MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Control Sprinklers with Valve on Same Level?

9/21/2022

7 Comments

 
Are sprinklers required to be controlled by valves which are physically located on the same floor level?

Are sprinklers in high ceilings OK to be controlled by valves on the upper level, or do they need to be controlled by a valve on the same level as the floor?

A project with a second, or even third-story high ceiling in a lobby would be one example of this scenario. Another example could be an entrance to an underground parking garage with an NFPA 13 system.

It makes sense for valves to control the sprinklers on the level the valve is on, just wondering about a specific code reference. I know about the exception for the top of stair shafts. Thank you everyone!

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
7 Comments
Dan Wilder
9/21/2022 08:13:04 am

Not to my knowledge, they just need to be labeled/identified as to what/where they serve and in an accessible/protected/heated location (8.3.1.8, 16.9.3.1.1, 16.9.3.4, 16.9.12.3 to name a few requirements, none say it has to be located on the same floor level)

Ummm...depends. Typically I have not taken this into account and run the sprinklers from the roof/deck level adjacent to the high ceiling (not the floor that they protect) however I have run lower zones up to high ceilings on projects with smoke control requirements. Garages are difficult because how do you define a floor level from a ramp and is the construction enough to provide separation to not activate adjacent zone/level sprinklers (I am also thinking of the last couple I have done where the ramp ran the length of the garage and was open to the 3rd/4th level underside as the ramp started from Level 1)?

I see it both ways but I will also defer the locating of the event to the fire alarm peeps, even with a single floor level having 52,000 FT², a water flow alarm at the riser tells me nothing as to the location within the building (yes I understand not every FA system includes addressable devices).

Reply
Franck
9/21/2022 08:27:50 am

Not a requirement to my knowledge

It is a good practice (especially from Insurance company recommended practices when looking to potential fires and consequences) to have the valve in the same sprinkler area, so that in case of impairment of the sprinkler system controlled by the valve you do not have other systems running in what has become an unprotected area.
But not mandatory

The best place is even to have the sectional valve as a PIV located 40 ft away from your building

Reply
Jesse
9/21/2022 08:50:43 am

Agree with Franck and Dan. Especially the part about knowing what level water is flowing on.

It can get goofy when the ground-floor area is less than 52,000 sq. ft. and we have multiple levels of protection effectively fed by a single riser.

Reply
Glenn Berger
9/21/2022 08:55:47 am

As long as everything is documented, approved by the AHJ and owner's rep(s), the isolation valve does not need to be on the same level as the sprinklers. None of us know what you building con figuration is, such that we would only be guessing on proper location of sprinkler control valve.

Reply
Munny Khan
9/21/2022 09:06:13 am

I've found this issue in my recent new role with this small company where we take note of all issues of every job (where in my old role with a big company there were individuals for every little thing). I've found with this is the zoning set up for the fire alarm panel and the importance to have it as simple as possible. I'll admit I'm still not 100% comfortable with it but the owner is excellent with it, so I'm learning. I haven't questioned a code reference for it but it is something in another code or standard that is fire protection related and can contribute to a better overall life safety system in the end.

Reply
Alex
9/21/2022 09:07:40 am

Nothing in the code I can think of that requires isolations to be installed on the floor. My first thought is a parking garage where each dry system is installed within a single room. Just want to make sure its clearly delineated and the fire department knows how to isolate the system in the case of a false activation.

Reply
Todd E Wyatt
9/21/2022 09:23:30 am

SUMMARY
Control valves are required at “each floor” in high-rise buildings (HRB).

EXPLANATION
The scoping Code (e.g. 2021 IBC) for Fire Protection (Chapter 9) includes (9) references to “control valves” (CV) … here are the applicable references pertaining to CV for automatic sprinkler systems (ASPS) :

Section 903 Automatic Sprinkler Systems
903.3 Installation Requirements
903.3.8 Limited Area Sprinkler Systems
903.3.8.4 Supervision
Control valves shall not be installed between the water supply and sprinklers unless the valves are of an approved indicating type that are supervised or secured in the open position.

903.4 Sprinkler System Supervision and Alarms
Valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures and waterflow switches on all sprinkler systems shall be electrically supervised by a listed fire alarm control unit.
Exceptions:
4. Jockey pump control valves that are sealed or locked in the open position.
5. Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position.
903.4.3 Floor Control Valves
Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor in high-rise buildings.

904.11 Automatic Water Mist Systems
904.11.2 Water Mist System Supervision and Alarms
904.11.2.3 Floor Control Valves
Floor control valves shall be provided as required for automatic sprinkler systems in accordance with Section 903.4.3.

904.13 Commercial Cooking Systems
904.13.4 Special Provisions for Automatic Sprinkler Systems
Automatic sprinkler systems protecting commercial-type cooking equipment shall be supplied from a separate, indicating-type control valve that is identified. Access to the control valve shall be provided.

The refernced standard for ASPS (2022 NFPA 13) includes (90) refernces to “control valve” and (13) refernces to “each floor” … of these, (3) include both :

Annex D — Sprinkler System Information from the 20182021 Edition of the Life Safety Code
This annex is not a part of the requirements of this NFPA document but is included for informational purposes only.
D.1.1.2 Special Structures and High-Rise Buildings.
High-rise buildings shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 101, Section 9.7. A sprinkler control valve and a waterflow device shall be provided for each floor. [101:11.8.3.1]
D.2 Life Safety Code.
D.2.2 Special Structures and High-Rise Buildings.
D.2.2.1 Design Criteria.
High-rise buildings shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7 of NFPA 101. A sprinkler control valve and a waterflow device shall be provided for each floor. [101:11.8.3.1]

Chapter 16 — Installation of Piping, Valves, and Appurtenances
16.11 System Attachments.
16.11.10* Alarm Attachments — High-Rise Buildings.
When a fire must be fought internally due to the height of a building, the following additional alarm apparatus shall be provided:
1. Each sprinkler system on each floor shall be equipped with a separate waterflow device. The waterflow device shall be connected to an alarm system in such a manner that operation of one sprinkler will actuate the alarm system, and the location of the operated flow device shall be indicated on an annunciator and/or register. The annunciator or register shall be located at grade level at the normal point of fire department access, at a constantly attended building security control center, or at both locations.

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​Jan 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT