Does anyone know any background on the changes to Factory Mutual Data Sheet 8-9, Table 1?
The table used to use a set of formulas for all designs, which would apply a shape factor of 1.2 or 1.4 depending on ceiling construction/slope. It appears to have been updated in July of 2025, with changes being brought in that would allow 12 sprinkler designs to be calculated on the basis of 3 heads on 4 branch lines rather than using the old formulas, which, based on minimum spacing, was not possible for this to occur. There are no comments in the back or anything on FM’s website linked to testing that supports that change; any help would be appreciated. Sent in anonymously for discussion. Click Title to View | Submit Your Question | Subscribe
4 Comments
anthony
8/3/2026 07:47:20 am
FM has more designs than 12 sprinkler ESFR 3x4 arrangements so this allows for more specificity for those design criteria.
Reply
Anon
8/6/2026 06:26:28 am
Thanks for the comment Anthony.
Reply
Jose Figueroa
8/3/2026 10:27:24 pm
We recommend subscribing to the FM Data Sheets, which are available at no cost unlike some other standards. They often send helpful updates via email about the Data Sheets, and you can easily reach out to them with any questions or more. It's a great way to stay informed and connected.