MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Smoke or Heat Vent with ESFR Sprinkler System?

6/10/2021

6 Comments

 
NFPA 13 Section 20.6.6.3:
"Early suppression fast-response (ESFR) sprinklers shall not be used in buildings with automatic heat or smoke vents unless the vents use a high-temperature rated, standard-response operating mechanism."

ESFR sprinklers are designed to act fast and suppress the fire, the inclusion of a roof vent that opens up before the sprinkler activates could severely impact sprinkler activation both in terms of timing and location (as the moving smoke could activate a more remote sprinkler). If automatic roof vents are present, they should have a high-temperature rated standard-response operating mechanism to ensure that the sprinkler activates before the vent opens up.

Based on the above, am I correct to interpret smoke venting is not required with ESFR systems?

How do I go about handling smoke or heat vents with ESFR, or are they not necessary to begin with?

​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
6 Comments
Franck
6/10/2021 08:13:46 am

The value of automatic vents in unsprinklered buildings is not questionable.

For sprinklered building, on the other hand...
Sprinkler protection systems are not designed to operate with open heat and smoke systems at the roof level which would generate air flows and might have a cooling effect at the sprinkler head location, this could result in a critical delay in sprinkler operation.
Sprinkler protection criteria are based on the assumption that roof vents and draft curtains are not being used.
When operating too early (before the sprinkler activation) it may open more heads.
On the control mode, this is an adverse situation, but not always critical.
With ESFR, it becomes critical because of the limited number of heads, the quick operation of the sprinklers and the purpose that is extinguishment, not control.
For that reason, "we" don't want heat/smoke vents to operate before the ESFR.
This the requirements for "no vents" or manually operated vents with a high temperature fusible link.

On the other hand, firefighters need smoke/heat vents for some operations.
This is when sometimes standards may come in conflict.

Venting in a sprinklered fire does not remove heat and smoke for manual access as effectively as in an unsprinklered fire because sprinkler water entrains smoke and absorbs much of the heat. With sprinklers preventing air temperatures from reaching very high levels, the temperature differential between the inside and outside air is fairly small, so the rate of smoke passage through the vents is minimized. Therefore, in most cases, venting a sprinklered storage fire is neither effective nor desirable. During the initial stages of the fire, it is usually best to keep the building closed to limit the supply of air while sprinklers gain control.

You will find interesting information in NFPA 13E– Recommended Practice for Fire Department Operations in Properties Protected by Sprinkler and Standpipe Systems – Annex B

Reply
Franck
6/10/2021 08:16:23 am

But at the end (as it is normally the case), the AHJ will have the last word on whether you need to put smoke vents or not in your building.

If you need to, with ESFR, just be sure to have manually operated vents only, and with a fusible link with a temperaute rating well above the operating temperature of the sprinklers (high temperature fusible links for smoke vents are better when using ordinary temperature ESFR).

Reply
CJ Bonczyk
6/10/2021 08:17:49 am

If a smoke and heat removal system is installed along with a sprinkler system, the automatic roof vents are required to have an operating element with a temperature classification higher than the sprinklers per NFPA 13. This is in hopes to minimize the potential effect the smoke and heat removal system can have on sprinkler activation. For automatic heat or smoke vents used with ESFR sprinklers by requiring automatic heat or smoke vents to use a high-temperature rated, standard-response operating mechanism. However if allowed by the AHJ depending on the use of local codes adopted, you can eliminate the use of smoke and heat vents with the use of ESFR sprinklers in high piled storage occupancies.

Reply
Jay
6/10/2021 09:08:24 am

See International Fire Code chapter 32 for the table that specifies when smoke and heat vents are required.
Pay attention to table note J, which states that the smoke/heat vents are not required when the building is protected with ESFR installed in accordance with NFPA 13.

Reply
Chong Y K link
6/11/2021 03:53:51 pm

Based on the above response please confirm on the following :-

We are doing a FEED for a Copper Foil Plant and would like find out whether any one of you have any experienced on the Copper Foil Factory for the production of electro-deposited copper foils used in Lithium-Ion Batteries for electric vehicle.

I would like to know whether any fire compartmentation and smoke fill system required as the Ground Floor occupies 7 acres of floor space.

From the Basement the copper materials are transported to the First Floor where 14% sulfuric is added to dissolve the copper scrap. Due to the array of piping in the production process, it would be difficult to do have an oversize compartment as they requires this free space for the production flow from Basement to the First Floor.

Appreciate your confirmation on the above as we intend to use ESFR sprinkler system as per NFPA 13 and all production floor shall be sprinklered.
Appreciate your comments and advice.

Reply
sean
6/12/2021 08:13:30 am

See 910.2 of the IFC or IBC they have an exception for ESFR sprinkler systems

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top May '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 45
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT