MeyerFire
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About
Picture
ALL THINGS FIRE PROTECTION | SUBSCRIBE NOW

Floor Control Valves on Each Stair in Highrises?

1/14/2020

10 Comments

 
I have a question that a architect brought up to me.  He is saying that on a highrise (11 stories) it is a fire code requirement to have floor control valves on both stairwells. I cannot find anything that states this in any of the NFPA books. The square foot of each floor is small and is NOT separated into zones.

Does an 11-story high-rise require floor control valves on both stairwells?

​​​Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
10 Comments
Mike L
1/14/2020 07:54:17 am

Kind of sounds like the architect is confusing some code requirements.

A high-rise building is required to have a floor control valve at every floor. Assuming your systems are smaller than 52,000 sf, then only 1 control is required per floor.

A high-rise is typically required to have a standpipe hose valve in EACH required egress stairwell.

Reply
Mln3d
1/14/2020 09:44:50 am

Unless it is a justificational adopted code requirement. Some AHJ’s require floor controls to alternate that way if you need to drain down the system it doesn’t completely impair the system. i.e. if you only had floor controls on one stand pipe and drained a floor down.

Reply
Thomas Jones
1/14/2020 10:06:51 am

It isn't an FM building or Marriot correct? Marriot has their own fire code that requires a control valve in each stairwell.

Reply
Anon.
1/14/2020 10:32:37 am

Some AHJ's require this. Last I checked, City of Seattle for example has such a redundancy requirement, but in hydraulic calcs, one cannot take advantage of both supplies simultaneously.

Reply
Diaaeldin Mostafa DM
1/14/2020 11:05:05 am

As per NFPA13 , Only one sprinkler riser with floor control valve per 52,000 ft2 . If NFPA 101 is asking for stand pipes so it shall be provided inside firemen stair or smoke stop lobby or fire fighting lobby

Reply
RY
1/14/2020 11:43:49 am

How high is your building? It is not an NFPA requirement. It is in the IBC... in PA we follow IBC 2015 and it is on page 58. 403.3.1 Number of Sprinkler Risers and Systems Design...
"Each sprinkler system zone in buildings that are more than 420 feet in building height shall be supplied by no fewer than two risers. Each riser shall supply sprinklers on alternate floors. If more than two risers are provided for a zone, sprinklers on adjacent floors shall not be supplied from the same riser."
Hope this helps!

Reply
ML
1/14/2020 12:02:49 pm

Yes, heard of this too.

Reply
Thomas Reinhardt
1/14/2020 01:50:28 pm

If you use the International Fire Code Section 903.4.3 states that Approved supervised indicating valves shall be provided at point of connection to the riser on each floor in high-rise buildings.(2012 edition) This reference makes no reference to both stairwells. Mr.Mostafa is correct about square footage.

Reply
Brian Gerdwagen FPE
1/14/2020 03:56:00 pm

As stated, buildings over 420 feet to the highest occupied floor must have two risers. Each of these risers will supply alternate floors and the standpipe valves in the stair. One riser will supply all the even floors, the other all the odd floors. This way if an entire standpipe is shut down, only half the building will be out of service.

You can not add up the area of floors until you hit 52,000sqft and then section those floors off with a control valve. Three story buildings and taller generally require a control valve on every floor.

Reply
Jess L.
1/15/2020 12:08:04 pm

Check your building code.
It might tell you that each floor must be fed by a minimum of 2 risers, hence 2 flowswitches per floor, depending on the building height or # of floors.

Reply



Leave a Reply.

    Jump to: Daily Posts
    Jump to: PE Problems
    Picture
    Why Sponsor?

    Free Signup

    Subscribe and learn something new each day:
    I'm Interested In:

    Community

    Thank You to Our Top
    ​February '21 Contributors!
    1. Dan W.
    2. Franck
    3. Jesse
    4. CJ B.
    ​5. Brian G.
    6. Mike
    7. Matt
    8. Casey M.
    9. Jay R.
    10. Glenn B.

    Your Post

    SUBMIT A QUESTION

    The Toolkit

    Sprinkler Designer or Engineer?
    ​
    ​Get all of our tools, including the Sprinkler Database, Friction Loss Calculator, Fire Pump Analyzer and more:
    Picture
    FREE 30-DAY TRIAL
    GET THE TOOLKIT

    Filters

    All
    ABA
    ADA
    ASCE 7
    ASME A17.1
    Daily Discussion
    Design Documents
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    IFC
    Information Sources For Analysis
    IRC
    Means Of Egress
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 12
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 24
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 415
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 72
    NFPA 92
    NICET
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    UFC 3 600 01
    UFC 3-600-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    Archives

    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    Daily
    Daily discussions are open-ended fire protection, fire alarm, and life safety questions submitted anonymously for the benefit of sharing expertise and learning from other perspectives. Anyone can submit a question here:
    SUBMIT A QUESTION

    Exam Prep

    Picture
    2020 PE Prep Guide​
    ​(Available Now!)
    Picture
    PE Prep Series
    ​(Available Now!)
    2020 PE Prep Series
    Current Leaderboard
    ​(Click to enlarge)
    Fire Protection PE Exam Prep

    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Picture
Home - About - Blog - Contact - Exam Prep - Store

​Copyright © 2021 MeyerFire, LLC

The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Forum
  • PE Exam
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Prep Series
  • TOOLS
    • TOOLKIT (FREE TRIAL)
    • *TOOLKIT (PURCHASE)
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE*
    • FIRE FLOW CALCULATOR*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'19)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • REMOTE AREA ANALYZER
    • QUICK RESPONSE AREA REDUCTION
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • TOOLKIT
  • LOGIN
  • STORE
  • About