MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Hydraulically Calculate Length of Dry Sprinkler?

5/10/2022

18 Comments

 
When performing hydraulic calculations, do I need to account for the length of the barrel of a dry sprinkler?

The sprinkler itself starts at the threads, but the length can sometimes be quite long before water hits the orifice of the sprinkler.

Under NFPA 13, under friction loss, the closest I can find says "friction loss shall be excluded for the fitting directly connected to the sprinkler."

Thanks in advance.

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
18 Comments
Alex Riley
5/10/2022 07:18:21 am

Hi,

The code section you referenced, NFPA 13 (2013) 23.4.4.7.1(9), I believe is referring to the reducer. For example, a 1" to 1/2" reducer you would typically find on an upright/pendant.

I have always added the length of the barrel for my calculations.

Thanks,
Alex

Reply
Jesse
5/10/2022 08:07:26 am

If you're using 1" dry pendents and also using 1" drops for other pendents the calculations is the same. If I was using a 3/4" dry pendent I would certainly put the dry barrel length in, but in most case I'm just doing it for fab purposes.

Reply
M. Newell
5/10/2022 08:10:36 am

It has always been my understanding that the way the dry sprinklers are tested and listed they have already factored in the length during the testing process. So based on their listing and testing it is the same for a dry sprinkler with a 12” barrel as it would be for a standard pendent in a bell or ell. You don’t add the drop length to your calculations as friction loss.


This can be seen with the Victaulic VS-1 series dry flexible sprinklers, they calculate the same as a normal sprinkler in a fitting or outlet with no additional friction loss.l even though they come with a flexible sprinkler hose up to 48” in length.

Ultimately it would be best to check the cut sheet for the specific dry sprinkler you are using to verify during your design.

Reply
Christopher J Logan link
5/10/2022 08:33:34 am

I have always been under the understanding that the length of the sprk is factured in as well.

part of the 48" max for listed assembly.

Reply
Anthony
5/10/2022 08:34:58 am

There is a significant hydraulic difference between a 4'-0 dry barrel and a 1'-0.

If you're flowing 30 gallons through that 4' pipe you're losing 1.5 psi compared to 0.38 psi through a 1' pipe (assuming 1'' nominal diameter sch 40, c100)

So yeah, you have to account for the barrel on the dry pipe.

Reply
Dan Wilder
5/10/2022 08:36:26 am

Many of the cut sheets have this kind of language (this was taken from a Viking Cut Sheet) which means you don't need to adjust for the dry length per NFPA 13-19' Section 27.2.4.10.3 - "Flow from a sprinkler shall be calculated using the nominal K-Factor except that the manufacturer's adjusted K-Factors shall be utilized for dry-type sprinklers"

"K-Factor applies for standard lengths (“A” Dimensions indicated above)."

Nominal K-Factor: 5.6 U.S. (80.6 metric*) for all listed and approved lengths.

These sprinklers are listed and approved in lengths from 4” to 48-1/4” (102 mm to 1,226 mm)

I have seen some lengths at 36" but it needs to be reviewed on a MFG sheet specific basis.

Reply
CJ Bonczyk
5/10/2022 08:41:10 am

Yes the length of the matters significantly for hydraulics. As the length changes the K-Factor changes for many manufacturers on their data sheets. Secondly pay attention to the C-Factor. Lastly the exposure temperature charts will dictate the minimum barrel length. All of this information is typically listed on the manufacturer data sheets as it varies for each type and manufacturer.

Reply
Glenn Berger
5/10/2022 09:09:36 am

You need to document what k-factor being used. K-factor for the dry barrel assembly should be used and assumed at the tee-connection.

Reply
David Kendrick
5/10/2022 09:13:54 am

The engineering behind a UL listed product probably exceeds my skill, knowledge and intelligence.

As an example from the Viking technical bulletin.

Viking K Factor 5.6 Dry Sprinkler -- "Nominal K-Factor: 5.6 U.S. (80.6 metric*) for all listed and approved lengths."

Pulled technical bulletins from two other manufacturers. None showed any changes in the K Factor for their dry sprinkler heads based on the length of the barrel.

The K Factor for dry sprinkler heads is the number you use. Lengths are limited by their listing but the K Factor remains the same.


Reply
Brian Gerdwagen FPE
5/10/2022 09:15:03 am

Glenn is 100% correct, as are some others. The adjusted K factor from the manufacturer gives you the K factor at the fitting the sprinkler is attached. There is no need to add additional friction loss for the length of the barrel of the dry pendent.

Reply
Alex
5/10/2022 12:46:42 pm

Brian, Glenn,

I didn't pose the original question but I want to follow up on both of your responses. I would agree to use a provided discharge k factor that takes in account the barrel length/diameter/C factor/etc, but what if they aren't provided? To me, its not common they are.

For example, how would you handle Tyco's TY3155 dry upright? There is no various K factors provided on the length of the barrel. Are you saying that Tyco has engineered the sprinkler to already adjust for the friction loss through the pipe? I don't see how that is possible since its contingent based on the flow.

I may be over thinking this issue but very curious now. It doesn't appear there is a lot of information out there explaining it..

Thanks in advance,
Al

Reply
David Kendrick
5/10/2022 03:06:16 pm

When you see the size of the orifice entering and exiting the assembly well rough guess the barrel is three times the area of the orifice. Relatively little resistance to the flow.

If it's published that the K Factor of the head is x.x then that is the K Factor.

Viking put it into words that this is the way the heads are listed up to 48" in length.

Reliable and Tyco did not publish that statement. With them there is no restrictions or method to calculate their UL listed product.

I read what they publish. Follow their printed data.
For me to rethink their product would be folly.

schulman
5/10/2022 09:56:32 am

i see conflicts in the responses - my state construction office requires calculating the lengths of flexible connections to Vic's Flex Sprinklers so whether M.Newell or others are correct or incorrect, my situation requires I calc the lengths (including dry barrel). Check with your AHJ or State Construction Office and streamline your process to include the most stringent requirements ... The "costs" should be passed on to the owner anyhow so why not be safe and do it ?

Reply
Dan Wilder
5/10/2022 10:37:28 am

Vic already states in the literature:
K Factor • 5.6/8.1 S.I.
For system design purposes, no equivalent length calculations are required.

These aren't sprinklers attached to flex hoses, these are listed assemblies including the sprinkler and the dry flex hose. What criteria are you using to add the eq. length, just the length of the hose itself? No requirements for # or bends as well?

Reply
Jack G
5/10/2022 10:41:41 am

Back in 63, my father taught me hydraulic calculations. Head k factors adjusted to account for length are factored in. It hasnt changed.
Attended Star Sprinklers course in 68- same. Gem s in Rhode island in 76. Automatic sprinkler course in 77. University of Md in 70, taught you the same.
The head data sheet may not, or might obscurely state that.

Reply
Alex
5/12/2022 04:54:53 pm

UPDATE [5-12-22]

Hi everyone who has notifications on,

This post has been on my mind still (does that make me a nerd? My fiancé thinks so.)

Since I was still curious, I decided to ask JCI in Cranston, RI. They stated on their dry sprinklers, you do need to add the length of the barrel within the calculation. They stated, once the head opens, you then in turn have a wet pipe system.

A few above mentioned the Vic dry flex heads. I agree with you stating you do not need to add the equivalent length per the cut sheet. While JCI wouldn’t give advice on other brands, I would imagine it would be the same process UNLESS a discharge K factor is included in the cut.

In the end, adding the barrel length simply just adds to your safety factor!

Thanks,
Alex

Reply
Larry A Gallego
10/3/2022 11:29:18 am

Another aspect that comes into play is whether the elevation of the outlet on an 12" dry pendent is used for the calculation or is the elevation of the connection to the branchline/mains selected?
On a small layout I calculated one 12" dry pendent head at 0.15 gpm/fqft for 116 sqft with a K-factor of 5.6 at 9'-4" and re-calculated using the branchline elevation of 10'-4" as the head elevation with the following results:

Including 12" barrel (9'-4");
Total Flow From Water Supply Curve . . . . . . . . 17.40
Pressure From Water Supply Curve . . . . . . . . . 60.00
System Pressure Demand At Supply Curve . . . . . . 18.13
Safety Margin at Supply Curve. . . . . . . . . 41.87

Excluding 12" barrel (10'-4");
Total Flow From Water Supply Curve . . . . . . . . 17.40
Pressure From Water Supply Curve . . . . . . . . . 60.00
System Pressure Demand At Supply Curve . . . . . . 18.28
Safety Margin at Supply Curve. . . . . . . . . 41.72

The difference of 0.15 psi when calculating multiple heads may produce a significant pressure difference on the safety cushion.

When I calculate 8 heads the difference is 0.36 psi less pressure for the non-barrel calculation.

Total Flow From Water Supply Curve . . . . . . . . 174.69
Pressure From Water Supply Curve . . . . . . . . . 59.93
System Pressure Demand At Supply Curve . . . . . . 52.95
Safety Margin at Supply Curve. . . . . . . . . 6.98

Total Flow From Water Supply Curve . . . . . . . . 173.88
Pressure From Water Supply Curve . . . . . . . . . 59.93
System Pressure Demand At Supply Curve . . . . . . 52.59
Safety Margin at Supply Curve. . . . . . . . . 7.34

If the barrel is to be calculated, would the C Factor be 100? I will check with the local AHJ and see how they can enlighten me.

Thanks,
Larry








Reply
David Kendrick
10/4/2022 09:14:51 am

I checked several manufacturers data sheets for dry pendants.

One specifically stated that 48" and under all follow the K factor stated. The others did not publish any restrictions.

For my two cents the NFPA standards, Insurance Underwriters and especially the manufacturers hold the interpretive rule.

When we engineer outside the published standards we become responsible. Until then we're following the documented requirements.

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Oct '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE 100-Day Marathon
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT