Store

​Copyright © 2021 MeyerFire, LLC

The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • ALL-ACCESS
  • LOGIN
  • STORE
  • About