MeyerFire
  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

A Check Valve Equivalent to BFP for Antifreeze?

10/19/2023

8 Comments

 
Our State Department of Natural Resources requires a double check on all water based sprinkler systems and an RPZ backflow when additives such as foam or antifreeze are used.

The rule is for containment. Meaning that the first available connection requires the backflow preventer.

With the details shown in NFPA 13 there are examples of check valves with a drilled clapper as well as an appropriate backflow preventer in the examples shown appear to be isolation devices.

NFPA 13 FIGURE 8.6.3.3 shows a backflow preventer and includes an expansion tank. 

If the entire building is protected by an RPZ the water department is satisfied.

When approaching the antifreeze pipe arrangement FIGURE 8.6.3.3 wouldn’t a swing check without a drilled hole be equal to the backflow preventer?

​​​​​​​​​​​​​​​​​​​​​​​​​Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
8 Comments
Mike
10/19/2023 08:09:23 am

I wouldn't say "equal" so much as "acceptable in lieu of". The check valve and drop loop minimizes but doesn't eliminate the possibility of dilution. NFPA doesn't mandate which arrangement you must pick. You really are weighing the cost to replace the premixed AF solution if it becomes too dilute vs the cost of an RPZ, expansion tank and forward flow testing the RPZ in the future. Premix AF is rather expensive, but so are RPZs and forward flow tests etc.

Reply
Dan Wilder
10/19/2023 08:28:22 am

No, a check valve does not perform the same as a backflow assembly. Even two check valves in line with each other do not perform the same.

The reason for a drilled hole in the clapper of a check valve is to allow thermal expansion of the anti-freeze back into the wet system, that is typically larger and can handle the pressure increase (essentially a very large expansion tank). Without that hole, a listed expansion tank or a pressure relief valve is required to handle that same thermal expansion.

8.6.3.1 would be for a connection to a wet system that "should" already have a pressure relief valve or at least a system that can handle the expansion. The 5' minimum drop is to prevent dilution of the nonfreezing solution as it interfaces with the wet system.

8.6.3.3 shows the backflow (or RPZ) with the expansion tank with no check valve (regardless of wet pipe supply) as there would be no loss of solution for thermal expansion/contraction thus no dilution.

8.6.3.4 shows the backflow without the expansion tank but with a pressure relief valve located above the incoming supply to allow pressure relief (loss of liquid) but would generally lose unmixed or lesser mixed solution due to the slower nature of pressure increase & drop (refill). You can also see that illustrated with the Water ->|<- Nonfreezing Solution delineation at the "A" valve.

Reply
SCHULMAN
10/19/2023 09:36:20 am

Dan's answer .... No, not the same.
Drilled holes in clappers went out of style many moons ago.

Reply
Anthony
10/19/2023 10:32:30 am

No. The purpose of a backflow device (BFD) is to prevent cross contamination with the water supply and check valves, even in series, does not do that. PRV's would work best of you are concerned about expansion issues but keep in mind a RPZ is still required for any hazardous system, not just foam or antifreeze.

Reply
Glenn Berger
10/19/2023 12:38:52 pm

A check valve is not a substitute for an approved backflow preventor.

Reply
RYAN HINSON
10/19/2023 01:04:18 pm

The location for the BFP required by your AHJ is indeed referencing the lead-in to your building and not at your antifreeze extension location. A backflow is already going to be required upstream of any non-potable system connection to a potable water supply per the applicable plumbing code for the jurisdiction (See IPC 2012 Section 608.16.4)...including any water-based sprinkler system.

Since you have antifreeze downstream of this connection, an RPZ would be required at the potable water interface upstream of any wet-pipe system per IPC Section 608.16.4.1. NFPA 13 requires 'listed' expansion chambers if the option consisting of "a backflow preventer with control valves" is provided per NFPA 13 Section 8.6.3.3 and Figure 8.6.3.3.

Perhaps it's an oversight, but I see nothing in NFPA 13 requiring a 'listed' BFP for separation between an auxiliary antifreeze system and a wet-pipe sprinkler system (as indicated in NFPA 13 (2022) Section 8.6.3.1.

As such, I want to agree with you that a check valve alone should be sufficient for the intent of this section...as currently written, however, Figure 8.6.3.4 includes mention of BOTH a 'check valve' AND a 'backflow preventer with control valves' where sprinklers are above valve A.

As indicated above, NFPA 13 does not require a listed backflow preventer at this location. One must go to NFPA 24 (2022) Section 5.4.2 to get the definition of a listed backflow prevention device. It says, "Where a backflow prevention device is installed to guard against possible cross-contamination of the public water system, it shall be listed for fire protection service."

Section 5.4.2.1 goes on to say, "Where a check valve or alarm check valve is permitted by the AHJ in lieu of a backflow preventer, it shall be listed for fire protection service."

Neither of these sections apply to the location your query is about IMO. Due to the fact that the BFP itself is optional under certain conditions per NFPA 13, this location is not required to meet the stipulations of plumbing code...since again, this is already handled upstream of the non-potable system piping.

Reply
Jesse
10/20/2023 08:21:22 am

No, not really. These aren't the same device

Reply
Mark
5/2/2024 10:12:41 pm

If you have an RP at the Anti-Freeze loop, are you required to have one at your riser as well? Or can you be ok with having a DC at the riser??

Reply



Leave a Reply.

    SUBMIT A QUESTION
    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top Dec '25 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A1171
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Blog Thread
    Daily Discussion
    Design-documents
    EN 12259-1
    EN 12845
    Explosion Protection
    Explosion-protection-prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable And Combustible Liquids
    Flammable-combustible-liquids
    FM Global
    Human-behavior
    IBC
    ICC 500
    IEBC
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 307
    NFPA 30B
    NFPA 31
    NFPA 33
    NFPA 37
    NFPA 400
    Nfpa-409
    Nfpa-415
    Nfpa-45
    Nfpa-495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 770
    NFPA 82
    NFPA 850
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    OSHA
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3-600-01
    UFC 4-021-01
    UFC 4-211-01
    UPC
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    January 2026
    December 2025
    November 2025
    October 2025
    September 2025
    August 2025
    July 2025
    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    SEE LEADERBOARD

    SEARCH THE FORUM

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is a NICET Recognized Training Provider and International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2016-2025 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • TOOLKIT
    • ALL TOOLS
    • BUY THE TOOLKIT
  • UNIVERSITY
    • ALL COURSES
    • JOIN THE UNIVERSITY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE PREP SERIES
    • PE Old Questions
  • LOGIN
    • TOOLKIT-ONLY LOGIN
    • UNIVERSITY LOGIN
  • STORE
  • OUR CAUSE
    • ABOUT MEYERFIRE
    • JOB OPENINGS
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT