Is there a complete list of points I need to monitor with fire alarm for a diesel driven fire pump?
I can't seem to find a comprehensive/definitive list in NFPA 20 or 72, but I would imagine at least one or more of the following would need to be monitored by code: fire pump running, primary sensor failure, low fuel level, main disconnect in "off" position, main disconnect in "manual" position, low pump room temperature, flowmeter left on, loss of AC power supply, loss of battery (load side of DC overcurrent), over-speed, and engine trouble (low oil, over temp, other?). Posted anonymously for discussion. Discuss This | Submit Your Question | Subscribe
2 Comments
Under the 2019 edition of NFPA 20, Section 12.4.2 provides the requirement for conditions to be monitored on a diesel engine-driven fire pump. Sections 12.4.1.3 and 12.4.1.4 identify the conditions that are to be remotely indicated when the fire pump room is not constantly attended.
Reply
10/10/2019 12:02:16 pm
Agree with Craig....NFPA 20 does indeed provide a detailed list, separated by LOCAL indicatators, and REMOTE indication. Section 12.4.1.3 and 12.4.1.4 provide requirements for local indicators; ie indicator IN the pump room. You usually don't need to worry too much about these as any NFPA 20 compliant controller will have these built in.
Reply
Leave a Reply. |
ALL-ACCESSSUBSCRIBESubscribe and learn something new each day:
COMMUNITYTop November '24 Contributors
YOUR POSTPE EXAMGet 100 Days of Free Sample Questions right to you!
FILTERS
All
ARCHIVES
December 2024
PE PREP SERIES |