MeyerFire
  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT
Picture

Where Should Exits be Located?

3/6/2023

0 Comments

 
MeyerFire University | LS183.06
By Steven Barrett, PE
RESOURCES
  • One-Page Summary [PDF]
​
CODE & STANDARD REFERENCES
  • IBC – 2021: Section 1007.1.1 – Separation of Exits or Exit Access Doorways by 1/2 x the Room Diagonal
  • IBC – 2021: Section 1007.1.1(E2) – Separation by 1/3 x the Room Diagonal for Sprinklered Building
  • IBC – 2021: Section 1010.2 – Door operation requirements
  • IBC – 2021: Section 1028.2 – Exit Discharge to the exterior

TRANSCRIPT

Where should exits be located?

INTRODUCTION

So far in this series, we’ve covered exits, types of exits, the different segments of exit access, exits and exit discharge, and in our last segment, we talked about arranging exits so that they’re far enough apart from each other.

In this segment, let’s talk specifically about where the exits need to be located.

ARRANGEMENT

Exits should be sufficiently separated so that a fire would not render both exits unusable. Ideally, exits should be located near the exterior of the building. And exits should be designed so they are readily available to all building occupants. Finally, they should be arranged so that an occupant doesn’t have to travel too far to reach them. Let’s dive in.

HOW MUCH SEPARATION?

This “sufficiently separated” concept sounds awfully familiar. It sure is. In the previous video, we talked about exit access doors. Specifically, we were looking at large rooms or a suite of rooms. Because those rooms have 50 or more occupants, there must be two ways out (two exit access doors). These two ways out must be far enough apart so that a fire wouldn’t block both doors.

This minimum separation distance is one-half the diagonal of the room in nonsprinklered buildings and one-third the diagonal in fully sprinklered buildings. The same concept also applies to exits.

AN EXAMPLE

Let’s imagine a multistory building with two interior exit stairs near the core of the building.

Around the perimeter of the building are various office tenants.

The only way out of the building is through one of these interior exit stairs.

Now, to maximize leasable space, the developer wants the core to be as small as possible.

This means bringing the stairs closer together. So if a fire were to occur in one of the tenant spaces, both exit stairs would be available.

But what if the fire occurred in the core?

Could it create a situation where both exits are blocked? What minimum distance must the two stairs be separated by? In this case, it is one half the diagonal of the building.

Just like exit access, in a fully sprinklered this is reduced to one-third the diagonal of the building.

WHY LOCATE EXITS NEAR EXTERIOR?

Why should interior exit stairs ideally be located near the exterior of the building?

Well for one, it makes the one-half or one-third diagonal exit separation easier.

The other reason is because of exit discharge. If you recall, we said as soon as an occupant enters the interior exit stair, they have exited the building.

From a life safety perspective, this is true but from a literal or intuitive standpoint, they are still in the physical structure that we call a building. Eventually, the stair will discharge the occupant somewhere. Either the stair will discharge the occupant directly to the outside or they will discharge the occupant back into the building.

Which is safer? Well, directly outside.

The building is on fire, after all. But that would mean the stairs have to be located along the exterior wall.

Because requiring all interior exit stairs to discharge directly to the exterior is restrictive from a design perspective, the code permits up to 50% of interior exit stairs to discharge back into the building, provided several requirements are met.

We’ll dive into this in much greater detail in a later video. The takeaway is that locating interior exit stairs on exterior walls is ideal, where feasible, due to exit separation and discharge requirements.

AVAILABILITY TO OCCUPANTS

Exits also must be available to all occupants.

What does available mean? It means the occupant has access to the exit.

If there is no pathway, then the occupant cannot reach the exit.

If the pathway has doors that are locked or under control of another tenant, then these exits are not available.

This goes hand in hand with the concept of exit access that we discussed in the previous video. It’s a bit of chicken and egg, but typically the exits are set first and the exit access is designed around it. But…there are situations where additional exits must be added late in design.

One example might be a public lobby of an otherwise secure building. It has only one set of doors for entry and exit. Occupants are not permitted to go beyond the building lobby without proper security credentials, even in an emergency.

So, this means that for occupants in the lobby, there is a single exit.

But if this lobby has more than 50 occupants, two exit access doors (or two exits in this example) are required, meaning a second exit would have to be added.

DISTANCE TO EXITS

Finally, exits should be located so that occupants don’t have to travel too far to get to them. 

If we assume the building is on fire, then every second counts in an evacuation. The further away the exit is, the longer it will take for an occupant to get out. So, how far is too far? What is the maximum travel distance?

We’ll dive into measurement of travel distance to exits in later videos. It depends on occupancy but generally, the range is between 100 feet to 400 feet for the maximum distance an occupant is permitted to travel before reaching the nearest exit. 

SUMMARY

So, how should exits be located?

They should be located far enough apart from each other, so that a fire would not render both exits unusable. Ideally, exits are located near the exterior of the building. 

Exits should be readily accessible to all buildings occupants. And the distance an occupant has to travel to reach an exit shouldn’t be excessive. 

We’re going to get through some examples on exit arrangement in the next segment and get some practice working through those. 

From there, we’re going to cover how we help occupants know where exits are located.

I’m Steven Barrett, this is MeyerFire University.
0 Comments



Leave a Reply.

    Sentry Page Protection
    Please Wait...

    FULL CATALOG

    SEARCH

    FILTER BY:

    All
    By: Aaron Johnson
    By: Al Yakel
    By: Ben Brooks
    By: Chris Campbell
    By: Chris Logan
    By: David Stacy
    By: Edward Henderson
    By: Franck Orset
    By: Joe Meyer
    By: Kelsey Longmoore
    By: Steve Frederick
    By: Steven Barrett
    By: Tyler Mobley
    Category: Business
    Category: Documents
    Category: Fire Alarm
    Category: Fundamentals
    Category: Life Safety
    Category: Smoke Control
    Category: Suppression
    Category: Tools
    Course
    Crossword
    Exercise
    Level: Advanced
    Level: Intermediate
    Level: Introductory
    On-Demand Course
    Simulation
    Workshop

    ARCHIVES:

    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021

    INSTRUCTORS:

    Aaron Johnson, CFEI
    Al Yakel, SET
    ​Chris Campbell, PE
    ​Chris Logan, CFPS, RSE
    ​
    David Stacy, PE
    Ed Henderson, PE
    ​Franck Orset
    Joe Meyer, PE
    Steve Frederick

    RSS Feed

Picture
​Home
Our Cause
The Blog
The Forum
PE Exam Prep
The Toolkit

MeyerFire University
​Pricing
Login
​Support
Contact Us
Picture

MeyerFire.com is a startup community built to help fire protection professionals shine.
Our goal is to improve fire protection practices worldwide. We promote the industry by creating helpful tools and resources, and by bringing together industry professionals to share their expertise.

​MeyerFire, LLC is an International Code Council Preferred Education Provider.

All text, images, and media ​Copyright © 2023 MeyerFire, LLC

We respect your privacy and personal data. See our Privacy Policy and Terms of Service. 
The views, opinions, and information found on this site represent solely the author and do not represent the opinions of any other party, nor does the presented material assume responsibility for its use. Fire protection and life safety systems constitute a critical component for public health and safety and you should consult with a licensed professional for proper design and code adherence.

Discussions are solely for the purpose of peer review and the exchange of ideas. All comments are reviewed. Comments which do not contribute, are not relevant, are spam, or are disrespectful in nature may be removed. Information presented and opinions expressed should not be relied upon as a replacement for consulting services. Some (not all) outbound links on this website, such as Amazon links, are affiliate-based where we receive a small commission for orders placed elsewhere.

  • Blog
  • Forum
  • THE TOOLKIT
    • SUBMIT AN IDEA
    • BACKFLOW DATABASE*
    • CLEAN AGENT ESTIMATOR*
    • CLOUD CEILING CALCULATOR
    • DOMESTIC DEMAND*
    • FIRE FLOW CALCULATOR*
    • FIRE PUMP ANALYZER*
    • FIRE PUMP DATABASE*
    • FRICTION LOSS CALCULATOR
    • HANGER SPACER*
    • IBC TRANSLATOR*
    • K-FACTOR SELECTOR*
    • NFPA 13 EDITION TRANSLATOR ('19 ONLY)
    • NFPA 13 EDITION TRANSLATOR ('99-'22)*
    • LIQUIDS ANALYZER*
    • OBSTRUCTION CALCULATOR
    • OBSTRUCTIONS AGAINST WALL*
    • PLUMBING FIXTURE COUNTS
    • QUICK RESPONSE AREA REDUCTION
    • REMOTE AREA ANALYZER*
    • SPRINKLER DATABASE*
    • SPRINKLER FLOW*
    • SYSTEM ESTIMATOR*
    • TEST & DRAIN CALCULATOR
    • THRUST BLOCK CALCULATOR
    • TRAPEZE CALCULATOR
    • UNIT CONVERTER
    • VOLUME & COMPRESSOR CALCULATOR
    • WATER STORAGE*
    • WATER SUPPLY (US)
    • WATER SUPPLY (METRIC)
  • UNIVERSITY
    • ABOUT
    • CATALOG
    • CONTENT LIBRARY
  • PE Exam
    • PE Forum & Errata
    • PE Store
    • PE Tools
    • PE Prep Series
    • PE 100-Day Marathon
  • LOGIN
  • PRICING
    • SOFTWARE & TRAINING
    • STORE
  • THE CAUSE
    • ABOUT US
    • BECOME AN INSTRUCTOR
    • HELP/SUPPORT