MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
A FORUM FOR FIRE PROTECTION QUESTIONS & PE EXAM PROBLEMS | SUBSCRIBE NOW

Sprinklers Needed Below Multiple Small Clouds?

11/5/2020

13 Comments

 
I have a project where there are multiple cloud ceilings with minimal gaps in-between. The clouds are 3'-6" wide, and the gaps between them are approximately 3-inches. Below is an image of the reflected ceiling plan.
Picture
Are sprinklers required below these cloud ceilings? Thanks in advance.

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
13 Comments
Dan Wilder
11/5/2020 07:35:03 am

Referencing 9.2.7 of the 13'-19 ed.

If this honeycomb pattern had extended to the perimeter wall, this may have qualified but due to several gaps against the walls, within the pattern, and the separation between patterns, protection would be required above and below.

This does not comply with the below section:
9.2.7.1(1)-Combined total area of opening is less than or equal to 20% of the area of the ceiling
Table 9.2.7.1 for the maximum area of open width due to entire honeycomb units being left out and the gaps against the walls.

Your layout also needs to comply with 9.2.7.2.5 for protection below the honeycombs.

Reply
Rosstan Snow
11/5/2020 10:40:32 am

Does this percentage differ between the 13-13' and 13-19' edition. Has the section been revised? This jurisdiction is under 13-13'

Reply
Franck
11/5/2020 11:56:23 am

For your information, requirements for cloud ceilings have been added to the 2016 edition of NFPA 13 following a Fire Protection Research Foundation (FPRF) project studying the behavior of heat and smoke.
Prior to this, sprinklers were generally required both above and below cloud ceilings.
The requirements of 9.2.7 in the 2018 Edition is to omit sprinklers above the cloud ceiling. In no way you can omit sprinkler below : in all cases, sprinklers need to be provided below the cloud ceilings as they create an obstruction.

In your case, I'm afraid you need sprinkler both above and below the cloud ceiling, as indicated by Dan (you don't fulfill the requirements of 9.2.7.1(1)).
In case of fire in your building, because of large openings in your "cloud ceiling system" (around it), the heat will first collect above the cloud ceiling and it would take time before you can activate the sprinklers located below the cloud ceiling.

For the sprinklers located below the cloud ceiling, you just need to provide them to cover the area below them with the min/max spacing specification as if it was a ceiling protection.
And avoid sprinkler located where there is no tile (you still need to collect the heat, i.e., you need a "cloud ceiling" above your intermediate sprinkler level of protection).

For the sprinklers located above the cloud ceiling, it is normally preferred to center them as much as possible above the obstruction tiles.

If you have access to NFPA 13 handbook, you will find a lot of interesting information on that topic.

Reply
Franck
11/5/2020 12:33:07 pm

In addition to my above comment, note that if sprinklers could be omitted above the could ceiling, then the position of sprinklers below the cloud ceiling should be based on table 9.2.7.1, which give a maximum coverage area per sprinkler, depending on the width dimension of the clouds and the opening width compared to ceiling height.

On the Clock
11/5/2020 02:03:01 pm

Thanks, Franck. Am I understanding you correctly that once it is determined that sprinklers are required BELOW the cloud array, then normal sprinkler spacing below the ceiling would apply? One does not need to make sure the gap between clouds will not "stop" the heat from jumping one cloud to the next? Would it be prudent to follow the same maximum gap-width formula for omitting sprinklers above the ceiling (A9.2.7.1) when placing sprinklers in say, every third or fourth cloud, skipping the clouds in-between?

When the architect will not allow penetration of the cloud, do you think a sprinkler with intermediate shield off to the side per 9.5.5.3.1.2 / Fig. A.9.5.5.3.1.2 is an option?
Thanks in advance.

Franck
11/5/2020 02:40:18 pm

Just matter of interpretation and whether you want to be conservative or not.

NFPA 13 in chapter 9.2.7 is regarding sprinkler spacing (and other requirement such as the provision of quick response sprinklers...) when you may omit sprinkler above the cloud ceiling.

The following is just my point of view.

If you have sprinkler both above and below, you can still follow the requirements (if they are more restrictive than the minimum requirements from other chapter), or not, for the sprinkler located below the cloud ceiling.
You can choose the most restrictive requirement just to be sure.

Note that 9.5.5.3.1.2 is to provide additional sprinklers below the obstruction, but does not prevent to provide sprinklers at the ceiling level. In other words, because the heat plume from the fire will collect anyway at the ceiling level, you may (and in most case will) operate sprinklers above the obstruction.
The protection below the obstruction is just in case the fire is so bad, and not controlled by the ceiling sprinklers because of the obstruction, that the sprinkler underneath will operate if the fire is located below.
Sprinklers do not operate with radiant heat from the heat plume if they are not located directly inside the heat plume.
Sprinklers operate at the ceiling level, because the ceiling collect the heat at the sprinkler location.
Sprinklers with shields (as within in-racks) are not collecting heat. The shield is just to avoid that water from the ceiling sprinkler can wet the fusible element (bulb) of the sprinkler underneath and thus delay its activation.

Whatever the size and shape of the shield, they are of poor benefit.

Work done at Factory Mutual showed that convective heat typically supplies more than 80 percent of the heat sprinklers need for activation.
Convective heat needs a flow of air past the sprinkler. Testing has shown that heat collectors with edges, such as inverted boxes, can actually delay sprinkler response, presumably because they create dead air space. Flat heat collectors are only effective where the edge of the heat collector picks up the fire plume and acts like a small ceiling. To work effectively, the combined areas of heat collectors need to make up a large percentage of the floor area.


A study performed in 1990 (“A Study of the Utility of Heat Collectors in Reducing the Response Time of Automatic Fire Sprinklers Located in Production Modules of Building 707,” prepared for the U.S. Department of Energy Rocky Flats Plant by Hughes Associates, Inc. (HAI)) stated the following:
• Heat collectors with the edges turned down around the side produced a dead air space and the sprinklers had longer response times than sprinklers with a flat heat collector

Different types of heat collectors (with or without edge)
• The heat collector must be in the plume to be effective. If the centerline of the fire is more than 1 to 2 feet from the edge of a flat heat collector, a standard-response sprinkler may take longer to respond, regardless of its thermal sensitivity.
• If a fire is midway between two sprinklers, the sprinklers may not respond at all (regardless of the size of the heat collector) because the sprinklers are not exposed to the convective heat flow of the ceiling jet.
• Quick-response sprinklers activate more quickly than standard-response sprinklers only if the fire was directly underneath the heat collector.

Franck
11/5/2020 02:41:30 pm

Sorry for being sometimes so late to answer... but I am living in France, with time difference :)

On the Clock
11/6/2020 10:48:34 am

Thank you for you time, expertise, and perspective, Franck - Have a good evening!

On the Clock
11/5/2020 10:47:39 am

I’m following this, as I am running into variations of this all the time. I feel NFPA #13 concentrates more on whether or not sprinklers are required above, but is lacking in what is required for protection below, unless extrapolating from similar sections. I often encounter several smaller clouds that individually, would not require sprinklers below, but if several are arranged side-by side, with only a small gap in-between, does this constitute one large obstruction based on ceiling height and width of gap, kind of applying in reverse the allowable gap with of 8.15.24.1(1) (2016) (A9.2.7.1(1) (2019)? And what if each cloud would individually require sprinklers, would several side-by-side require a sprinkler in each cloud, or could you utilize maximum sprinkler spacing and skip clouds based on the paragraphs mentioned above? ID the gap is no more than 6-inches, can you center a pendent sprinkler with shield in the gap itself if complying with the 3-inch rule of 8.5.5.3.1.2 (2016) and 9.5.5.3.1.2 (2019)? As in the original post, I’m running into this with ceiling cloud arrays and sound reflectors in performing arts centers.

Reply
Franck
11/5/2020 12:20:44 pm

This is a difficult question and the answer, as very often, is... it depends

You have to consider the smaller clouds as obstructions from the ceiling sprinklers and make a technical judgement whether it creates an obstruction or not.
It may depend on the width of the obstruction and the distance below your sprinkler head.

Check §10.2.7.2 Obstructions to sprinkler discharge pattern development in NFPA 13 (2019).

It is just like with ducts or cable trays or pipes.
One cable tray (less than 4 ft wide) may not be an obstruction, but 3 cables trays running in parallel may create an obstruction.
It is the same with pipes or ducts.
Remember, for example, that with upright sprinklers, you need a riser nipple to limit the obstruction from the branch line if the size of the piping is 3" or more, for example... (§10.2.7.2.1.8).

Figure 10.2.7.2.1.3(b) is quite explanatory for small obstructions below the deflector that create obstruction to sprinkler discharge. If your deflector at the ceiling level is less than 3 times the width of the obstruction and the obstruction located less than 24 in. from the deflector, then you have an issue (and need to provide sprinkler protection underneath).

The only permission is for obstruction less than 4 ft and located more than 18 in. below the deflector's plane (which is a result of 10.2.7.3.2).

Reply
Franck
11/5/2020 12:00:33 pm

Note that in the MeyerFire tool kit, you have an interesting Cloud Ceiling Calculator

Reply
Rosstan Snow
11/5/2020 03:54:11 pm

It does but for this application its impossible to determine given the various opening between clouds, the wall...etc. There is no doubt protection below is required based on condensed spacing. Overhead protection is a given. If the edge to edge spacing of the clouds were 6" or more, then it would interesting to see what sum the calculator would advise. Nevertheless; everyone's feedback has been impeccable. In Houston, the adopted code is still 2010 NFPA 13; Harris County is 2013 NFPA 13. Very few jurisdictios have adopted 2016 much less 2019. However, I have submitted a variance in code between 2013 and 2016 and Harris County accepts certain design approaches based on the newest code. Houston? Not a chance

Reply
Franck
11/6/2020 01:11:57 am

My life is easier :)
Working in loss prevention for an insurance company based in Europe, we don’t have your IBC (which is not “international” but “north american”) and I can use the latest version of NFPA to recommend improvement.
This way, we can improve situations based on the latest evaluation and modernization.

On the other hand, each country may have its own regulation and it is sometimes a hard job to convince them to do more than the minimum legal requirement and to follow an “american” standard




Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​January '21 Contributors!
    1. Franck
    2. CJ B.
    3. Dan W.
    4. Jesse
    ​5. Gleen B.
    6. Casey M.
    7. Mike
    8. Pete
    9. HJ
    10. Wayne


    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2020 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About