MeyerFire
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
ALL THINGS FIRE PROTECTION | SUBSCRIBE NOW

How to Layout Sprinklers Beneath Steep Slope?

11/3/2020

8 Comments

 
What design options do I have with a fire sprinkler design to address protection underneath a 45-degree pitched roof?

​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
8 Comments
Franck
11/3/2020 10:14:13 am

We may need more information on what design parameters you want some guidance. There are so many.

Here are just a few.

Normally, according to NFPA, you need to increase the area of application by 30%.
Regarding the sprinkler deflectors, there are 2 schools :
- NFPA recommend the deflector parallel to the roof
- FM Global recommend deflector parallel to the floor

If you have storage underneath, note that this is out of scope of NFPA 13 and you should normally provide a false ceiling to limit the slope.
BUT, if you have a sawtooth roof (high slope, but on a limited length), you may have storage underneath, you just need to adapt your remote area to the roof configuration, so that you will activate all sprinklers along one sloped area(or 2 adjacent, depending on your building configuration).

When you determine the area of operation (remote area), you have to take into consideration the area projected on the floor (2500 sq ft on the floor will be much more sq ft of sprinklers in operation at the roof ceiling). But the min./max. distances to consider are along the roof (on the branch lines or between adjacent branch lines).

Reply
Jonathan Sullivan
11/3/2020 10:46:27 am

Not doing a lot of storage design, can you explain the logic of a false ceiling? Is it a question of activation time?

Reply
Franck
11/3/2020 11:12:36 am

If you have a large peak roof with a slope >16.7%, you cannot protect it with NFPA (out of the scope of NFPA 13).
The 30% increase with sloped ceiling is only for occupancy hazards (LH, OH, EH), but not applicable to storage occupancies.
But if you have anyway storage in such a building, the only solution (when feasible, but most of the time not cost effective) is to provide a false ceiling to eliminate the peak roof and install sprinkler underneath.

This is also done with ESFR protection when you want to eliminate possible ceiling obstruction from construction or possible roof slope exceeding the ESFR requirements.

Another solution (sometimes accepted by some AHJ/Insurance companies) is to provide additional In Rack sprinklers at the top level of rack storage arrangement to compensate and have a 30% increase at the ceiling sprinkler density.
But this is not "according to the standards" and is subject to acceptability by AHJ and sense of judgement based on commodity classification... And is not applicable to pile storage, shelf storage... only rack storage...

Note that there are many studies at the moment done by FM Global and the NFPA Research foundation regarding the effect of slope to the water distribution pattern of sprinklers.

More info can be find here:

https://www.nfpa.org/News-and-Research/Data-research-and-tools/Suppression/Protection-of-Storage-Under-Sloped-Ceilings

Or more direct access:

https://nfpa.org/-/media/Files/News-and-Research/Fire-statistics-and-reports/Suppression/RFStorageUnderSlopedCeilingsPhase1.ashx

and

https://nfpa.org/-/media/Files/News-and-Research/Fire-statistics-and-reports/Suppression/rfslopedceilingsPhase2.ashx

Jonathan Sullivan
11/3/2020 01:02:57 pm

Thanks Franck. Is this an implied or explicit slope limit? I checked Ch. 1, 10, and 20 of 13-2019 and didn't see this 16.7% stated. I do doubt my reading comprehension sometimes.

Franck
11/3/2020 03:08:38 pm

NFPA 13 - 2019 Edition
20.6.1 Ceiling Slope.
The sprinkler system criteria specified in Chapters 20 through 25 are intended to apply to buildings with ceiling slopes not exceeding 2 in 12 (16.7 percent) unless modified by a specific section in Chapters 20 through 25.

It was 12.1.2 in 2016 Edition.

Jonathan Sullivan
11/3/2020 03:23:47 pm

Thank you for the reference. To conclude, as that section is for storage occupancies, NPFA 13 would still be applicable if the slope is greater than 2 in 12 in a non-storage occupancy.

Franck
11/3/2020 03:23:09 pm

It is one of the few "dark" areas of NFPA 13 where there is no proposed solution, either than just "out of the scope of NFPA 13".

I remember the good old time when I started this job and it was still allowed to have storage and sloped roofs. We just applied the 30% penalty on the remote area and that was it... And then, suddenly, it was not permitted anymore, with no solution !
Hard time !

For other occupancies, the same limit applies (16.7% or 1:6 or 2:12, or 9.4° which is all the same), but in that case you add 30%:

19.3.3.2.4 Sloped Ceilings.
The system area of operation shall be increased by 30 percent without revising the density when the following types of sprinklers are used on sloped ceilings with a pitch exceeding 1 in 6 (a rise of 2 units in a run of 12 units, a roof slope of 16.7 percent) in nonstorage applications:

(1)
Spray sprinklers, including extended coverage sprinklers listed in accordance with 11.2.1(4), and quick-response sprinklers

(2)
CMSA sprinklers

Reply
Chris
11/3/2020 10:29:39 am

There is some information still needed. You say you have a 12:12 pitch on your roof. What is the structure? Combustible or non-combustible? What is the distance from one eave to the other eave across the roof? Dry system or wet? If dry add an additional 30% onto your remote area. And due to the pitch of the roof, you will have an additional 30% area increase to your remote area.

The structure and construction will determine the head spacing. The distance is so you can see if can use a BB type head and avoid a lot of extra ssu's.

Good luck.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​February '21 Contributors!
    1. Dan W.
    2. Franck
    3. Jesse
    4. CJ B.
    ​5. Brian G.
    6. Mike
    7. Matt
    8. Casey M.
    9. Jay R.
    10. Glenn B.

    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Picture
Home - About - Blog - Contact - Exam Prep - Store

​Copyright © 2021 MeyerFire, LLC

The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About