MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Is a Jockey Pump Necessary with Small 13R Pump?

2/12/2021

11 Comments

 
We have a small project (13,800 sqft total) which is a four-story, all residential apartment building, using mostly CPVC pipe. The system is under NFPA 13R.

The city supply is very poor, so we will have a fire pump that meets NFPA 20 (as is required by 13R). The pump is an 8-HP, 70 PSI at 75 GPM.

Is a jockey pump necessary with such a small fire pump?

Normally, for our large commercial NFPA 13 projects, a jockey pump is not even a discussion because we don't want the main fire pump (500 - 1,500 gpm) cycling on just to support system maintenance pressure.

For such a small project with a significantly smaller fire pump, is there any harm in not providing a jockey pump?

The question is not based on cost - the pump room is microscopic and we're already having trouble fitting in all the equipment and controllers as is.

Appreciate you all - thanks in advance.

​​​​​​Sent in anonymously for discussion. Discuss This | Submit Your Question | Subscribe
11 Comments
Peter
2/12/2021 09:08:31 am

A jockey pump is required under all installations except under a few scenarios when the fire pump is a positive displacement pump per NFPA 20, 2016: 4.26.7. The size of the pump is irrelevant.

Reply
OP
2/12/2021 09:11:43 am

Thank you Peter! Had always provided them, but didn't realize it was mandated as part of NFPA 20. Thanks for the standard reference.

Reply
matt
2/12/2021 09:39:33 am

I would disagree with peter. NFPA 20 4.26.1 specifically says that a pressure maintenance pump is one approved method - NOT required.

NFPA 20 4.26.7 says you cannot maintain the pressure with the primary pump.

It is not even required that the system pressure be maintained at any particular level. It is also not required that the main pump be activated by a pressure switch. The pump could be activated by a flow switch or other approved means.

Reply
Peter
2/12/2021 11:06:29 am

Matt,

4.26.1 lists 3 options:

(1) A pressure maintenance (jockey) pump
(2) A water mist positive displacement pump
(3) Another approved means that is not the main fire pump.

I believe the spirit of the question was if a maintenance mechanism was needed at all due to the small size of the pump. The answer to that is, yes. Simplifying that in my statement above to “yeah a jockey pump is required” was meant to mean that only in the limited instances of positive displacement pumps that do their own maintenance of pressure, you need some other external means. The most common, by significant orders of magnitude to achieve that is a standalone ‘jockey’ pump.

With that being said, in regards to the original posters comment about the need for a jockey pump, what would you recommend?

Reply
Matt
2/12/2021 11:20:25 am

I would recommend a jockey pump.

Maybe they could tie into a domestic booster? Or if the AHJ allows, just use a small domestic pump.

A jockey pump is not required, but that is what I have always done.

CJ Bonczyk
2/12/2021 10:18:54 am

NFPA 20 - A.4.26 Pressure maintenance (jockey or make-up) pumps should be used where it is desirable to maintain a uniform or relatively high pressure on the fire protection system. A domestic water pump in a dual-purpose water supply system can function as a means of maintaining pressure. A.4.26.2.1 The sizing of the pressure maintenance pump requires a thorough analysis of the type and size of system the pressure maintenance pump will serve.

Jockey pumps are not required by NFPA 20. However, requirements for their installation, sizing, and maintenance exist in NFPA 20. Thus, the reason systems using underground piping for both domestic and fire protection purposes are permitted to operate as pressure maintenance pumps. This is the reason jockey pumps, valves and appurtenances are not required to be listed. The suction valve for a pressure maintenance pump does not need to be an OS&Y and the isolation valves are not required to be supervised.

A jockey pump is required with automatically controlled pumps (unless a way of maintaining system pressures above the fire pump start pressure is provided) and used when system pressures need to be boosted or maintained regularly to lower the chances of pressure surges and decrease chances of waterflow false alarms. Additionally, since fire pumps are not designed for pressure maintenance purposes and should not be used for operating short periods of time to boost system pressure, a pressure maintenance pump is typically placed on the system

Reply
Franck
2/12/2021 10:36:20 am

As a fire pump may start automatically upon pressure drop and normally does not stop when a higher pressure is obtained, you may have an issue if there is a pressure drop in your system (small leakage somewhere that slowly put the pressure down) that start your pump automatically if you start it upon a preset pressure in the system.
In that case, you fire pump will run forever, with no -or very limited- flow, which is not desirable.
Another advantage of maintaining the pressure in your system close to the pressure at churn of your pump, is to avoid water hammer.
But a Jockey pump is not the only solution.
You can also have a pressure tank (even though it takes even more space to install).
Or maybe your city water system can provide some sufficient pressure at no flow to maintain your system at a desirable level ?
And note also that this does not apply if your pump is activated by a flow switch, as indicated by Matt

Reply
Mike
2/12/2021 12:38:09 pm

A jockey pump is only required where the fire pump is started by pressure actuation. Some systems may use pumps but may not require constant pressurization as is the case with manually operated foam systems.

In this case, the alarm valve pressure switch activated the pump.

Reply
Phil W
2/14/2021 12:08:35 pm

Where you do have a large system/s that does need a pressure maintenance pump, I would even consider providing two (one as back up) given the chaos that can happen if the duty jockey pump fails (fire pumps constantly starting, alarms being raised, building evacuations.....) We often offer a contingency spare at least

Reply
Onur
2/15/2021 07:07:18 am

Hello to everyone,
There are many variables to consider in the question.
But shortly,
As far as i understand, the pump capacity is able feed drop pressure (leakage) and working pressure.So i think it's applyible.

Thanks for good question and comments.

Best Regards,
Onur,

Reply
Oscar Relucio
10/23/2022 05:20:17 am

My comments below consider logic and practicality more than invoking the code.
1. Space for the jockey pump should not be an issue at all since a very small compact in-line pump can be mounted on the pipeline along the wall, hence would not even take up floor space;
2. Given a four-storey apartment building, any slight building movement (due to minor earthquakes, etc.) and/or ageing or poorly maintained pipe fittings and valves may produce leaks which would be more economically addressed by a fractional hp pump running 24/7 than an 8-hp pump.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top May '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 45
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT