MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Weekly Exams
  • TOOLS
    • COMING SOON
    • BACKFLOW DATABASE (MEMBER)
    • CLOUD CEILING CALCULATOR
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE (MEMBER)
    • FLAMMABLE & COMBUSTIBLE LIQUIDS
    • FRICTION LOSS CALCULATOR
    • K-FACTOR SELECTOR
    • OBSTRUCTION CALCULATOR
    • SPRINKLER DATABASE (MEMBER)
    • THRUST BLOCK CALCULATOR
    • TOOLKIT (MEMBER)
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • LOGIN
  • STORE
Picture
A FORUM FOR PE EXAM PROBLEMS & DAILY DISCUSSION | SUBSCRIBE NOW

Does a Clean Agent Room Count as Protected?

11/26/2018

10 Comments

 
There's many code contingencies that depend on a fully-sprinklered building. If a room within a fully-sprinklered building is protected with a clean agent system (per NFPA 2001) and sprinklers are omitted from that room, does the building still meet the criteria to be considered fully protected and qualify for the numerous code contingencies?

Posted anonymously by a member for discussion. Discuss this | Subscribe.
10 Comments
Adam Hicks
11/26/2018 10:23:31 am

F

Reply
Kendall Nightlinger link
11/26/2018 10:33:38 am

The building would not count as Completely sprinkled, therefore would not count for allowances during building area analysis, nor for increases in MAQ.

From a FPE standpoint, clean agent is a "1 and done" discharge and does not provide for any of the effects that a sprinkler system does, nor for the required protection durations for building protection.

Clean agent systems are typically only equipment event protection as they try to prevent catastrophic equipment damage.

Good suppression design will provide a double interlock precaution system in addition to the clean agent system. Or a traditional wet pipe system, if there are concerns about water damage when there is no event, specify sidewall heads of an intermediate temperature with head guards.

This design provides extra time and a safety cushion with the intermediate temperature ordinary response heads.

This should alleviate All concerns about unnecessary damage to equipment as if we've created enough heat to activate an intermediate temperature ordinary response head, the equipment is toast anyways.

Reply
Michigan
11/26/2018 10:35:15 am

We are an IFC location, under IFC, a system complaint with NPFA 2001 without a NPFA 13 system in the room does not meet the requirements of fully sprinklered building. This also means that any Building Code "give" for a sprinklered building would not be applicable. I can try to find the code section when I return if that is necessary.

Reply
Michigan
11/26/2018 10:37:25 am

IFC 2015 edition, 903.3.1.1

Reply
sean
11/26/2018 11:07:41 am

904.2.1 Restriction on using automatic sprinkler system
exceptions or reductions. Automatic fire-extinguishing
systems shall not be considered alternatives for the purposes
of exceptions or reductions allowed for automatic sprinkler
systems or by other requirements of this code.

Reply
Pari
11/26/2018 10:51:34 am

IFC ,Section 904.2.1 : Automatic fire - extinguishing system shall not be considered alternative for the purposes of exceptions or reductions allowed for automatic sprinkler system or by other requirements of this code.

So installation of fire sprinkler system required, even the room or space is protection with clean agent.

Reply
Jennifer Olson
11/26/2018 11:14:30 am

What if it is a small telecom closet that the clean agent system is protecting? Would the telecom equipment be considered "electrical equipment" in which if the room is 2 hour rated and only houses dry electrical equipment, it does not require sprinklers and the clean agent is above and beyond?

Reply
Peter
11/26/2018 11:35:42 am

Jennifer, I think it is a stretch of the imagination to define a telecom room, a data processing room or other a low voltage control room as an electrical room for purposes of exempting it from sprinkler coverage under NFPA 13, even with the 2-hr rating and the other 3 criteria in 8.15 being met. The important thing to consider is the reasons we want the "fully sprinklered" designation is to keep fire flow demand low, to keep standpipe demands low, and to lessen the requirements for detection and others under the IFC. A key point to remember is that an exemption for a small area can be approved by the AHJ. If the AHJ is completely unwavering in his application of the code, then we can add a double-interlock preaction system with dry-pendent sprinklers to the clean agent protected area, and still have a reasonable degree of certainty that the room will stay dry. Yes, it will be at an additional expense to the owner, and yes- it will be beyond our control.

Reply
Jennifer Olson
11/26/2018 04:09:29 pm

Peter, thank you for your reply-it does help a lot. Since I cannot find a location in NFPA that defines "electrical equipment", what are the reasons that telecom equipment wouldn't be considered "electrical equipment" for this purpose? Is it that there would be more cables that would be a different fire hazard than just electrical wiring and machines?

Peter
11/27/2018 08:25:08 am

Jennifer,
It's a good question. Electrical Equipment is not defined in Ch. 3, and there is no further discussion in Annex A. I am not an absolute definitive source, but my informal interpretation is that it can be reasonably inferred from the terminology that electrical equipment is that equipment that serves the electrical power distribution for the site, or that equipment listed in the matrix under the electrical discipline. It can be further inferred that the reason the exemption from sprinkler coverage was included was to mitigate the loss of power to life safety equipment, such as an electric fire pump, due to sprinkler discharge water causing short circuits in electrical equipment. Also, if you look at 8.15.11.2. (2), the term "dry-type" most likely refers to transformers with coils that aren't filled with oil insulation. You might be able to convince an AHJ that it refers to all electrically-operated equipment (like an electric water heater closet). Of course, if you think that section of the standard could be better worded, there is a process by which you can recommend changes for the next edition.




Leave a Reply.

    Free Signup

    Subscribe for posts on PE Problems and Daily Discussions, straight to your inbox, for free:
    I'm Interested In:

    Community

    Thank You to Our Top January '19 Contributors:
    1. PETE
    2. Mike
    3. Wayne A.
    4. Brian G.
    ​5. Sean
    6. Sue B. 
    7. Nimal W.
    8. Dave L.
    9. James A.
    ​10. Dan W.

    Your Post

    Ask your question here  (members area)

    Search

    All-Access

    Get all-access to the downloadable Toolkit, Sprinkler Database, Ask-A-Question and more.
    Picture
    ALL-ACCESS

    Filters

    All
    Daily Discussion
    Explosion Protection & Prevention
    Fire Alarm
    Fire Detection And Alarm Systems
    Fire Dynamics
    Human Behavior
    Information Sources For Analysis
    Means Of Egress
    Passive Building Systems
    PE Prep Guide
    PE Sample Problems
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    Updates
    Water Based Fire Suppression
    Weekly Exams

    Archives

    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015

    Daily
    Daily discussion questions are open-ended questions posed by members for the benefit of sharing expertise and learning from other perspectives. Join as a member here.

    Exam Prep

    Picture
    2018 PE Prep Guide​
    ​
    Picture
    Weekly Practice Exams
    ​
    Picture
    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2018 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Weekly Exams
  • TOOLS
    • COMING SOON
    • BACKFLOW DATABASE (MEMBER)
    • CLOUD CEILING CALCULATOR
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE (MEMBER)
    • FLAMMABLE & COMBUSTIBLE LIQUIDS
    • FRICTION LOSS CALCULATOR
    • K-FACTOR SELECTOR
    • OBSTRUCTION CALCULATOR
    • SPRINKLER DATABASE (MEMBER)
    • THRUST BLOCK CALCULATOR
    • TOOLKIT (MEMBER)
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • LOGIN
  • STORE