MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Distance from FDC to the Nearest Hydrant?

5/20/2019

18 Comments

 
For years on my code calls I have asked the Authority Having Jurisdiction what the maximum distance the nearest hydrant is allowed to be away from a building's fire department connection. I get answers that range from 50 feet to 400 feet or even more.

I was looking into the code basis behind this question, and the only applicable section that I found is the International Fire Code, Section 507.5.1.1 that addresses hydrant locations for standpipe systems:

"Buildings equipped with a standpipe system installed in accordance with Section 905 shall have a fire hydrant within 100 feet (30 480 mm) of the fire department connections. Exception: the distance shall be permitted to exceed 100 feet (30 480 mm) where approved by the fire code official."

Is there any relevant requirement for hydrants near fire department connections for sprinkler-only systems?

Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
18 Comments
Dan Wilder
5/20/2019 10:16:24 am

NFPA 14 - 19' Edition states in 6.4.5.4 the the maximum distance is 100' between the FDC and the nearest fire hydrant unless allowed by the AHJ to be further.

This goes back through at least the 07' edition using the same section.

Reply
JEN
5/20/2019 10:32:21 am

Dan, I think the person who posted is looking for a distance from FDC to hydrant for a sprinkler system only (NFPA 14 I understand is only for standpipe FDC's).

I am curious about this one as well and don't have an answer. I have always just done 100 feet even if it is just the sprinkler system, but I have no basis for this other than applying the standpipe code reference to sprinkler system as well.

Reply
Clifford Schulze
5/20/2019 10:40:21 am

There is no reason to believe that the distance would be any different for a sprinkler system only vs a standpipe system. The distance is related to the amount of hose the fire department needs to run to make the connection.

Reply
Jimmy Landmesser, Jr.
5/20/2019 11:03:50 am

Good afternoon,

Similarly to IFC (2012) Section 507.5.1, NFPA 1 (2018), Sections 18.5.2 and 18.5.3 have requirements for maximum distance of hydrants to the closest point on the building. It is 400 ft. for all buildings except one and two-family dwellings where 600 ft. is allowed.

NFPA 13 (2019), Section 16.12.5.7 requires the FDC to be located at the nearest point of FD apparatus accessibility or as approved by the AHJ.

So, unless approved by the AHJ, the FDC should not be located any further than 400 ft. except one- and two- family dwellings (600 ft. allowed). The expectation for a sprinkler system is that it automatically actuates and continues to flow at the minimum design for a specified amount of time (30 mins for light, 60-90 for ordinary and 90-120 mins for extra hazard). The standpipe system requires manual intervention and so closer fire department access is essential to limit response times, friction loss through hose lays, etc. I know a lot of jurisdictions reduce the minimum distance from ANY FDC to a hydrant, sprinkler or standpipe.

Reply
Nimal Tissa Wijetunga
5/20/2019 11:06:45 am

Fire Hydrant shall be positioned minimum of 6 meters and the maximum of 30 meters the facility it is going to be protected.

The breaching inlet or fire department connection shall be positioned withing 18 meters from the fire vehicle hard standing position.

In this situation, where hose can be fixed to the fire vehicle from the hydrant point where water can be drawn and and from the other side of the vehicle, a hose can be fixed to the fire vehicle and then fixed to the Breaching inlet here the fire vehicle can pump water to the stand pipe /sprinkler system in the building to replenish the availability of the water.

Reply
MODERATOR
5/20/2019 11:09:22 am

Nimal, please provide references when you cite requirements. It benefits everyone to discuss based on codes and standards. Thank you!

Reply
Nimal Tissa Wijetunga
5/20/2019 11:52:53 am

Pls refer Chapter 2 Section 6.3 and Chapter 2 Table 2.3 of UAE Fire and Life safety code of practise - 2011 edition. and NFPA 24 - Chapter 4 & 7 for information.

PETE
5/20/2019 12:34:37 pm

I would like to comment on something here that for those who are aware or are reviewing plans should be obvious, but it isn't obvious if you're inspecting a physical site or if you're just new to the industry. My comment is not meant to be patronizing.

If you have private service mains that are supplied by a pump and they feed a plurality of sprinkler systems as well as private hydrants, and the FDC is connected to the same private service main, it is not sufficient to have a hydrant from the same private service main within close proximity to the FDC. Drawing suction from the same water that the FDC discharges to will not allow for differential pressure to be created by the pumper. Regardless of whether the AHJ wants the hydrant to be 100 ft or 50 ft away, the hydrant that is designated the "FDC" hydrant, needs to be supplied from upstream of the fire pump suction and any backflow preventer. It's usually a city hydrant, but not always.

Reply
Jon Nisja
5/20/2019 02:13:28 pm

These comments are from an AHJ perspective. Without sounding too flippant, the answer to this and almost any code question is "it depends".

Our state has adopted the 2012 International Fire Code (IFC) and is in the process of updating to the 2018 IFC. This requirement was new to the 2012 IFC and was likely an attempt to correlate with NFPA 14 requirements for the same.

We have interpreted this to mean standpipe-only systems, not sprinkler system FDCs and not combination sprinkler/standpipe connections. For sprinkler or combination FDCs, we default to the maximum hydrant distance, which is 400 feet (IFC 507.5.1, as amended in our state).

Our rationale: history has shown us that sprinkler systems buy us time so the 100 ft. spacing from standpipe FDCs to hydrants is not necessary.

This is especially true with low and moderate hazard buildings. The vast majority of the 1,100 sprinkler system activations that we studied (76% of wet systems and 57% of dry systems) were extinguished with a single sprinkler. In 94% of the wet systems and 82% of the dry systems, the fire was extinguished with four or fewer sprinklers. Hence, the need to immediately connect to and charge the sprinkler FDC is greatly reduced.

That said, if this were a high hazard occupancy with high challenge fires where augmenting the water supply quickly was a concern, as an AHJ, I might ask for the hydrant to be located closer. Hence, the answer "it depends".

Reply
JAMES
5/20/2019 02:19:23 pm

Well said Jon! Not sure where your jurisdiction is, but that's a very thorough and well-thought answer to an answer that can feel arbitrary to designers. This is very helpful information to help foster quality discussions with AHJs in the future.

Reply
Jon Nisja
5/20/2019 03:15:40 pm

Thanks for your feedback, James. I am with the Minnesota State Fire Marshal Division. We are presently conducting research on our 1,100 + sprinkler saves in recent years (similar to the research studies that NFPA does on sprinkler saves). Hopefully that data will be published within a few months. Our preliminary data appears positive and we are happy to share our data with interested parties. jon.nisja@state.mn.us

p.s. We try to apply performance measures, experience, and common sense but not everyone likes that or has had the same experiences. People often forget that the beginning sections of all of the codes and standards talk about a reasonable level of fire protection, not an absolute "zero-risk" level of fire protection built on "what-if" scenarios

sean
5/20/2019 03:14:26 pm

I agree with most of what you said.

FDC to fire hydrant maximum spacing only applies to FDC serving a standpipe system.

I would apply the same restriction to a building with sprinklers and a standpipe system combination or otherwise. There is a subsection in NFPA 14 about combination systems and it does not provide relief for FDC spacing.

Reply
Chris Ferguson
5/21/2019 07:28:25 am

One thing I would like to add for those working in IFC locations, if the jurisdiction has adopted appendix C, the 400' and 600' distances can get altered. It will also give a more definitive amount of hydrants needed + spacing requirements. Sometimes it is a pain to apply however.

Reply
Nimal Tissa Wijetunga
5/21/2019 10:07:34 am

The question asked is the distance from FDC or Breaching inlet to the nearest Yard Fire Hydrant.

Stand pipe system is in the building and usually 1 inch or 11/2 inch in size and refers to NFPA 14.

Yard Fire Hydrant is in the yard with 21/2" outlets ad refers to NFPA 24.

Reply
Jim Ramsay
7/31/2020 03:48:18 pm

How's this for an obscure code reference?

NFPA 1141 8.1.3 * (2017 edition)
Where municipal-type water systems are available, fire department connections for sprinkler systems designed to NFPA 13 or NFPA 13R shall be located not more than 100 ft (30.5 m) along an approved path from a fire hydrant and shall be arranged so that hose lines can be readily and conveniently attached to the inlets without interference from any nearby objects, including buildings, signs, fences, posts, or other fire department connections.

Reply
Jason Burnett
10/5/2020 05:15:04 pm

Located with in the Seattle area, I am a LVL U installer and not a designer. We do employ designers for new systems, yet I specialize in cross connection control retro fits of double check valve assemblies on the fire system, which most are located below ground in vaults to be relocated above ground ( in enclosures ) due to the submersion in vaults below ground. ( It rains here, a little )
The location of the nearest city hydrant becomes a design review concern as the local AHJ states 50 LF. This would include 1 fire hose from the truck to the hydrant and 1 hose from truck to FDC. Most often it is acceptable to be under 100 LF of unobstructed path but never over the 100 LF.
If a DCDA unit is relocated from a below ground driving surface to an above ground, we have to be sure not to over extend the distance. Cost to relocate / add a hydrant is a driving factor for many customers to be compliant with the AHJ's requirements. .
No codes to reference, this has been more of open communication with the AHJ to physically see opportunities and make our best judgment on when and where an FDC should be placed.

Reply
Ninetta Violante
6/9/2022 02:41:13 pm

glad you found that.

Reply
CHRIS R
11/5/2020 11:21:16 am

From the time i used to work with Insurance Advisory Organization in Ontario, I can tell you that we were enforcing 150ft.(45m) from hydrant to the F.D.C. and max. 500ft.(15m) from the hydrant to any point on the perimeter of a building.

Reply



Leave a Reply.

    Picture
    Why Sponsor?

    ALL-ACCESS

    Picture
    GET ALL OUR TOOLS

    SUBSCRIBE

    Subscribe and learn something new each day:
    I'm Interested In:

    COMMUNITY

    Top ​Jan 2023 Contributors
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    Picture
    SEE LEADERBOARD

    YOUR POST

    SUBMIT A QUESTION

    PE EXAM

    Get 100 Days of Free Sample Questions right to you!
    SIGN ME UP!

    FILTERS

    All
    A117.1
    ABA
    ADA
    ASCE 7
    ASME A17.1
    ASTM E1354
    Daily Discussion
    Design Documents
    EN 12845
    Explosion Protection & Prevention
    Fire Detection And Alarm Systems
    Fire Dynamics
    Flammable & Combustible LIquids
    FM Global
    Human Behavior
    IBC
    ICC-500
    IFC
    IMC
    IPC
    IRC
    ISO
    Means Of Egress
    NBC
    NFPA 1
    NFPA 10
    NFPA 101
    NFPA 11
    NFPA 110
    NFPA 1142
    NFPA 1221
    NFPA 13
    NFPA 13D
    NFPA 13R
    NFPA 14
    NFPA 15
    NFPA 16
    NFPA 17A
    NFPA 20
    NFPA 2001
    NFPA 214
    NFPA 22
    NFPA 220
    NFPA 24
    NFPA 241
    NFPA 25
    NFPA 291
    NFPA 30
    NFPA 33
    NFPA 400
    NFPA 409
    NFPA 415
    NFPA 495
    NFPA 497
    NFPA 5000
    NFPA 502
    NFPA 54
    NFPA 55
    NFPA 654
    NFPA 68
    NFPA 70
    NFPA 701
    NFPA 72
    NFPA 75
    NFPA 82
    NFPA 855
    NFPA 90A
    NFPA 92
    NFPA 96
    NICET
    OBC
    Passive Building Systems
    PE Prep Guide
    PE Prep Series
    PE Sample Problems
    Poll
    Smoke Management
    Special Hazard Systems
    UFC 3 600 01
    UFC 3-600-01
    UFC 4-021-01
    Updates
    Water Based Fire Suppression
    Weekly Exams


    ARCHIVES

    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    November 2016
    October 2016
    July 2016
    June 2016


    PE PREP SERIES

    Fire Protection PE Exam Prep
    SEE LEADERBOARD

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • About
    • Catalog
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT