BM: Problem 174 I also believe should not include Type V (000) per NFPA 101 Table 12.1.6. 1-story is not permitted for the given occupant load.
MF: Sorry I should have combined this with the previous email. For problem 174 when I look at the table Type V (000) construction 1 story non-sprinklered is only allowed for 300 or less people. If its sprinklered then 1story is allowed for less than 1000 people and 2 stories for less than 300 people. Am I looking at this wrong?
2 Comments
Chris Campbell
9/22/2020 10:34:20 am
Agree with the comment, Type V(000) would not be permitted since the assembly occupant load is greater than 300.
Reply
Joe Meyer
9/23/2020 11:07:00 am
Agreed, thanks for the input. 2020 Errata updated: www.meyerfire.com/errata
Reply