MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • Content Library
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Privacy Pods (Framery O, Q, Q2) Need Sprinklers?

4/23/2020

7 Comments

 
Are office privacy pods such as Framery O, Q, and Q2 required to have sprinkler protection in the United States?

Their literature says there is no need for installing sprinklers within them in Europe? Here is a link to an example: frameryacoustics.com

​​​​​​​​​​​​​​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
7 Comments
Thomas Jones III
4/23/2020 09:40:48 am

For the Q2, yes, any obstruction over 4'-0 requires a fire sprinkler. For your other options I would say yes as well, especially if they cannot move and do not count as furniture.

Reply
Donna Kimler
4/23/2020 10:35:21 am

Yes, to all. The small one would be treated like a closet. You could possibly state a case that they are furniture to the AHJ. As always, the AHJ would have the final say.

That is not something I have seen previously.

Reply
Mike L
4/23/2020 10:51:46 am

We deal with these a lot in the modern open-office concept in NYC. We apply the requirement of IBC Section 903.3.3. Obstructed Locations "....automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands or equipment that exceeds 4 feet in width."

Reply
Jonathan Joseph
4/23/2020 11:07:16 am

I would have to say that is an occupied compartment and obstruction, so yes. I would treat this as a light hazard Tenant Improvement if there is an existing system.




































.

Reply
Jesse
4/24/2020 08:53:25 am

In the US, each AHJ is autonomous. So each would have its own final say. That being said, this is clearly an obstruction to ceiling level sprinklers, and would require protection.

Reply
Bruce Verhei
4/27/2020 11:15:36 am

Good morning.

I do not believe European or British sprinkler design practice has adopted reduced design area for quick response heads in smooth, level, lower height ceilings, the common use of extended coverage heads, and hydraulically calculated systems in office, light hazard systems.* So at this point European office sprinkler standards are more conservative in at least three ways, meaning they deliver a higher real world actual delivered density over a larger area.

Step back from NFPA 13 and let’s look at the higher level building and fire code level. American codes are widely viewed as being more dependent on active vs passive fire protection systems.

NFPA 13 may limit its design light hazard design to fire control. For example there is no smoke production control design criteria in 13. Yet American building codes make large allowances for exactly this factor, even in non-performance designed buildings. See especially exiting in sprinklered vs unsprinklered buildings.

Again sprinkler designers are not required to consider their system as alarm detection, except as codes specify breakdown of flow switches and piping configuration to match. Designers and reviewers applying the building and fire codes do explicitly view and consider the sprinklers heads, in combination with flow switches, as heat detectors.

By the time you get to high-rise activation of a sprinkler head initiates more than ten systems just at the building.

So back to the original question. A review and approval to European design standards is not transferable to American situation. American sprinkler design is less conservative. American building codes are more active system dependent. Those active systems are all dependent on timely fusing of one sprinkler head.

We also count on fire, and by implication, production of smoke, control, by the applied water. Go Parmalee & Grinnell.

Based on information supplied, I’d say sprinkler protection does need to be extended to interior of unit.

Best.

* Please correct me where I am wrong. I have never applied BS or European standards. bv.

Reply
Ck
4/27/2020 02:18:40 pm

This will depend on what the AHJ chooses to enforce. This issue has been coming up as new and existing office buildings continue to add these. For me, it is an easy call if it is over 4 feet, and we have looked at everything else on a case by case basis.

Here is a similar question and answer from NFSA.

#8 - Phone Booths


A bank of phone booths is installed in a facility adjacent to a wall. Each booth is approximately 36 in. by 36 in. Are sprinklers required in these features in accordance with the 2016 edition of NFPA 13?


Answer: There are no specific exceptions for phone booths to omit sprinkler protection in NFPA 13. The closest section would be NFPA 13 -2016, section 8.1.1 (7) which states that furniture and similar features are not required to be provided with sprinklers; however, this section limits this omission to features that are not intended for occupancy. A phone booth will be subject to occupancy of at least one person. NFPA 13 does not have a definition of "intended for occupancy" so it is not clear if the transient nature of occupancy in a phone booth was intended to disqualify these features from this exception.


The 2018 IBC does address this issue in section 903.3.3:

[F] 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with regard to obstructions that will delay activation or obstruct the water distribution pattern and shall be in accordance with the applicable automatic sprinkler system standard that is being used. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers.


This section seems to exempt the phone booths if they do not exceed 4 ft in width; however, the commentary for this section did not provide any additional helpful information. In light of the vagueness of the requirement of installing sprinklers in these booths, it would be prudent for the responsible design professional to take into consideration the combustibility of the booth, the potential sources of ignition and the transient nature of the occupancy of the phone booths and come to a determination with the input of the AHJ(s). If it is decided to omit sprinkler from these booths, the ceiling sprinkler coverage needs to cover to the wall as it the booths were not present

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​July '22 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 75
    NFPA 82
    NFPA 90A
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2022 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • Content Library
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT