MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Ignore Fire Pump Boost if City Supply Sufficient?

4/29/2021

9 Comments

 
​I'm designing a fire suppression system for a new boiler room at an existing hospital. It will connect to the existing fire suppression piping. The hospital is served by a fire pump, but the existing pressure at the street is satisfactory to supply this particular space with enough water for Ordinary Hazard Group 2 occupancy without the pump.

Do I still need to include the fire pump in the hydraulic calculation, or can I ignore it?

​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Matt
4/29/2021 08:09:44 am

Can you exclude the pump - I suppose. The design will likely work. It is probably not a good idea, especially if the drawing will become part of the building record. The lack of accuracy in the drawings will likely create confusion when the plans are referenced in the future. I would put it in there.

Reply
Cameron
4/29/2021 08:15:52 am

Depending on the street static pressure and the pump churn pressure, you may just want to verify and/or document (more importantly document to cover yourself) that your not exceeding the maximum allowable pressure in you system components. I myself would include the pump in order to provide the most accurate picture of the system.

Reply
Mr Glenn Scott Berger
4/29/2021 08:16:28 am

It all depends on the piping arrangement.

If the fire pump is on the supply to the sprinklers in that space, no you cannot ignore the pump. If there is a normally opened bypass of the pump, then potentially you can ignore the pump.

Reply
Franck
4/29/2021 08:28:46 am

If your connection to your sprinkler is downstream your booster pump, I would suggest you to do both.
That way you can prove that with the booster pump you are not overpressurizing your system (but it shouldn't as the booster pump is already in place for the other systems) and shows a lot of reliability as the demand point of your system will be well below your water supply curve.
And you can also prove that in case of an impairment of your booster pump, you can still adequately supply your sprinkler system by using a by pass (if a bypass is provided around your pump).
This would give credit to the reliability of your installation.

Reply
Dan Wilder
4/29/2021 08:47:44 am

Unless there are some pretty specific circumstances to ignore the pump (or any other fire protection feature affecting the design and layout of a system), it should be drawn to match what is installed.

The design may not require the pump, but is there not optimization of the higher available supply curve to reduce pipe sizing?

In other systems (I assume the system is closed sprinkler wet), but with deluge, foam, or preaction systems with delivery times, omitting the pump will have some negative and misleading results that can be crucial for both our design and others (containment, duration of application, over pressurization of equipment being some factors).

Reply
Brian Hoole
4/29/2021 08:50:13 am

The pump will allow you to minimize your pipe sizes. Be sure to keep in mind that for lower floors you will either need a pressure limiting device at the floor control when boosted by the pump or to feed a riser manifold prior to the pump that will supply the lower areas.

Our city water has a fairly flat curve with a static pressure above 110 psi. Utilizing a separate manifold on the supply side of the pump we had two small dry/preaction risers for the server room and parking garage. The supply main then tied into a the primary fire pump and filled a tank for the secondary pump. The discharge of the pumps supplied the various standpipes. This allowed us the mitigate three pressure zones within the high rise.

Reply
Aaron
4/29/2021 08:54:38 am

You didn't mention whether the total water demand for the ordinary hazard II exceeds the max flow (at 150%) of the pump or not.
We had a similar situation and the EOR directed us to connect the control valve to the system requiring more water than the pumps output to the incoming water supply before the pump. Otherwise the pump will reduce the water supply.
(I'm not sure why we couldn't rely on the normally opened bypass as mentioned by Mr. Berger.)

Reply
NK
4/29/2021 09:04:32 am

Most of the AHJ's in our area require a fire pump test report from within one year for hydraulic calculations of buildings with fire pumps. One of the big reasons is to check to see if the fire pump is performing in compliance with NFPA 25. If a pump is performing very poorly the AHJ might ask the building owner to investigate the situation even if the calculations work. Your calculations might work for this project but the the fire pump is most likely needed for a different area of the building and should be maintained per NFPA 25.

Reply
CJ Bonczyk
4/29/2021 09:19:35 am

I would suggest that you include the booster pump. The purpose of this is that in your calculation if this area now becomes the most demanding portion of the system on that floor hydraulically then you will want to ensure your new hydraulic calc plate accurately reflects the information based on what is actually boosting the system water supply. You can easily obtain a most recent copy of a fire pump test report that provides the 3 point curve indicating the suction supply along with the booster pump operating and providing the discharge pressures and flows. I would then calculate back to the discharge side of the pump using that information as your supply. It does not hurt to additionally calculate the system without the use of the booster pump to confirm the water supply works alone. Thus at a later date if the booster pump is out of service you will know what minimum water supply is needed to allow the system to work if there is any degradation in the city supply.

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​Jan 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT