MeyerFire
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
ALL THINGS FIRE PROTECTION | SUBSCRIBE NOW

Relief Valve for Wet Pipe Sprinkler Systems?

5/3/2019

9 Comments

 
NFPA 13 (2016 Section 7.1.2 or 2019 Section 30.3.1) requires a relief valve on all wet pipe systems. The only exemption is where air reservoirs are installed to absorb pressure increases, then a relief valve isn't required.

This seems straightforward but I don't recall seeing independent relief valves on the far majority of the wet pipe systems I've come across. How is this requirement typically met from a design standpoint? Am I missing something or looking in the wrong place?

Posted anonymously for discussion. Discuss This | Submit a Question | Subscribe
9 Comments
Wayne Ammons
5/3/2019 06:54:19 am

Prior to the 2010 edition of NFPA 13, only gridded wet pipe systems were required to have this relief valve. Tree systems typically have more trapped air than gridded but with air venting becoming more popular for mitigating corrosion (also required with the 2016 edition of NFPA 13), there should be less trapped air in all wet pipe systems. This can cause increased pressures within the system due to water fluctuations, solar heating, etc.

I typically include the relief valve on the inspector's test on the riser. You can buy an inspector's test and drain assembly (i.e. AGF) or piece it together with individual components.

Reply
Jim McHugh link
6/4/2019 11:55:59 am

Hi Wayne,
Prior to 2010 you also needed to install a relief valve downstream of all pressure reducing valves. One of the issues is code recommend 1/2" valves in one area and 1/4" in another.
This was cleaned up in the 2010 edition.
Thank for mentioning our AGF TESTanDRAIN valves. Our models 1011A and 2511A included a UL/FM pressure relief valve and drainage piping.
Thanks, Jim McHugh

Reply
TJ Jones III
5/3/2019 10:16:39 am

Your Ready Risers can come with a Relief valve on the Test and Drain. You can also order them in an assortment of settings. 175 PSI is the standard for them so you have to plug them during testing.

Reply
Franck
5/3/2019 10:23:57 am

As indicated above, this is quite a new requirement (less than 10 years) and is not retroactive. So many systems are installed without this piece of equipment.
But it is not a bad requirement. Not only for possible air trapped in the system (and corrosion issues) as indicated by Wayne, but also for possible pressure built-up in some systems.
Some sprinkler systems are regulated at quite a high pressure. And the pressure downstream the ACV remains at a high level, whatever the possible fluctuations on the pressure upstream on the water supply side.
If the building has high difference of temperature between day and night (heated by the sun under the roof, for example) or for systems running close to hot equipment, the pressure might increase even more (this is a closed system and a fluid that is heated will expand) and could reach very high levels, sometimes up to 175-200+ psi... which is not good for long term operations on sprinkler systems (sprinkler heads are normally rated at 175 psi).
This is when this pressure relief valve is interesting, even for old systems.

Reply
Ivonn
5/3/2019 10:29:30 am

Relief Valve are require in a wet system agree with section 8.1.2 NFPA 13 Ed.2019 in each system except where have an air reservoirs like you said, typically the inspector, test and drain have a 1/2" relief valve and you comply with that point.

Reply
StephenJ
5/3/2019 11:18:13 am

I just wanted to point out that the requirement you pointed out are different. Section 30.3.1 in the 2019 version of NFPA 13 is a requirement specific to merchant vessel systems. Chapter 30 is titled marine systems.

Section 7.1.2 in the 2016 version is now 8.1.2 in the 2019 version. The intent of 8.1.2.1 is to prevent pressure in wet pipe systems from exceeding 175 psi for sprinkler systems or the maximum working pressure. You would have to use a little judgment here and evaluate the supply to determine the likelihood of exceeding this pressure.

Reply
David Toshio Williams, PE/FPE link
5/6/2019 11:24:57 am

Before this change in the Code we were the A/E firm on a project fairly near a city water system pump station, the pressure pulsations from the pump station would gradually build in the sprinkler system until the heads would blow. In the end the system check valve was drilled with a small hole to relieve pressure (and the City checked how it was operating their pumps). (Back in the day we only provided a single check valve on the water service connection).

Today we would have called for the installation of the relief valve and that would have taken care of this issue.

I have seen more than one "new" installation where the relief valve has been skipped even if we show it in the design details we call for in a performance design project. I think the trades are still learning about this 10 years later!

The test connection with 3/4 inch relief valve tapping seems to be the way to go.

Reply
Jon Paton
5/17/2020 10:22:28 pm

My system was poorly designed. Static fire water pressure is constantly at or above the relief valve rating. This causes the valves to constantly leak. I can't rebuild the fire system. Can I put two valves in parallel or in series to reduce pressure? Would that invalidate the system?

Thank you

Reply
Jim McHugh link
5/18/2020 07:39:42 am

Hi Jon,
You can get different pressure ratings on the pressure relief valves. The pressure marked on the valve indicates an operating range. An example would be a 175 PSI valve begins opening at 90% of its range so it would begin opening at 158 psi. Also the valves are designed to be fully closed once the pressure drops below 80% of it indicated range or 140 psi. You may need to simply swap out the valve you have for a different pressure such as 205 psi or 225 psi. If you have other technical questions please give me a call at 610-240-4900 Thanks Jim McHugh

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​February '21 Contributors!
    1. Dan W.
    2. Franck
    3. Jesse
    4. CJ B.
    ​5. Brian G.
    6. Mike
    7. Matt
    8. Casey M.
    9. Jay R.
    10. Glenn B.

    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Picture
Home - About - Blog - Contact - Exam Prep - Store

​Copyright © 2021 MeyerFire, LLC

The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About