MeyerFire
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Weekly Exams
  • TOOLS
    • COMING SOON
    • BACKFLOW DATABASE (MEMBER)
    • CLOUD CEILING CALCULATOR
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE (MEMBER)
    • FLAMMABLE & COMBUSTIBLE LIQUIDS
    • FRICTION LOSS CALCULATOR
    • K-FACTOR SELECTOR
    • OBSTRUCTION CALCULATOR
    • SPRINKLER DATABASE (MEMBER)
    • THRUST BLOCK CALCULATOR
    • TOOLKIT (MEMBER)
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • LOGIN
  • STORE
Picture
A FORUM FOR PE EXAM PROBLEMS & DAILY DISCUSSION | SUBSCRIBE NOW

Flange Connections on Suction Side of Fire Pump?

12/6/2018

4 Comments

 
Many fire pump arrangements I've seen include flanged fittings and pipe connections on the suction side of the fire pump. Is there a requirement for this?

Are grooved connections allowed for pipes and fittings on the suction side of the pump assembly?

Posted anonymously by a member for discussion. Discuss this | Subscribe
4 Comments
RichP
12/6/2018 10:24:31 am

I've always been taught that grooved fittings should not be used on suction pipes because of potential for negative pressures for which they are not designed or approved. Viking Johnson style couplings should be used to allow any flexibility.

Reply
ZS
12/6/2018 12:21:11 pm

As far as I know, there is no code requirement for flanged fittings in pump suction. NFPA 20 section 5.13.2 says grooved joints are acceptable. Section 5.14 does not limit this. (It says the suction piping is subject to NFPA 24, which allows grooved joints when used per their listing.)

I don't think negative pressures at the pump suction should be a big concern, but check with your manufacturer or supplier. I know that Victaulic does offer some vacuum-rated grooved couplings.

Reply
NEW PE
12/6/2018 02:34:10 pm

I have also heard that it should be avoided, putting grooved fittings/couplings on the suction side of a pump, but I have not seen evidence that their use poses any threat. Not only, as it is mentioned above, is there no code prohibiting their use, but if the suction side of a pump were to become low enough that it risked pulling the gasket out of the coupling, the pump would be seriously over-sized for the available water source such that it would be dangerously close to causing cavitation. I am not saying that gaskets haven't pulled out of couplings, but in those cases the couplings probably weren't installed properly. I mean, what pressure is that? The vapor pressure of water @ 25C is about 24 torr, or ~ 4.6 psia, which is roughly -10psi gauge. We size a pump based on the maximum demand for the FP systems, then based on the feasibility of the water supply in both terms of suitability and reliability we either use that supply or specify a suction tank. So, included in the supposition, "potential for negative pressure", that potential should not exist. Negative compared to what? Using the 20 psig benchmark imposed by some municipal purveyors on the suction side, even if there was some problem and the supply pressure approached the vaporization pressure, you have to take into account that pressure is only acting on the 1/16 " thickness of the gasket on the inside diameter pulling it in the radial direction. How much force could it possibly translate to given the limited area it is acting on? So, I just don't see it being a real problem. If someone is calling for them, yes, you should use a vacuum rated coupling, but you should also question the logic.

Reply
Franck
12/7/2018 10:22:10 am

Just one comment to ZS, it is now in section 4 and not 5.
Regarding the use of flanged fittings, it is clear in NFPA 20 that this is the "preferred" method (A.4.13.2), but is not the only one.
If you are looking to 4.14.6.5, strain relief is required when the pump and suction supply are on separate foundations. Normally, strain relief is achieved by using an expansion joint. But there are many installations where a series of grooved couplings achieve the same purpose.
You can have additional information if you have a look on NFPA 20 handbook (more pictures, more explanations than just NFPA 20 standard) at 4.16.6.5 (Strain Relief).

So, yes, flanged fittings are preferred (more robust), but grooved couplings are fully acceptable.

Reply



Leave a Reply.

    Free Signup

    Subscribe for posts on PE Problems and Daily Discussions, straight to your inbox, for free:
    I'm Interested In:

    Community

    Thank You to Our Top January '19 Contributors:
    1. PETE
    2. Mike
    3. Wayne A.
    4. Brian G.
    ​5. Sean
    6. Sue B. 
    7. Nimal W.
    8. Dave L.
    9. James A.
    ​10. Dan W.

    Your Post

    Ask your question here  (members area)

    Search

    All-Access

    Get all-access to the downloadable Toolkit, Sprinkler Database, Ask-A-Question and more.
    Picture
    ALL-ACCESS

    Filters

    All
    Daily Discussion
    Explosion Protection & Prevention
    Fire Alarm
    Fire Detection And Alarm Systems
    Fire Dynamics
    Human Behavior
    Information Sources For Analysis
    Means Of Egress
    Passive Building Systems
    PE Prep Guide
    PE Sample Problems
    Smoke Management Systems
    Special Hazard Systems
    Types Of Analysis
    Updates
    Water Based Fire Suppression
    Weekly Exams

    Archives

    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016
    June 2015

    Daily
    Daily discussion questions are open-ended questions posed by members for the benefit of sharing expertise and learning from other perspectives. Join as a member here.

    Exam Prep

    Picture
    2018 PE Prep Guide​
    ​
    Picture
    Weekly Practice Exams
    ​
    Picture
    PE Problems
    ​Visit July-October for daily Fire Protection PE Exam sample questions.

    Solutions are posted the day after posting.

    Comment with your solutions, questions or clarifications.

    Please note that questions posted are unofficial and in accordance with NCEES rules are intended to be similar to actual exam questions, not actual exam questions themselves.

    RSS Feed

Home - About - Blog - Contact - Exam Prep - Store
Picture
Copyright © 2018 MeyerFire, LLC
The views, opinions, and information found on this site represent solely the author shown and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a commission for orders placed elsewhere.
  • Blog
  • Daily
  • Exam Prep
    • CFPS Tools
    • NICET Tools
    • PE Forum & Errata
    • PE Problems
    • PE Store
    • PE Tools
    • PE Weekly Exams
  • TOOLS
    • COMING SOON
    • BACKFLOW DATABASE (MEMBER)
    • CLOUD CEILING CALCULATOR
    • FIRE PUMP ANALYZER
    • FIRE PUMP DATABASE (MEMBER)
    • FLAMMABLE & COMBUSTIBLE LIQUIDS
    • FRICTION LOSS CALCULATOR
    • K-FACTOR SELECTOR
    • OBSTRUCTION CALCULATOR
    • SPRINKLER DATABASE (MEMBER)
    • THRUST BLOCK CALCULATOR
    • TOOLKIT (MEMBER)
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • LOGIN
  • STORE