MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • JOIN
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

How to Address Multiple Ducts Under 4-ft Wide?

4/9/2021

9 Comments

 
I have two large ducts 20-inches below sprinklers. One duct is 32-inches wide, the other is 42-inches wide. There is maybe 4- to 7-inches between them, only a couple inch gap on each side, running the length of a hallway.

The only rule for a continuous obstruction I can find says no coverage is needed below if the obstruction is under 4-feet. 

Individually these ducts aren't over 4-feet, but how does NFPA 13 address multiple obstructions like this?

​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
9 Comments
Mike
4/9/2021 08:08:25 am

If there is only a few inches between them and in between them, they essentially obstruct discharge to the whole hallway.

I would consider it one duct, possibly 2, and provide sprinklers beneath.

The argument could be made that the separation between ducts will not allow actuation of the heads but that depends on the AHJ.

If you want to try with one line, add 1" outlets for an additional line.

Reply
Dan Wilder
4/9/2021 08:13:32 am

While not considered a single continuous obstruction over 48", it "obstructs" up a large percentage of the available area from the ceiling/roof level sprinklers to floor coverage, additional sprinklers below would be warranted in this case (IMO).

Additional rules like "Obstructions against walls" show intent of protection below obstructions less than 48" wide but "technically" if the obstruction (or multiple) are below the 18" and do not exceed 48", the standard does not require additional protection (see 2019-A.10.2.7.1.2 for an example of a soffit or obstruction against a wall, more than 18" below the deflector, and up to 48" wide with the intent of not requiring additional protection).

I have not been able to apply a rule like this with an AHJ when the obstruction is up to 30" (See 2019-10.2.7.1.2(b)), but I have used the "intent" of 2019-10.2.7.1.2 to remove sprinklers from similar instances of obstructions against walls or by using the 3x rule per 2019-10.2.7.2.1.3.

Reply
Ray Ramos
4/9/2021 08:15:12 am

I think the obstruction rules (that has to do with size and proximity) will apply in this case, not the 4 feet rule but the other ones. Therefore you will need to add sprinkler above and below.

Reply
Jesse
4/9/2021 08:24:11 am

While you don't have a single contiguous obstruction over 48", effectively the 2 ducts act as an obstruction and will negatively affect the spray pattern from ceiling level sprinklers. I would protect underneath it.

Reply
Glenn Berger
4/9/2021 08:36:52 am

Rule of thumb - If you can't see the sprinkler from the floor, than it is obstructed and then sprinkler protection is required below the obstruction.

Reply
CJ Bonczyk
4/9/2021 09:05:42 am

A general rule of thumb in these instances (specifically corridors) I try and treat them as your would grouped obstruction similar to those addressed from FM global data sheets.

Reply
Art
4/9/2021 09:22:42 am

Maybe the intent of the code requirement for Open Grid Ceilings can be applied here. It requires 70% open and the thickness of the grid to not be greater than the clear openings. If you treat the ducts as the open grid ceiling then in your instance the gap between the ducts and between the walls does not comply and hence sprinkler coverage is obstructed and needs additional heads below the ducts. Curious what others think about this. Please let me know if you think I am way off on this.

Reply
Franck
4/9/2021 10:46:26 am

When I was still working for an insurance company and was reviewing installations (acting like an AHJ), I often asked for additional protection below grouped piping (or grouped cable trays).
If you ask yourself “would I need sprinklers below”, you already have the answer : Yes.
Your gut feeling is already that the situation is not that good.

The point of view of Art (above) is a practical one and can be used to solve such dilemma

Do not forget to consider also the distance between the obstruction and the sprinkler deflector. A 4 in. pipe can be an obstruction if located too close to the sprinkler

Reply
ken thackery
4/9/2021 02:00:27 pm

I have seen this go both ways with small grouped ducts and cable trays. It's best to stay within the code. Also I have referenced
A8.1.1(3)

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​May 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    Aba
    Ada
    Asce-7
    Asme-a171
    Astm-e1354
    Daily Discussion
    Design-documents
    En-12845
    Explosion-protection-prevention
    Fire-detection-and-alarm-systems
    Fire-dynamics
    Flammable-combustible-liquids
    Fm-global
    Human-behavior
    IBC
    Icc500
    IFC
    Imc
    Ipc
    Irc
    Iso
    Means Of Egress
    Nbc
    Nfpa-1
    Nfpa-10
    NFPA 101
    Nfpa-101
    Nfpa-11
    Nfpa-110
    Nfpa-1142
    Nfpa-1221
    Nfpa 13
    Nfpa-13
    Nfpa-13d
    Nfpa-13r
    Nfpa 14
    Nfpa-15
    Nfpa-16
    Nfpa-17a
    Nfpa-20
    Nfpa-2001
    Nfpa-214
    Nfpa 22
    Nfpa-220
    Nfpa 24
    Nfpa-241
    Nfpa-25
    Nfpa-25
    Nfpa-291
    Nfpa-291
    Nfpa-30
    Nfpa-30b
    Nfpa-33
    Nfpa-400
    Nfpa-409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • JOIN
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT