MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Flow Switch Won't Activate (Stay Engaged)

1/22/2019

12 Comments

 
Have a paddle flow switch for a wet system that is located on the first story riser. The riser serves the entire 3-story building.

When flowing an inspector's test on the first floor or even the third floor, the flow switch paddle only stays engaged for 10-12 seconds before cycling back and forth. Without keeping the engaged position, the alarm won't activate.

Has anyone come across this before? What remedies could help the flow switch operate properly?

Posted anonymously by a member for discussion. Discuss this | Subscribe
12 Comments
Bob Jeske
1/22/2019 10:14:58 am

I have seen this occur with backflow preventers installed back in the 1990's. The issue was that the backflow preventer's checks had too stiff springs installed on the backflow preventer. The manufacturer of the backflow sent us new check valves with softer springs in order for the flow switch to not cycle.

Reply
PETE
1/22/2019 11:18:13 am

Is there a pump with a pressure reducing valve on the discharge that is feeding this wet system?

Reply
JOE
1/22/2019 11:23:39 am

Nope, I was told it's just a city feed wet system.

Reply
PETE
1/22/2019 11:29:02 am

Here is what I am thinking. It ma be useful to read the Principles of Operation section on this cut sheet. https://www.systemsensor.com/en-us/Documents/WFD_Series_Manual_I56-0459.pdf

The pressure reducing valves that are commonly put on pump discharges have a "break-in" flow rate, beneath which they do not operate. That is why for a typical 8" pump discharge, a parallel flow path has to be made with 2" pipe and a 2" PRV with control valves for maintenance in order to accommodate a low flow rate scenario and still achieve the pressure reducing function. That's why it's an optimal scenario to just have the pump properly sized from the beginning, because this takes up a lot of real estate and it's a pain in the butt. But, this is the proper solution.

Another solution that is not proper, but more of a work-around... shorten the time delay on the flow switch. As you can in the linked document, the delay is not additive (cumulative). It resets when the flow drops. But, understand that the delay is designed to minimize false trips, and by lowering the time delay... what happens is the valve seats on the system valves wear out over time. Then flowing a hydrant or some other system will create a pressure differential across that valve and water will flow causing false trips.

Reply
PETE
1/22/2019 11:31:17 am

With no pump, it sounds like a partially closed valve on the system is causing friction loss. A damaged valve stem will do the same thing.

Kent Wise
1/22/2019 11:54:33 am

What you are experiencing is caused by too much trapped air in your system. When you flow an inspectors test the pressure drops low enough for the clapper to open on the alarm valve. Once the clapper opens a column of water the diameter of your main riser pipe starts to flow up into the riser. The mass in motion of the water column causes it to compress the air in your riser. That compression pressure eventually exceeds the city water pressure causing the clapper to be forced closed. The pressure has to drop below the city water pressure by additional flow out the inspectors test till the whole process starts over again.

We have seen this happen a lot on large risers, particularly in storage facilities. Your solution is to remove the trapped air by either manual or automatic air vents on the upper parts of the riser.

Reply
Mike
1/22/2019 12:42:03 pm

These are all great comments and I have learned some valuable insights.

I'd go with the easiest option to lower the retard feature if water surge isn't a problem.

Reply
Doug
1/22/2019 07:52:02 pm

I would generally recommend the same thing except he stated the paddle only stayed down for about 12 seconds.
If he adjusts the retard down to that level the will probably get a lot of false alarms.

Reply
Doug Funk
1/22/2019 05:19:59 pm

Back in the mid to late 90's we had a similar problem on many systems. Mainly it was the Ames 2000 backflow preventers. The spring on one of the checks was to stiff. The paddle on the flow switch would cycle exactly like you described.
You can call the backflow maker and they can help you with it.

Reply
James Armentor
1/24/2019 06:56:28 am

I've run into this same issue. I ended up loosening the tension on the return spring to get the switch to work. There is a small flat head screw at the top of the switch that holds the spring.

Reply
PETE
1/24/2019 08:29:25 am

Bear in mind that modifying the switch in a way that is inconsistent with the O&M sheet will void the listing. If the switch you're using doesn't describe this procedure and you are going to do it anyway, you might consider using Locktite or super glue on the screw threads so it doesn't fall out completely.

Reply
Randall link
6/12/2020 07:08:11 am

This issue is NOT caused by air trapped in the system!
That is something the manufacturer of the backflow told me when I ran into this problem. They claimed it WAS not the backflow issue. They were wrong.

It was caused by the springs being too strong for the amount of city pressure supplied.

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​Feb 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 30B
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT