MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Playpipe without Tip OK for Testing?

10/10/2023

8 Comments

 
I have observed forward-flow tests of backflow preventers, and fire pumps tests, that are conducted through 2.5-inch nozzles identical to the image below, but without the playpipe tip screwed onto the end of the nozzle.

Image Link

​
The pitot reading was taken off the 1-3/4" threaded end of the nozzle where the playpipe tip gets screwed on.

Is this approach acceptable, and would the GPM table for the 1-3/4" butt for converting the pitot pressure to flow be acceptable?

​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Dan Wilder
10/10/2023 08:46:06 am

As long as the measurements are taken from the correct location per NFPA 291 for the discharge orifice size and the corrected Coefficient is used, this is acceptable. Just make sure that the hose between the two points isn't too long and creates excessive friction loss and skewing results.

Reply
Eric R
10/10/2023 08:53:25 am

I think it would depend on what kind of test you are performing, and what level of precision is needed.

You can use the playpipe as a generic "stream straightener", but I would not recommend using the GPM flow rates listed with the device based on an actual 1.75" tip. NFPA-291 4.9.2 recommends that you use a 0.95 coefficient of discharge if there is no specific listing information. I did a quick check online, and it looks like all the major brands sell a 1.75" tip as opposed to listing the cD of the tube without a tip.

So if the flow test is for a hydrant or backflow you should be able to comfortably use the 0.95 cD and at worst case get a slightly conservative test result.

For a fire pump though, that margin of error could put the pump off it's factory curve enough to fail the test, so I would be much more hesitant in that case.

Reply
Anthony
10/10/2023 08:58:31 am

NFPA 291 will say the reading from the hydrant should come from:

Q = 29.83 * c * d2 * √P

So you'll have to get a proper coefficient of friction for you nozzle and use the proper diameter.

I'd also assume you have some loss through your hose you'll need to account for. I don't think this is a table look up problem.

Reply
David Kendrick
10/10/2023 09:22:02 am

Curious, I've read this comment several times about hose length.

If there is a known pitot pressure (flow) and a known supply gauge (residual) pressure points. Using this along with a static pressure these two points would create a flow curve.

If the hose is "long" the resistance would lower the flow. It would be a known flow reduced none the less. With a short hose the flow resistance would decrease and flow increase.

A flow test with a static and residual from the same consistant supply should plot along the curve.

If the goal is to flow a specific quantity of water as in forward flow or fire pump test larger or multiple flowing sources might become more important.

Fairly confident that flows from a consistant source will generate the curve whether it is from a direct connection to the outlet or through hoses.

Really looking for input. I may have been misunderstanding the physics of this for a long time.

Reply
DAVE
10/10/2023 01:33:46 pm

That has been my belief as well, and have argued the same. I think we purched 3" diameter hose material just to have the ability to crank the gpm to #11.

Reply
Ivan Humberson
10/11/2023 07:31:39 am

David, I totally agree. As long as the static and residual pressures are taken at the source, where the flow characteristics need to be determined, the length of hose will have no effect on the characteristic flow curve, other than the data point while flowing water may be a lower gpm due to the friction loss in the hose.

Reply
Glenn Berger
10/10/2023 04:03:38 pm

As long as the calculations are based upon the true flowing orifice the test results should be acceptable.

Reply
James Art. FPE
10/21/2023 08:59:38 pm

Using a Playpipe is fine! Great Idea.

Esp. useful if the flow is weak and the pitot readings are low.
See Meyerfire's write up on flow testing.
If pitot readings from the hydrant butt are 10 psi or below, great time to use a playpipe or other nozzle.
to reduce the opening (take your choice of the 1 3/4 " without the last reducer or the 1 1/2" if that is the size of your reducer. Even with a low flow, that will get your pitot readings up where they are more accurate, more reliable.

And while it is easiest to just screw it to the hydrant butt, a bit of hose doesn't really hurt. You need to secure it to something, like running under a pickup and tying to the bumper.
A hose will reduce the Flow a little, but the curve is the same,
( the Residual at the lower Flow will be higher) and the results will still show the same water supply curve.

When I tested often for the HPR Insurance industry, I had exactly that in the trunk.
I also carried a Test Nozzle made of 2.5 inch pipe, about 10 diameters long. Produced a straight stream with less bouncing of the gauge.
It had a 2.5 inch hose coupling, with a 2.5 inch female pipe thread, cut off a fitting, welded to it. Piece of cake for a fab shop.
I also carried a 2.5 inch threaded "street" 45 degree elbow: Male on one end female on the other.
So I either just screwed the pipe into the pipe threads for a straight shot
OR
used with the elbow to aim away from the landscape, etc.
Could point it up or to either side. You gotta be careful!

These nozzles were mine, so they came with me.
But when I parked in San Francisco to survey a warehouse, I found a parking space out front, where my car had been!
When the stolen car was recovered, after weeks in their $torage yard (And they didn't tell me) all my tools were gone.
Please let me know if anyone can help me get more!

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top July '26 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 3-601-02
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    August 2026
    July 2026
    June 2026
    May 2026
    April 2026
    March 2026
    February 2026
    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • STUDENTS
    • LAND JOB/INTERNSHIPS
    • STUDENT CONNECTOR
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT